FläktGroup DC_10606GB 20221117_R0 Specifications are subject to alteration without notice.
5
Volumetric flow control device 327VMZ - Modbus implementation guide
MODBUS REGISTERS
2.2 SERVICE VALUES
The values are used only when commissioning the damper or monitoring status. Do not write values constantly to the Service registers.
Number Name Address Data type Value range Read/write Description Default
104 Software version 103 WORD 1...65535 RShows software version -
105 Service information 104 WORD 1...65535 RShows status of the actuator
See status register table. -
106 Min. value relative 105 WORD 0...10 000 R/W Sets Min value [%] 0... 100.00% 0
107 Max. value relative 106 WORD 0...10 000 R/W Sets Max value [%] 0... 100.00% 10 000
109 Bus fail position 108 WORD 0...5 R/W
Sets the actuator position when no communica-
tion on bus within 120 seconds
’0’ = Last setpoint. De-activates bus fail position
function if analog control is used.
’1’ = Closed position at bus monitoring timeout
’2’ = Open position at bus monitoring timeout
’3’ = Min flow at bus monitoring timeout
’4’ = Btw flow at bus monitoring timeout
’5’ = Max flow at bus monitoring timeout
0
119 Btw. value relative 118 WORD 0...10 000 R/W Sets Btw value [%] 0...100.00% 5 000
120 Btw. value absolute 119 WORD 0...10 000 R/W Sets Btw value in selected unit [l/s, m
3
/h] Size
depended
121 Min. value absolute 120 WORD 0...10 000 R/W Sets Min value in selected unit [l/s, m
3
/h] 0
122 Max. value absolute 121 WORD 0...10 000 R/W Sets Max value in selected unit [l/s, m
3
/h] Size
depended
123 Setpoint source and
analog output mode 122 WORD 0...3 R/W
Sets setpoint reference and analog output mode
0
Value of the
register
Setpoint
source
Value of Output
signal U
0Setpoint from
analog input Y
Analog to actual
flow 0(2)...10V
1
Setpoint from
register 1 or 21
Analog to actual
flow 0(2)...10V
2
Setpoint from
register 1 or 21
Value from
register 11
3Setpoint from
analog input Y
Value from
register 11
131 Modbus address 130 WORD 1-247 R/W Sets device Modbus address 1
132 Sensor status 131 WORD 1...65535 RShows sensor status
See sensor status register table. -
133 Installation
parameter 132 WORD 50...150 R/W Sets Inst. parameter 100
202 Air volume flow unit 201 WORD 0...1 R/W Sets air volume flow unit
0 = l/s, 1 = m
3
/h 0
542 Automatic calibration 541 WORD 0...1 R/W ’0’ = Automatic calibration on
’1’ = Automatic calibration off 1
569 Modbus communication
parameter 568 BYTE 0...32 R/W
Sets Modbus communication settings
See Modbus comm. settings register table.
Note: Stored value starts from 0.
13
570 Modbus response delay 569 BYTE 0...255 R/W
Some master devices require a delay when
switching from transmission mode to reception
mode. This response delay is added to 3.5 char-
acters at the end of the message. The delay time
is adjustable in steps of 3 ms x 0...255.
0
770 Mode register 769 WORD 1...65535 RShows override status
See Mode register table. -