FläktGroup Optivent Ultra ULSA, ULDA Installation guide

Type
Installation guide

FläktGroup Optivent Ultra ULSA, ULDA is a high-performance air volume damper designed for precise airflow control in various HVAC systems. With its advanced features, it offers accurate and efficient air management solutions for demanding applications:

  • Precise Airflow Control: Equipped with ultrasonic measurement technology, it delivers highly accurate and stable airflow measurement, ensuring optimal system performance.

  • Wide Application Range: Suitable for a variety of applications, including constant air volume (CAV), variable air volume (VAV), and smoke control systems.

  • Modbus Communication: Enables seamless integration with building management systems (BMS) for centralized control and monitoring.

FläktGroup Optivent Ultra ULSA, ULDA is a high-performance air volume damper designed for precise airflow control in various HVAC systems. With its advanced features, it offers accurate and efficient air management solutions for demanding applications:

  • Precise Airflow Control: Equipped with ultrasonic measurement technology, it delivers highly accurate and stable airflow measurement, ensuring optimal system performance.

  • Wide Application Range: Suitable for a variety of applications, including constant air volume (CAV), variable air volume (VAV), and smoke control systems.

  • Modbus Communication: Enables seamless integration with building management systems (BMS) for centralized control and monitoring.

INSTALLATION, COMMISSIONING, MAINTENANCE
OPTIVENT® ULTRA VAV DAMPER
with 227VMZ-MB
FläktGroup DC_10055GB 20221219_R6 Specifications are subject to alteration without notice.
2
OPTIVENT
®
ULTRA - Installation, Commissioning, Maintenance
INSTALLATION
Installation Size Minimum
safety distance
Velocity in the duct (m/s)
0,5 - 1 > 1 > 4
In the straight tube
100 - 630 3 x D ± 8% or 1 l/s ± 5% ± 4%
Type of flow disturbance
(only applies to a single type of disturbance) Installation case Size Minimum
safety distance
Velocity in the duct (m/s)
0,5 - 1 > 1 > 4
Bend
100 - 400 0 x D ± 10% or 1 l/s ± 8% ± 6%
100 - 250
315, 400
0 x D ± 10% or 1 l/s ± 8% ± 6%
T-piece 1
100 - 400 0 x D ± 10% or 1 l/s ± 8% ± 6%
100 - 250
315 - 400
0 x D
1 x D
± 10% or 1 l/s ± 8% ± 6%
100 - 125
160 - 250
315 - 400
0 x D
1 x D
-
± 10% or 1 l/s ± 8% ± 6%
MEASURING ACCURACY
For the best possible accuracy, it is recommended to install the air volume damper so that it is preceded by a straight duct, at least 3 x D safety dis-
tance.
Valid when the damper blade opening is > 30%. Recommended maximum air velocity with shorter than 3 x D safety distances is 8 m/s.
Adequate safety distance is recommended after the type of flow disturbance (3 x D).
With sizes 500 and 630 should the safety distance be at least 3 x D.
The motor/ultrasound shall be placed as shown on the pictures above.
*) recommended position
*)
When using the minimum safety distance after the type of flow disturbance, the installation parameter must be set according to the commissioning
section (p.9-10) to achieve the accuracies.
FläktGroup DC_10055GB 20221219_R6 Specifications are subject to alteration without notice.
3
OPTIVENT
®
ULTRA - Installation, Commissioning, Maintenance
INSTALLATION
Type of flow disturbance
(only applies to a single type of disturbance) Installation case Size Minimum
safety distance
Velocity in the duct (m/s)
0,5 - 1 > 1 > 4
T-piece 2
100 - 400 0 x D ± 10% or 1 l/s ± 8% ± 6%
T-piece 3
100 - 250
315 - 400
0 x D
2 x D
± 10% or 1 l/s ± 8% ± 6%
100 - 160
200 - 400
0 x D
2 x D
± 10% or 1 l/s ± 8% ± 6%
100 - 250
315 - 400
0 x D
2 x D
± 10% or 1 l/s ± 8% ± 6%
T-piece 4 (lid)
100 - 250
315 - 400
0 x D
2 x D
± 10% or 1 l/s ± 8% ± 6%
100 - 400 2 x D ± 10% or 1 l/s ± 8% ± 6%
MEASURING ACCURACY
When using the minimum safety distance after the type of flow disturbance, the installation parameter must be set according to the commissioning
section (p.9-10) to achieve the accuracies.
Valid when the damper blade opening is > 30%. Recommended maximum air velocity with shorter than 3 x D safety distances is 8 m/s.
Adequate safety distance is recommended after the type of flow disturbance (3 x D).
With sizes 500 and 630 should the safety distance be at least 3 x D.
The motor/ultrasound shall be placed as shown on the pictures above.
Lid
FläktGroup DC_10055GB 20221219_R6 Specifications are subject to alteration without notice.
4
OPTIVENT
®
ULTRA - Installation, Commissioning, Maintenance
INSTALLATION
Type of flow disturbance
(only applies to a single type of disturbance) Installation case Size Minimum
safety distance
Velocity in the duct (m/s)
0,5 - 1 > 1 > 4
Reducer 2:1 and 3:1
100 - 400 0 x D ± 10% or 1 l/s ± 8% ± 6%
Round sound absorber
BDER-30, -40, -44 and -60
100 - 400 0 x D ± 10% or 1 l/s ± 8% ± 6%
Rectangular sound absorber
BDER-70, -71, -72 and -73
100 - 400 0 x D ± 10% or 1 l/s ± 8% ± 6%
3 x D
3 x D
3 x D
Valid when the damper blade opening is > 30%. Recommended maximum air velocity with shorter than 3 x D safety distances is 8 m/s.
Adequate safety distance is recommended after the type of flow disturbance (3 x D).
With sizes 500 and 630 should the safety distance be at least 3 x D.
The motor/ultrasound shall be placed as shown on the pictures above.
MEASURING ACCURACY
When using the minimum safety distance after the type of flow disturbance, the installation parameter must be set according to the commissioning
section (p.9-10) to achieve the accuracies.
FläktGroup DC_10055GB 20221219_R6 Specifications are subject to alteration without notice.
5
OPTIVENT
®
ULTRA - Installation, Commissioning, Maintenance
INSTALLATION
Type of flow disturbance
(only applies to a single type of disturbance) Installation case Size Minimum
safety distance
Velocity in the duct (m/s)
0,5 - 1 > 1 > 4
ETPR fire damper
100 - 315
400
0 x D
3 x D
± 10% or 1 l/s
± 8% or 1 l/s
± 8%
± 5%
± 6%
± 4%
ELPO flue & ETPR-E-1 fire damper
125
(ELPO flue: 250)
4 x D
*)
2 x D
0 x D
± 8% or 1 l/s
± 10% or 1 l/s
± 5%
± 8%
± 4%
± 6%
*) recommendation
NOTE! Fire damper shaft parallel to the ELPO flue.
MEASURING ACCURACY
When using the minimum safety distance after the type of flow disturbance, the installation parameter must be set according to the commissioning
section (p.9-10) to achieve the accuracies.
FläktGroup DC_10055GB 20221219_R6 Specifications are subject to alteration without notice.
6
OPTIVENT
®
ULTRA - Installation, Commissioning, Maintenance
INSTALLATION
WIRING
1
2
34A
B
1 2 3 4 A B
24 VAC
24 VDC –
24 VAC ~
24 VDC +
0...10 V
2...10 V
0...10 V
2...10 V
Modbus
RS485
Operating voltage Control signal Feedback signal
blue
(BU)
brown
(BN)
black
(BK)
grey
(GY)
white
(WH)
RS485 A
RS485 B
RS485 Common
230 V
24 V AC/DC
A B G G0 A B G G0 A B G G0 A B G G0
Actuator Actuator Actuator Actuator
230 V
24 V AC/DC
A B G G0 A B G G0 A B G G0 A B G G0
RS485 A
RS485 B
RS485 Common
Actuator Actuator Actuator Actuator
FläktGroup DC_10055GB 20221219_R6 Specifications are subject to alteration without notice.
7
OPTIVENT
®
ULTRA - Installation, Commissioning, Maintenance
WIRING
Parallel control
INSTALLATION
+
-
24
V AC/DC
Modbus
RS485
~
12
BNBU
∆p M
GY
0-10 V
2-10 V
0-10 V
2-10 V
GT-MB
EMSF UL(S,D)A
227VMZ-MB
4 A
WH WH
B A
WH WH
B12
BNBU BK
3
GY
4
Vmax S (GT) = Vmax (227VMZ) Vmin (227VMZ) = 0
EMSF control
BKBU
0...10/2...10
V DC
M
odbus RS485
24
V AC/DC
1
M
234
BN GY
A
WH
B
WH
A
WH
B
WH
BKBU
1
M
234
BN GY
BU BN BK GY
227VMZ-MB
Y/ U/
ZPP
~
0-10V - CLOSE if Vm
in=0
2-10V - CLOSE
Vmin
Vbtw
Vmax
Open
~
Y
U
AC
24 V
DC 24
V+
DC 0...10V
DC 2...10V
DC 0...10V
DC 2...10V
1N4007
A
B
Modbus RS485
A
WH
B
WH
BKBU
24
V AC/DC
1
M
234
BN GY
CAV constant air volume Forced control
Vmax = 0
Vmin = Setpoint
FläktGroup DC_10055GB 20221219_R6 Specifications are subject to alteration without notice.
8
OPTIVENT
®
ULTRA - Installation, Commissioning, Maintenance
FACTORY SETTINGS
COMMISSIONING
Transmission mode RTU
Address 1
Transfer rate 19200 bps
Data bits 8
Parity Even
Stop bits 1
Delay 0 ms
Response time 10 ms + Delay
Unit l/s
Vmax Vnom
Vmin 0 m/s
Signal range setup 0 - 10 V
1Air flow unit selection
Flow
2Vmax value setup
Vmax example:
Vmax = 100 l/s
3Vmin value setup
Vmin example:
Vmin = 50 l/s
4Input signal range setup
Mode
5Modbus address setup
Adr Adr = 1 - 247
example: Adr = 10
6Modbus communication
parameters setup
Adr Adr = "2in"
Factory setting:
Adr = 5 *
7Installation parameter
setup
Inst Factory setting:
Inst = 100
(straight tube 2D
Edit
10°
Edit
10°
Edit
10°
Edit
10°
Edit
10°
Edit
10°
Edit
10°
Edit
10°
Edit
10°
Edit
10°
Edit
10°
Edit
10°
Edit
10°
Edit
10°
l/s
m3/h
l/s
m3/h
Note!
1 250 l/s
0-10 V
12 500 l/s
2-10 V
l/s
m3/h
l/s
m3/h
l/s
m3/h
l/s
m3/h
l/s
m3/h
FläktGroup DC_10055GB 20221219_R6 Specifications are subject to alteration without notice.
9
OPTIVENT
®
ULTRA - Installation, Commissioning, Maintenance
COMMISSIONING
Bend Min. safety
distance
Installation
case
Size
100 125 160 200 250 315 400
0 x D
1
2
3
4
126
132
125
126
119
120
121
118
125
122
120
125
120
122
119
120
116
120
119
124
115
116
122
121
1 x D
1
2
3
4
125
123
124
124
113
112
113
116
122
120
119
121
118
120
118
118
110
118
110
122
112
110
118
119
2 x D
1
2
3
4
117
117
113
113
108
106
107
108
118
117
116
117
115
117
116
116
106
116
108
111
105
104
114
113
With sizes 500 and 630 should the safety distance be at least 3 x D.
T-piece 1 Min. safety
distance
Installation
case
Size
100 125 160 200 250 315 400
0 x D
1
2
3
125
132
128
125
120
119
114
128
122
126
120
117
122
120
1 x D
1
2
3
122
129
125
119
118
118
112
115
123
115
114
113
113
113
109
118
117
114
111
2 x D
1
2
3
117
125
119
110
110
110
108
108
115
110
109
109
109
111
107
115
113
109
109
With sizes 500 and 630 should the safety distance be at least 3 x D.
T-piece 2 Min. safety
distance
Installation
case
Size
100 125 160 200 250 315 400
0 x D
1 & 4
2
3
102
96
96
98
95
93
98
96
98
96
95
100
101
100
99
97
98
99
103
98
98
1 x D
1 & 4
2
3
101
102
99
99
99
95
98
100
98
101
97
97
101
97
100
102
99
100
100
102
101
2 x D
1 & 4
2
3
102
100
98
96
96
96
99
99
101
100
100
99
100
99
100
101
99
102
103
103
101
With sizes 500 and 630 should the safety distance be at least 3 x D.
T-piece 3 Min. safety
distance
Installation
case
Size
100 125 160 200 250 315 400
0 x D
1 & 4
2
3
131
126
130
121
117
114
117
118
124
131
122
123
115
1 x D
1 & 4
2
3
119
117
118
115
115
113
112
113
114
113
116
112
109
2 x D
1 & 4
2
3
114
111
110
108
107
107
108
111
112
106
109
105
109
108
108
108
108
109
105
104
105
With sizes 500 and 630 should the safety distance be at least 3 x D.
INSTALLATION PARAMETER SETTINGS (INST)
1
2
2
2
2
3
1
1
1
4
4
4
3
3
3
FläktGroup DC_10055GB 20221219_R6 Specifications are subject to alteration without notice.
10
OPTIVENT
®
ULTRA - Installation, Commissioning, Maintenance
T-piece 4 (lid) Min. safety
distance
Installation
case
Size
100 125 160 200 250 315 400
0 x D
1 & 4
2
3
134
130
122
119
115
120
124
126
122
119
1 x D
1 & 4
2
3
130
132
115
115
110
114
116
117
115
116
2 x D
1 & 4
2
3
119
122
123
109
109
109
106
108
109
110
109
108
110
109
111
112
110
105
105
104
106
With sizes 500 and 630 should the safety distance be at least 3 x D.
Rectangular sound absorber
BDER-70, -71, -72 and -73 Min. safety
distance
Installation
case
Size
100 125 160 200 250 315 400
0 x D
1
2
3
96
89
96
94
93
95
94
92
99
96
97
98
97
101
99
100
100
100
100
100
100
1 x D
1
2
3
98
93
101
96
94
97
98
94
100
98
99
98
98
99
99
100
100
100
100
100
100
2 x D
1
2
3
101
95
102
99
96
99
101
97
101
98
99
100
99
99
100
100
100
100
100
100
100
With sizes 500 and 630 should the safety distance be at least 3 x D.
ETPR fire damper Min. safety
distance
Installation
case
Size
100 125 160 200 250 315 400
0 x D
1
2
3
111
112
110
97
95
103
94
101
104
99
101
105
96
106
109
95
96
106
1 x D
1
2
3
111
111
110
95
95
103
95
100
102
100
101
103
97
100
101
100
97
102
2 x D
1
2
3
106
110
106
98
95
100
97
98
99
101
102
101
102
102
99
99
98
99
With sizes 400 - 630 should the safety distance be at least 3 x D.
ELPO flue & ETPR-E-1 fire damper
Size Installation
case
Minimum safety distance
4 x D 2 x D 0 x D
125 1 - 4 100 111 Do not use! *)
*) Note that a double disturbance creates a lot of turbulence and a straight tube before the damper must be used.
COMMISSIONING
INSTALLATION PARAMETER SETTINGS (INST)
2
1
4
3
3 x D
Lid
FläktGroup DC_10055GB 20221219_R6 Specifications are subject to alteration without notice.
11
OPTIVENT
®
ULTRA - Installation, Commissioning, Maintenance
COMMISSIONING
MODBUS COMMUNICATION PARAMETERS (ADR)
Display number Baudrate Parity Stop bits
19600 none 2
29600 even 1
39600 odd 1
419200 none 2
5* 19200 even 1
619200 odd 1
738400 none 2
838400 even 1
938400 odd 1
10 9600 none 1
11 19200 none 1
12 38400 none 1
FläktGroup DC_10055GB 20221219_R6 Specifications are subject to alteration without notice.
12
OPTIVENT
®
ULTRA - Installation, Commissioning, Maintenance
The product can be (mechanically) cleaned with nylon brush when the
ductwork is cleaned as shown in the pictures below. No other mainte-
nance is required.
MAINTENANCE
FläktGroup DC_10055GB 20221219_R6 Specifications are subject to alteration without notice.
13
OPTIVENT
®
ULTRA - Installation, Commissioning, Maintenance
WWW.FLAKTGROUP.COM ULSA, ULDA 10055
»
Learn more on www.flaktgroup.com
or contact one of our oices
FG_DC_10055GB_ULSA_ULDA_IN-MA_20221219_R6 © Copyright 2022 FläktGroup
FläktGroup is the European market leader for smart and energy eicient Indoor Air
and Critical Air solutions to support every application area. We oer our customers
innovative technologies, high quality and outstanding performance supported by
more than a century of accumulated industry experience. The widest product range
in the market, and strong market presence in 65 countries worldwide, guarantee
that we are always by your side, ready to deliver Excellence in Solutions.
PRODUCT FUNCTIONS BY FLÄKTGROUP
Air Treatment | Air Movement | Air Diusion | Air Distribution | Air Filtration
Air Management & ATD’s | Air Conditioning & Heating | Controls | Service
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14

FläktGroup Optivent Ultra ULSA, ULDA Installation guide

Type
Installation guide

FläktGroup Optivent Ultra ULSA, ULDA is a high-performance air volume damper designed for precise airflow control in various HVAC systems. With its advanced features, it offers accurate and efficient air management solutions for demanding applications:

  • Precise Airflow Control: Equipped with ultrasonic measurement technology, it delivers highly accurate and stable airflow measurement, ensuring optimal system performance.

  • Wide Application Range: Suitable for a variety of applications, including constant air volume (CAV), variable air volume (VAV), and smoke control systems.

  • Modbus Communication: Enables seamless integration with building management systems (BMS) for centralized control and monitoring.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI