Columbia Lighting CRN2 Installation guide

Type
Installation guide
CRN2 Instruction Manual
CRN2
WET LOCATION HIGH BAY
DAMP LOCATION HIGH BAY WHEN USING OPTIONAL EMERGENCY LED DRIVER (BATTERY BACKUP)
currentlighting.com/columbialighting
© 2022 HLI Solutions, Inc. All rights reserved. Information and specifications subject to change
without notice. All values are design or typical values when measured under laboratory conditions.
Page 1 of 3
Rev 07/20/22
COL_CRN2_inst_R01
As for the wire color of DIM
+ and DIM - , pls check the
lamp label !
Application:
For use in settings such as warehouses, manufacturing plants, sporting
venues, big-box retailers, and similar locations.
CAUTION:
1. Read all instructions before starting installation.
2. This product must be installed in accordance with the applicable
installation codes by a qualified electrician familiar with the
construction and operation of the product and the hazards involved.
3. Disconnect power at circuit breaker of fuse before starting installation.
4. To avoid injury, wear gloves during installation.
5. To reduce the risk of electrical shock and product damage, do not
install this luminaire during rain or other storms.
6. Do not test luminaire using an electric generator before installation.
7. Use minimum 75°C Supply Wires.
Instructions:
ROUND LED HIGH BAY
INSTALLATION INSTRUCTIONS
Installation using the Eyebolt Hook:
1. Thread the enclosed eyebolt hook into the top of the luminaire housing,
and tighten securely. Tighten the set screw to prevent the eyebolt from
loosening. (See Figure 1)
2. Use a chain, cable, mounting hook or other mounting hardware to
suspend the luminaire. Make sure the mounting hardware is securely
attached to a stationary structure, and is strong enough to safely suspend
the luminaire. (See Figure 2)
3. Refer to the Wiring Diagram to make electrical connections.
Figure 1 Figure 2
SAVE THESE INSTRUCTIONS
Wiring Diagram
Luminaire
Supply Line Black Wire
Supply Ground Green/ Bare Wire
Supply Neutral White Wire
Violet Wire
For dimming wires, use class 1 wiring methods.
Cap dimming wires (separately) if not used.
0-10V Dim +
(pos)
Grey Wire
0-10V Dim - (neg)
3-conductor cord
(for all models)
has white, black,
and green
conductors
2-conductor cord
(for non-sensor
models only) has
violet and grey
conductors
EYEBOLT
HOOK
NOTE: Components shown in images are
representative only and may vary based
on the conguration ordered.
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be followed including the following:
a. READ AND FOLLOW ALL SAFETY INSTRUCTIONS.
b. Do not use outdoors.
c. Do not mount near gas or electric heaters.
d. Equipment should be mounted in locations and at heights where it will not readily be subjected to tampering by unauthorized personnel.
e. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
f. Do not use this equipment for other than intended use.
WARNINGS
1. This product contains chemicals known to the state of California to cause cancer, birth defects and/or other reproductive harm. Thoroughly wash
hands after installing, handling, cleaning, or otherwise touching this product.
2. Contact Current Lighting for information and direction before relamping or replacing this light fixture.
3. Disconnect power before installing or servicing. Observe all precautions usually followed when dealing with high voltage equipment when installing
or servicing this light fixture.
4. The product must be installed in accordance with the applicable installation code by a person familiar with the construction and operation of the
product and the hazards involved.
5. Protect all wiring connections with approved insulators rated 600V / 150°C (by others).
6. Selected fixture voltage must match supply line voltage.
SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE
Upon receipt of this fixture, thoroughly inspect it for any damage. If any is found, the carrier should be notified and held accountable.
WIRING DIAGRAM
APPLICATION
For use in settings such as warehouses, manufacturing plants, sporting venues, big-box retailers and similar locations.
STEP 1
Thread the enclosed eyebolt hook into the top of the luminaire
housing, and tighten securely. Tighten the set screw to prevent the
eyebolt from loosening (see Figure 1).
STEP 2
Use a chain, cable, mounting hook or other mounting hardware to
suspend the luminaire. Make sure the mounting hardware is securely
attached to a stationary structure and is strong enough to safely
suspend the luminaire (see Figure 2).
STEP 3
Refer to the Wiring Diagram to make electrical connections.
EYEBOLT HOOK INSTALLATION
Figure 1 Figure 2
Installaon Instrucon
Cautions:
1. Can not use the electric generator to test the LED lamp.
2. Please abide by related country, regional and local law and regulations when install this fixture.
3. Please turn off the power before installation or maintenance.
4. Proper earth grounding is required to ensure safety.
Notice:
1. To avoid possibility of electrical shock or fire, the installation personnel must have professional electric
knowledge.
2. Please wear gloves to avoid injury before installation.
3. If any smoke or spark of the wire happened, please turn off the power immediately and notify relevant
personnel.
Attention:
1. Please check if there is any damage during shipping. If so, please contact manufacturer timely.
2. Please read the installation instruction carefully to check whether all the accessories are complete.
After confirmation, then install the fixture according to installation steps.
Installation Methods: Hook Mount, Ceiling Mount, 1/2"NPT Mount.(Please choose
the most suitable installation method for the purchased produdct as per your needs)
Hook Mount:
Figure 1
Figure 2
1. Screw the hook into the fixture, tighten and fix
it. (figure 1)
2. Hang the fixture on the ceiling hook or chain.
(figure 2)
3. After installation, connect the wire of the fixture
to the mains according to local wiring rules, ensure
the connection is stable and make good protection
on the connection.
Wiring Diagram & Instruction:
This led highbay light can be equipped with optional DC
motion sensor, and is available with 1-10V dimming
fuction, with following 3 dimming solutions:
1. 1-10V dimming,
2. Intelligent dimming with DC motion sensor,
3. Pre-install tool-free handling DC motion sensor
dimming module, and choose dimming function freely.
Installation Instruction
Cautions:
1. Can not use the electric generator to test the LED lamp.
2. Please abide by related country, regional and local law and regulations when install this fixture.
3. Please turn off the power before installation or maintenance.
4. Proper earth grounding is required to ensure safety.
Notice:
1. To avoid possibility of electrical shock or fire, the installation personnel must have professional electric
knowledge.
2. Please wear gloves to avoid injury before installation.
3. If any smoke or spark of the wire happened, please turn off the power immediately and notify relevant
personnel.
Attention:
1. Please check if there is any damage during shipping. If so, please contact manufacturer timely.
2. Please read the installation instruction carefully to check whether all the accessories are complete.
After confirmation, then install the fixture according to installation steps.
Installation Methods: Hook Mount, Ceiling Mount, 1/2"NPT Mount.(Please choose
the most suitable installation method for the purchased produdct as per your needs)
Hook Mount:
Figure 1
Figure 2
1. Screw the hook into the fixture, tighten and fix
it. (figure 1)
2. Hang the fixture on the ceiling hook or chain.
(figure 2)
3. After installation, connect the wire of the fixture
to the mains according to local wiring rules, ensure
the connection is stable and make good protection
on the connection.
Wiring Diagram & Instruction:
This led highbay light can be equipped with optional DC
motion sensor, and is available with 1-10V dimming
fuction, with following 3 dimming solutions:
1. 1-10V dimming,
2. Intelligent dimming with DC motion sensor,
3. Pre-install tool-free handling DC motion sensor
dimming module, and choose dimming function freely.
Base model CRN (no sensor)
Purple (Dim+)
Pink (Dim-)
Black and White (DC12V+)
Green GND
Green GND
Black ACL
Black ACL
White ACN
White ACN
CRN with sensor
Luminaire
Violet Wire
For dimming wires, use class 1 wiring methods.
0-10V Dim +
(pos)
Grey Wire
0-10V Dim -
(neg)
Black Wire
Supply Line
upply Neutral White Wire
upply Ground Green/Bare Wire
12V+ Pink Wire
Black & White Wire
Purple Wire Pink Wire
CRN2
WET LOCATION HIGH BAY
DAMP LOCATION HIGH BAY WHEN USING OPTIONAL EMERGENCY LED DRIVER (BATTERY BACKUP)
CRN2 Instruction Manual
currentlighting.com/columbialighting
© 2022 HLI Solutions, Inc. All rights reserved. Information and specifications subject to change
without notice. All values are design or typical values when measured under laboratory conditions.
Page 2 of 3
Rev 07/20/22
COL_CRN2_inst_R01
STEP 1
To install the luminaire using ½” (NPS) conduit, use the optional yoke mount
bracket.
STEP 2
Remove the nut from threaded electrical conduit (½” NPS, provided by others (see
Figure 8).
STEP 3
Install the mounting bracket on the threaded conduit, and reinstall the conduit nut.
Tighten securely (see Figures 9 & 10).
STEP 4
Refer to the Wiring Diagram to make electrical connections.
STEP 1
To install the luminaire using ¾” (NPS) conduit, use the optional snap hook.
STEP 2
Install the snap hook on threaded electrical conduit (¾” NPS, provided by others
—see Figure 11).
STEP 3
Clip the snap hook onto the enclosed eyebolt hook (see Figure 12).
STEP 4
Refer to the Wiring Diagram to make electrical connections.
INSTALLATION USING 1/2" NPS CONDUIT:
INSTALLATION USING 3/4" NPS CONDUIT:
Ceiling-Mounted Installation (using optional Yoke Mount Bracket):
1. To install the optional yoke bracket on the luminaire, begin by attaching
the L-shaped yoke mounting brackets on the luminaire. (See Figure 3)
2. Next, attach the yoke bracket to the L-shaped yoke mounting brackets.
(see Figure 4)
3. Using the yoke mount bracket as a template, mark and drill holes in the
ceiling or other solid structure to which the luminaire will be attached.
(See Figure 5)
4. Use a hammer to install the expansion screws into the drilled holes. (See
Figure 6)
5. Using the enclosed nuts, install the yoke mounting bracket onto the
expansion screws, and securely tighten the nuts. (See Figure 7)
6. If the luminaire will be installed at an angle (see step 8), tighten the
mounting bracket adjustment bolts only partially tight. Otherwise,
securely tighten these bolts.
7. If the luminaire will be installed at an angle, rotate the luminaire up to 50
in either direction (100total adjustability), and securely tighten the
mounting bracket adjustment bolts.
8. Refer to the Wiring Diagram to make electrical connections.
Figure 4
Figure 3
Figure 6Figure 5
Figure 8Figure 7
Mounting Bracket
Adjustment Bolts
100°
Installation Using ½” (NPS) Conduit:
1.To install the luminaire using ½” (NPS) conduit, use the optional yoke
mount bracket.
2.Remove the nut from threaded electrical conduit (½” NPS, provided by
others). (See Figure 9)
3.Install the mounting bracket on the threaded conduit, and reinstall the
conduit nut. Tighten securely. (See Figures 10 & 11)
4.Refer to the Wiring Diagram to make electrical connections.
Installation Using 3/4” (NPS) Conduit:
1.To install the luminaire using ¾” (NPS) conduit, use the optional
snap hook.
2.Install the snap hook on threaded electrical conduit (¾” NPS,
provided by others). (See Figure 12)
3.Clip the snap hook onto the enclosed eyebolt hook. (See Figure
13)
4.Refer to the Wiring Diagram to make electrical connections.
Figure
11
Figure 10Figure 9
Figure 12 Figure 13
Ceiling-Mounted Installation (using optional Yoke Mount Bracket):
1. To install the optional yoke bracket on the luminaire, begin by attaching
the L-shaped yoke mounting brackets on the luminaire. (See Figure 3)
2. Next, attach the yoke bracket to the L-shaped yoke mounting brackets.
(see Figure 4)
3. Using the yoke mount bracket as a template, mark and drill holes in the
ceiling or other solid structure to which the luminaire will be attached.
(See Figure 5)
4. Use a hammer to install the expansion screws into the drilled holes. (See
Figure 6)
5. Using the enclosed nuts, install the yoke mounting bracket onto the
expansion screws, and securely tighten the nuts. (See Figure 7)
6. If the luminaire will be installed at an angle (see step 8), tighten the
mounting bracket adjustment bolts only partially tight. Otherwise,
securely tighten these bolts.
7. If the luminaire will be installed at an angle, rotate the luminaire up to 50
in either direction (100total adjustability), and securely tighten the
mounting bracket adjustment bolts.
8. Refer to the Wiring Diagram to make electrical connections.
Figure 4
Figure 3
Figure 6Figure 5
Figure 8Figure 7
Mounting Bracket
Adjustment Bolts
100°
Installation Using ½” (NPS) Conduit:
1.To install the luminaire using ½” (NPS) conduit, use the optional yoke
mount bracket.
2.Remove the nut from threaded electrical conduit (½” NPS, provided by
others). (See Figure 9)
3.Install the mounting bracket on the threaded conduit, and reinstall the
conduit nut. Tighten securely. (See Figures 10 & 11)
4.Refer to the Wiring Diagram to make electrical connections.
Installation Using 3/4” (NPS) Conduit:
1.To install the luminaire using ¾” (NPS) conduit, use the optional
snap hook.
2.Install the snap hook on threaded electrical conduit (¾” NPS,
provided by others). (See Figure 12)
3.Clip the snap hook onto the enclosed eyebolt hook. (See Figure
13)
4.Refer to the Wiring Diagram to make electrical connections.
Figure
11
Figure 10Figure 9
Figure 12 Figure 13
Figure 8
Figure 11
Figure 9 Figure 10
Figure 12
STEP 1
To install the optional yoke bracket on the luminaire, begin by attaching
the L-shaped yoke mounting brackets on the luminaire (see Figure 3).
STEP 2
Next, attach the yoke bracket to the L-shaped yoke mounting brackets
(see Figure 4).
Ceiling-Mounted Installation (using optional Yoke Mount Bracket):
1. To install the optional yoke bracket on the luminaire, begin by attaching
the L-shaped yoke mounting brackets on the luminaire. (See Figure 3)
2. Next, attach the yoke bracket to the L-shaped yoke mounting brackets.
(see Figure 4)
3. Using the yoke mount bracket as a template, mark and drill holes in the
ceiling or other solid structure to which the luminaire will be attached.
(See Figure 5)
4. Use a hammer to install the expansion screws into the drilled holes. (See
Figure 6)
5. Using the enclosed nuts, install the yoke mounting bracket onto the
expansion screws, and securely tighten the nuts. (See Figure 7)
6. If the luminaire will be installed at an angle (see step 8), tighten the
mounting bracket adjustment bolts only partially tight. Otherwise,
securely tighten these bolts.
7. If the luminaire will be installed at an angle, rotate the luminaire up to 50
in either direction (100total adjustability), and securely tighten the
mounting bracket adjustment bolts.
8. Refer to the Wiring Diagram to make electrical connections.
Figure 4
Figure 3
Figure 6Figure 5
Figure 8Figure 7
Mounting Bracket
Adjustment Bolts
100°
Installation Using ½” (NPS) Conduit:
1.To install the luminaire using ½” (NPS) conduit, use the optional yoke
mount bracket.
2.Remove the nut from threaded electrical conduit (½” NPS, provided by
others). (See Figure 9)
3.Install the mounting bracket on the threaded conduit, and reinstall the
conduit nut. Tighten securely. (See Figures 10 & 11)
4.Refer to the Wiring Diagram to make electrical connections.
Installation Using 3/4” (NPS) Conduit:
1.To install the luminaire using ¾” (NPS) conduit, use the optional
snap hook.
2.Install the snap hook on threaded electrical conduit (¾” NPS,
provided by others). (See Figure 12)
3.Clip the snap hook onto the enclosed eyebolt hook. (See Figure
13)
4.Refer to the Wiring Diagram to make electrical connections.
Figure
11
Figure 10Figure 9
Figure 12 Figure 13
STEP 3
Using the yoke mount bracket as a template, mark and drill holes in the
ceiling or other solid structure to which the luminaire will be attached
(see Figure 5).
STEP 4
Attach yoke mount bracket to surface or structure. Ensure attachment is
adequate to support the weight of the light fixture. Mounting hardware
provided by others.
Ceiling-Mounted Installation (using optional Yoke Mount Bracket):
1. To install the optional yoke bracket on the luminaire, begin by attaching
the L-shaped yoke mounting brackets on the luminaire. (See Figure 3)
2. Next, attach the yoke bracket to the L-shaped yoke mounting brackets.
(see Figure 4)
3. Using the yoke mount bracket as a template, mark and drill holes in the
ceiling or other solid structure to which the luminaire will be attached.
(See Figure 5)
4. Use a hammer to install the expansion screws into the drilled holes. (See
Figure 6)
5. Using the enclosed nuts, install the yoke mounting bracket onto the
expansion screws, and securely tighten the nuts. (See Figure 7)
6. If the luminaire will be installed at an angle (see step 8), tighten the
mounting bracket adjustment bolts only partially tight. Otherwise,
securely tighten these bolts.
7. If the luminaire will be installed at an angle, rotate the luminaire up to 50
in either direction (100total adjustability), and securely tighten the
mounting bracket adjustment bolts.
8. Refer to the Wiring Diagram to make electrical connections.
Figure 4
Figure 3
Figure 6Figure 5
Figure 8Figure 7
Mounting Bracket
Adjustment Bolts
100°
Installation Using ½” (NPS) Conduit:
1.To install the luminaire using ½” (NPS) conduit, use the optional yoke
mount bracket.
2.Remove the nut from threaded electrical conduit (½” NPS, provided by
others). (See Figure 9)
3.Install the mounting bracket on the threaded conduit, and reinstall the
conduit nut. Tighten securely. (See Figures 10 & 11)
4.Refer to the Wiring Diagram to make electrical connections.
Installation Using 3/4” (NPS) Conduit:
1.To install the luminaire using ¾” (NPS) conduit, use the optional
snap hook.
2.Install the snap hook on threaded electrical conduit (¾” NPS,
provided by others). (See Figure 12)
3.Clip the snap hook onto the enclosed eyebolt hook. (See Figure
13)
4.Refer to the Wiring Diagram to make electrical connections.
Figure
11
Figure 10Figure 9
Figure 12 Figure 13
STEP 5
If the luminaire will be installed at an angle (see Figures 6 & 7), tighten
the mounting bracket adjustment bolts only partially tight. Otherwise,
securely tighten these bolts.
STEP 6
Rotate the luminaire up to 50° in either direction (100° total adjustability),
and securely tighten the mounting bracket adjustment bolts.
STEP 7
Refer to the Wiring Diagram to make electrical connections.
CEILINGMOUNTED INSTALLATION
(Using optional Yoke Mount Bracket)
Figure 3
Figure 5
Figure 6
Figure 4
Figure 7
Ceiling-Mounted Installation (using optional Yoke Mount Bracket):
1. To install the optional yoke bracket on the luminaire, begin by attaching
the L-shaped yoke mounting brackets on the luminaire. (See Figure 3)
2. Next, attach the yoke bracket to the L-shaped yoke mounting brackets.
(see Figure 4)
3. Using the yoke mount bracket as a template, mark and drill holes in the
ceiling or other solid structure to which the luminaire will be attached.
(See Figure 5)
4. Use a hammer to install the expansion screws into the drilled holes. (See
Figure 6)
5. Using the enclosed nuts, install the yoke mounting bracket onto the
expansion screws, and securely tighten the nuts. (See Figure 7)
6. If the luminaire will be installed at an angle (see step 8), tighten the
mounting bracket adjustment bolts only partially tight. Otherwise,
securely tighten these bolts.
7. If the luminaire will be installed at an angle, rotate the luminaire up to 50
in either direction (100total adjustability), and securely tighten the
mounting bracket adjustment bolts.
8. Refer to the Wiring Diagram to make electrical connections.
Figure 4
Figure 3
Figure 6Figure 5
Figure 8Figure 7
Mounting Bracket
Adjustment Bolts
100°
Installation Using ½” (NPS) Conduit:
1.To install the luminaire using ½” (NPS) conduit, use the optional yoke
mount bracket.
2.Remove the nut from threaded electrical conduit (½” NPS, provided by
others). (See Figure 9)
3.Install the mounting bracket on the threaded conduit, and reinstall the
conduit nut. Tighten securely. (See Figures 10 & 11)
4.Refer to the Wiring Diagram to make electrical connections.
Installation Using 3/4” (NPS) Conduit:
1.To install the luminaire using ¾” (NPS) conduit, use the optional
snap hook.
2.Install the snap hook on threaded electrical conduit (¾” NPS,
provided by others). (See Figure 12)
3.Clip the snap hook onto the enclosed eyebolt hook. (See Figure
13)
4.Refer to the Wiring Diagram to make electrical connections.
Figure
11
Figure 10Figure 9
Figure 12 Figure 13
Ceiling-Mounted Installation (using optional Yoke Mount Bracket):
1. To install the optional yoke bracket on the luminaire, begin by attaching
the L-shaped yoke mounting brackets on the luminaire. (See Figure 3)
2. Next, attach the yoke bracket to the L-shaped yoke mounting brackets.
(see Figure 4)
3. Using the yoke mount bracket as a template, mark and drill holes in the
ceiling or other solid structure to which the luminaire will be attached.
(See Figure 5)
4. Use a hammer to install the expansion screws into the drilled holes. (See
Figure 6)
5. Using the enclosed nuts, install the yoke mounting bracket onto the
expansion screws, and securely tighten the nuts. (See Figure 7)
6. If the luminaire will be installed at an angle (see step 8), tighten the
mounting bracket adjustment bolts only partially tight. Otherwise,
securely tighten these bolts.
7. If the luminaire will be installed at an angle, rotate the luminaire up to 50
in either direction (100total adjustability), and securely tighten the
mounting bracket adjustment bolts.
8. Refer to the Wiring Diagram to make electrical connections.
Figure 4
Figure 3
Figure 6Figure 5
Figure 8Figure 7
Mounting Bracket
Adjustment Bolts
100°
Installation Using ½” (NPS) Conduit:
1.To install the luminaire using ½” (NPS) conduit, use the optional yoke
mount bracket.
2.Remove the nut from threaded electrical conduit (½” NPS, provided by
others). (See Figure 9)
3.Install the mounting bracket on the threaded conduit, and reinstall the
conduit nut. Tighten securely. (See Figures 10 & 11)
4.Refer to the Wiring Diagram to make electrical connections.
Installation Using 3/4” (NPS) Conduit:
1.To install the luminaire using ¾” (NPS) conduit, use the optional
snap hook.
2.Install the snap hook on threaded electrical conduit (¾” NPS,
provided by others). (See Figure 12)
3.Clip the snap hook onto the enclosed eyebolt hook. (See Figure
13)
4.Refer to the Wiring Diagram to make electrical connections.
Figure
11
Figure 10Figure 9
Figure 12 Figure 13
CRN2
WET LOCATION HIGH BAY
DAMP LOCATION HIGH BAY WHEN USING OPTIONAL EMERGENCY LED DRIVER (BATTERY BACKUP)
CRN2 Instruction Manual
currentlighting.com/columbialighting
© 2022 HLI Solutions, Inc. All rights reserved. Information and specifications subject to change
without notice. All values are design or typical values when measured under laboratory conditions.
Page 3 of 3
Rev 07/20/22
COL_CRN2_inst_R01
Battery is damp location rated only. Battery backup not compatible with factory installed sensors.
MAXIMUM MOUNTING HEIGHT NOT TO EXCEED 37 FEET FOR EMERGENCY LIGHTING.
EMERGENCY LED DRIVER BATTERY BACKUP INSTALLATION
12V +
Emergency Battery
Backup Driver
Wiring Diagram - (FIG. 13)
All electrical connections to be routed to J-Box. Emergency Battery is supplied with flexible conduit.
STEP 1
Use provided connecting link to connect emergency battery backup to CRN2 luminaire.
STEP 2
Connect emergency battery backup and CRN2 luminaire to ceiling structure using eye-bolt located on top of emergency battery. Ensure that
mounting method will support weight of fixture and battery (20 lbs.). Any user-provided mounting hardware must be suitable for rated weight.
STEP 3
All wiring connections must be made inside junction box. Route flexible conduit from emergency battery to junction box, route power/dimming
cord from luminaire to junction box. See Wiring Diagram (FIG. 13) below for wire connections.
AC CABLE
DIM
AUX+
AUX-
Connecting link
(provided)
CRN2
luminaire
Emergency
battery backup
Eyebolt
Connecting link
(provided by others)
Flexible conduit from
emergency battery backup
Junction box
  • Page 1 1
  • Page 2 2
  • Page 3 3

Columbia Lighting CRN2 Installation guide

Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI