  • Hello! I am an AI chatbot trained to assist you with the Danfoss SpeedUp Eco - Direct load User guide. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
Application sheet
SpeedUp Eco
Massive wooden planks on battens
Direct load
1
2
3
4
5
1 Wooden planks ≤ 22 mm
2 SpeedUp Eco heat panel + FH composite pipe 30 mm
3 Support batten (30mm)
4 Wood bre insulation 150 kPa 30 mm
5 SpeedUp Eco perimeter insulation
6 If necessary construction sealing
Floor nish ≤ 22 mm Massive wooden planks or parquet
Construction height ≤ 72 mm Height including oor nish
Weight ~ 26 kg / m² Weight including oor nish
Thermal resistance R 1,35 m²K / W The minimum thermal resistance requirement of DIN EN 1264 is
fullled.
Thermal transmission coecient U 0,66 W / m²K If the architectural design species better thermal insulation, this
must be taken into account.
Design load ≥ 2,0 kN / m²
Point load (≥ 20 cm²) ≥ 2,0 kN Sum of point loads not exceeding rated design load; particularly
heavy objects (such as aquariums and bathtubs) must be consid-
ered separately.
Impact subsonic noise reduction 21 dB Test value according to DIN ISO 140-8; applies to concrete slabs
thicker than 12 cm (DIN 4109: m’ > 276 kg/m²)
Application area
Residential spaces, hallways and attic spaces in residential buildings and hotel rooms.
Corresponds to categories A1, A2 and A3 of DIN 1055-3. Oce spaces, hallways in oce
buildings, medical oces, stations and spaces with human occupancy, and commercial
spaces with oor areas up to 50 m² in residential or oce buildings. Corresponds to
categories B1, D1 and D2 of DIN 1055-3.
Requirements & special features
A level, smooth and structurally sound surface is necessary for full surface contact with
the heating elements (elevated requirements according to DIN 18202 Table 3, row 4). The
R value must be increased if the groundwater level is less than or equal to 5 m. A U value
not exceeding 0.5 W/m²K must be maintained in existing buildings and additions with
areas up to 50 m². If necessary, protect oorboards and prefabricated parquet against
moisture penetration from below according to the manufacturer’s instructions (vapour
barrier). Observe all installation instructions and manufacturers instructions.
Additional insulation
30 mm wood bre insulation 150 kPa; alternative: 20 mm Gutex Thermosafe wd ≥ 50 kPa.
Existing buildings: wood bre insulation 60 mm 150 kPa, WLG 050; alternatively 40 mm
50 kPa, WLG 040.
Construction
According to EnEV, EN 1264, DIN 1055, 4108 and 18202
Construction number 89
Technical Data Floors/ceilings facing unheated rooms or the ground
6
© Danfoss 11/2008
VA.CS.M1.02