Fläkt Woods 9138 GB 2011.10 1 Rätt till ändringar förbehålls
Installation instruction
Intake and exhaust air section LQVE
– outdoor execution
Size 60 62 64 71 73 80 82 84
Torque Nm
b = 1–5 15 10 14 13 15 14 16 18
b = 6, 7 10 11 9 11 9 13 10 11
Number of
damper motors
b = 1–5 1 2 2 2 2 2 2 2
b = 6, 7 1 1 2 1 2 1 2 2
Installation of damper actuators
Damper actuator LQAZ-11 (accessory) is installed in
accordance with the following installation.
Fig. 2
Actuator
Actuator LQAZ-11 is installed in accordance with Fig.
2 and the manufacturer’s instructions.
The angle of rotation of the damper actuator must be
limited to 90°.
Commissioning
Fig. 1
 IMPORTANT!
Ensure that the intake damper is open
during commissioning of the fan.
The maximum permissible pressure
difference over the damper = 1000 Pa.
Max. torque for damper actuator: 30 Nm.