  • Hello! I am an AI chatbot trained to assist you with the FläktGroup LQVE Intake and exhaust air section for outdoor Installation guide. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
Fläkt Woods 9138 GB 2011.10 1 Rätt till ändringar förbehålls
Installation instruction
Intake and exhaust air section LQVE
– outdoor execution
Size 60 62 64 71 73 80 82 84
Torque Nm
b = 1–5 15 10 14 13 15 14 16 18
b = 6, 7 10 11 9 11 9 13 10 11
Number of
damper motors
b = 1–5 1 2 2 2 2 2 2 2
b = 6, 7 1 1 2 1 2 1 2 2
Installation of damper actuators
Damper actuator LQAZ-11 (accessory) is installed in
accordance with the following installation.
Fig. 2
Actuator
Actuator LQAZ-11 is installed in accordance with Fig.
2 and the manufacturer’s instructions.
The angle of rotation of the damper actuator must be
limited to 90°.
Commissioning
Fig. 1
 IMPORTANT!
Ensure that the intake damper is open
during commissioning of the fan.
The maximum permissible pressure
difference over the damper = 1000 Pa.
Max. torque for damper actuator: 30 Nm.
/