  • Hello! I am an AI chatbot trained to assist you with the Danfoss SpeedUp Eco - laminate User guide. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
Application sheet
SpeedUp Eco
Laminate
Strongboard tile and laminate
1
2
3
4
5
1 Laminate ≥ 8 mm
2 Strongboard tile and laminate 5 mm
3 SpeedUp Eco heat panel + FH composite pipe 30 mm
4 Support batten (30mm)
5 Load bearing panel ≥ 15 mm
6 Wood bre insulation 20 mm
7 SpeedUp Eco perimeter insulation
8 If necessary moisture barrier
Floor nish ≥ 8 mm Laminate; strength without subsonic noise lamination
Construction height ≥ 78 mm Height including oor nish
Weight ~ 28 kg / m² Weight including oor nish
Thermal resistance R 1,26 m²K / W The minimum thermal resistance requirement of DIN EN 1264 is
fullled.
Thermal transmission coecient U 0,70 W / m²K If the architectural design species better thermal insulation, this
must be taken into account.
Design load ≤ 2,0 kN / m²
Point load (≥ 20 cm²) ≤ 1,0 kN Sum of point loads not exceeding rated design load; particularly
heavy objects (such as aquariums and bathtubs) must be consid-
ered separately.
Impact subsonic noise reduction 19 dB Test value according to DIN ISO 140-8; applies to concrete slabs
thicker than 12 cm (DIN 4109: m’ > 276 kg/m²)
Application area
Residential spaces, hallways and attic spaces in residential buildings and hotel rooms.
Corresponds to categories A1, A2 and A3 of DIN 1055-3.
Requirements & special features
A level, smooth and structurally sound surface is necessary for full surface contact with
the heating elements (elevated requirements according to DIN 18202 Table 3, row 4).
Structural sealing according to DIN 18195 must be placed beneath the oor panel in
case of structures facing the ground, and otherwise on the unnished oor. The R value
must be increased if the groundwater level is less than or equal to 5 m. A U value not
exceeding 0.5 W/m²K must be maintained in existing buildings and additions with areas
up to 50 m². Strongboard is used under the laminate as a structural and subsonic noise
reduction layer. Protect laminate against moisture penetration from below if necessary
(vapour barrier). Observe all installation instructions and manufacturer’s instructions.
Additional insulation
20 mm wood bre insulation 150kPa, renovation: 50 mm wood bre insulation 150 kPa,
WLG 050
Construction
According to EnEV, EN 1264, DIN 1055, 4108 and 18202
Construction number 88
Technical Data Floors/ceilings facing unheated rooms or the ground
6
7
8
© Danfoss 11/2008
VA.CS.L1.02