FläktGroup eCO TOP Installation and Maintenance Manual

Category
Split-system air conditioners
Type
Installation and Maintenance Manual
INSTALLATION AND MAINTENANCE MANUAL
eCO TOP®
WITH ROTARY HEAT EXCHANGER
eCO TOP
®
with Rotary heat exchanger - Installation and maintenance
2
FläktGroup DC_10430GB_20221117_R4 Specifications are subject to alteration without notice
CONTENTS
Page
1. SAFETY INSTRUCTIONS ................................................................................3
VDI 6022 ..........................................................................................................3
2. DESCRIPTION OF THE UNIT .......................................................................... 4
3. TRANSPORT AND PLACEMENT ..................................................................5
4. CONNECTIONS ...................................................................................................6
4.1 Duct connections .................................................................................. 6
4.2 Post heater, electrical .......................................................................... 6
4.3 Post heater, hot water ......................................................................... 6
4.4 Cooling coil, water ................................................................................. 7
4.5 Valve and valve actuator .....................................................................7
4.6 Damper......................................................................................................7
4.7 Silencer ......................................................................................................7
5. ELECTRICAL CONNECTIONS.........................................................................8
5.1 Fuse protection .......................................................................................8
5.2 Electrical data .........................................................................................8
5.3 Main supply .............................................................................................8
6. CONNECTION OF EXTERNAL COMPONENTS ..........................................9
6.1 Post heater, water/electrical ............................................................ 9
6.2 Cooling coil, water ............................................................................... 9
6.3 Cooling coil, DX ..................................................................................... 9
6.4 Damper..................................................................................................... 9
6.5 Temperature sensors ........................................................................10
6.6 Humidity sensors ................................................................................10
6.7 Pressure sensors ................................................................................10
6.8 Air quality sensors ............................................................................. 11
6.9 External control/Extended functions ........................................... 11
6.10 Fire protection function ................................................................... 11
6.11 Summary alarm.................................................................................. 11
6.12 Unit operation on/off indication ................................................... 11
6.13 7” HMI connection ............................................................................. 11
7. TESTING FUNCTIONS ....................................................................................12
8. CONTROL PANEL, OPERATIONS, COMMISSIONING ............................13
8.1 General .....................................................................................................13
8.2 Commissioning setupwizard ...........................................................14
8.3 Home screen ........................................................................................17
8.4 Time/date, language, basic settings............................................18
8.5 Alarms .................................................................................................... 20
8.6 PID settings ............................................................................................ 21
8.7 Room HMI ...............................................................................................21
Page
9. CONTROL FUNCTIONS ................................................................................23
9.1 Heating, cooling, energy recovery ...............................................23
9.2 Temperature controls ......................................................................23
9.3 Humidity control ................................................................................24
9.4 Fan control ...........................................................................................24
9.5 Night purge/Night heating .............................................................24
9.6 Freeze protection ..............................................................................25
9.7 Defrost function ................................................................................25
9.8 Fire protection ..................................................................................25
10. COMMUNICATION .........................................................................................26
10.1 Modbus, RS485.................................................................................26
10.2 Modbus, TCP/IP ...............................................................................26
10.3 Fieldbus ..............................................................................................26
10.4 Bacnet .................................................................................................26
10.5 Webserver .........................................................................................26
11. PARAMETER LIST ........................................................................................27
12. MAINTENANCE ...............................................................................................31
12.1 General ................................................................................................. 31
12.2 Filter ..................................................................................................... 31
12.3 Rotary Heat Exchanger .................................................................32
12.4 Post heater, hot water ....................................................................33
12.5 Post heater, electrical ................................................................... 34
12.6 Water cooling coil, duct mounted .............................................34
12.7 Fans ......................................................................................................35
12.8 Service schedule .............................................................................36
12.9 Alarm list ............................................................................................ 37
13. DECLARATION OF CONFORMITY ............................................................45
14. DISPOSAL .......................................................................................................46
eCO TOP
®
with Rotary heat exchanger - Installation and maintenance
3
FläktGroup DC_10430GB_20221117_R4 Specifications are subject to alteration without notice
OPERATION OF AIR HANDLING UNITS
AND ACCESSORIES
WARNING
Before taking the air handling unit into
operation fit any unused connections with
protective mesh.
In addition, all electrotechnical and me-
chanical safety devices must be
installed before taking the air handling
unit into operation.
Before opening the unit check that its power has been
disconnected.
Take care when opening the isolating valves for the hot
water to the air heater. There is a risk of water hammer
or steam discharge.
When servicing or inspecting the unit, turn off the
safety switch before opening the inspection doors.
Reset all safety devices before restarting.
The clearance in front of electric heaters and electrical
cabinets shall conform to applicable electrical safety
regulations.
Use the control panel to stop the unit.
The unit’s hatches are fitted with locking handles.
Ensure that the unit is always left locked, and that the
keys cannot be accessed by unauthorized persons.
Do not open inspection hatches when the unit is in
operation.
Use protective gloves during installation and service.
1. SAFETY INSTRUCTIONS
Installation may only be
carried out by qualified personnel.
VDI 6022
eCO TOP is designed in accordance
to hygiene standard VDI 6022 and
is easy to clean with no place where dirt can accumulate. Non-
metallic part, have been chosen as proven free of micro bacterial
or mold growth.
Following the VDI 6022, AHU should ensure a physiologically
favourable indoor climate and a hygienically perfect indoor air
quality.
The eCO TOP is designed in order, not to endanger health, not to
disturb the condition and the thermal comfort, not to lead to odour
nuisance and to prevent exposure and impact of inorganic and
organic pollutants.
The casing is approved for T2 / TB2.
eCO TOP
®
with Rotary heat exchanger - Installation and maintenance
4
FläktGroup DC_10430GB_20221117_R4 Specifications are subject to alteration without notice
FANS
The unit has two plug fans with EC motors.
ROTARY HEAT EXCHANGER
The speed controlled rotor is fitted with a purge sector and a
rotation sensor.
FILTER
Bag filter class (F7) ePM1 50% on both outdoor and extract air.
POST HEATER, HOT WATER
Hot water coil containing copper tubes and aluminum fins. Pipe
connection ø12 mm. Freeze protection temperature sensor or
freeze protection thermostat is included.
POST HEATER, ELECTRICAL
The heater for size 03 and 04 is built-in. For size 06 the heater is
duct mounted.
CONTROL SYSTEM
The ISYteq control system is integrated with the unit and is ready
for use with a large number of functions.
INTERNAL SILENCER (ACCESSORY)
An internal silencer can be fitted in the supply air inside the unit.
COMPONENTS
The unit can be supplied in left-hand or right-hand configurations.
Refer to the order code in Technical Instruction.
2. DESCRIPTION OF THE UNIT
RIGHT HAND CONFIGURATION
Outdoor air
Supply air
Extract air
Exhaust air
1. Outdoor air sensor
2. Outdoor air filter
3. Rotary heat exchanger with rotation sensor
4. Supply fan
5. Electrical heater including overheating protection
alternatively hot water coil with freeze protection
6. Supply air sensor
7. Extract air sensor
8. Control plate
9. Extract filter
10. Exhaust fan
11. A Internal silencer or second filter step (accessory)
1 6
5
11
4
9
810
32
7
eCO TOP
®
with Rotary heat exchanger - Installation and maintenance
5
FläktGroup DC_10430GB_20221117_R4 Specifications are subject to alteration without notice
SOUND TRANSMISSION
When a unit is positioned next to a wall, low frequency sound can
generate vibrations in the wall, even if the sound level from the
unit is acceptable. Generally the unit should be positioned against
a wall adjacent to a room that is not sensitive for noise. When this
is not possible the unit should be positioned 400-500 mm from
the wall.
Duct lead-through must be designed with care so that rigid
connections between the duct and wall do not occur. In addition,
the seal around the duct must be carefully installed to prevent
the transmission of noise to adYescent areas. For sensitive in-
stallations it may be a good idea to connect ducts using flexible
connections.
If the floor structure is weak, noise can be transmitted to other
areas in the building. Use of a heavy insulating mat can prevent
that problem.
TRANSPORT
Use a fork lift truck, pallet truck or platform trolley for transport on
site. The unit can be lifted from the front or from the side.
To move size 06 through a 900 mm opening remove the door and
the center strut. See section 12.3.
3. TRANSPORT AND PLACEMENT
UNIT WEIGHT (ESTIMATED WEIGHT)
Size 03 = 260 kg
Size 04 = 300 kg
Size 06 = 400 kg
SPACE REQUIREMENTS
Make sure that it is enough space around the unit for routine
service work, such as replacing filters and cleaning the fan and
casing.
Consideration has to be taken for future replacement of
com ponents.
PLACEMENT
The unit can be placed directly onto the surface if this is flat and
horizontal, otherwise use adjustable feet.
Available as accessory RDTZ-13.
Size B1 S
03 1694 700
04 1844 776
06 2114 911
B1 = width with open doors
S = minimum space for service*)
B1
S
* in front of the control cabinet there has to be enough space
according to local electrical regulations.
eCO TOP
®
with Rotary heat exchanger - Installation and maintenance
6
FläktGroup DC_10430GB_20221117_R4 Specifications are subject to alteration without notice
NOTE! The weight of the duct system
with components must not lay weight on the unit.
4. CONNECTIONS
4.1 DUCT CONNECTIONS
Size 03 and 04 (Ø315 mm) have circular duct connections. Size
06 has rectangular duct connections (600 x 300 mm).
4.2 POST HEATER, ELECTRICAL
The electrical post heater for size 06 is duct mounted, see sepa-
rate instruction.
4.3 POST HEATER, HOT WATER
Connect the pipes for the heating coil inside the unit according to
pictures below. View from top.
NOTE! To avoid freezing the temperatures for frost
protection must not be set too low. If the building
has to be left unheated for long periods during
winter, the water must be drained from both the
pipework and the heating coil.
WARNING! Wear protective gloves
when using a fin comb.
Warning - hot water!!
FläktGroup takes no responsibility neither for
the connection of air heaters to the heating
system, nor for damage or injury caused by
incorrect planning, installation or maintenance
of this system. Pipework, valves etc. are to be
designed due to pressure drop and function, not
the dimensions of the air heater connections. The
weight of the pipe work system with components
must not lay weight on the water coil.
PIPE CONNECTION
Size 03 = 12 mm
Size 04 = 12 mm
Size 06 = 12 mm
PREVENTING FREEZING
There is a risk of freezing in the hot water coil at low outdoor
temperatures. This can cause water damage. The risk can
appear:
1. if the temperature of the water is too high. The risk increases
in spring and autumn. Adjust the water temperature in relation
to the outdoor air temperature.
2. if the post heater is oversized. Decrease the temperature of
the water to increase the water flow.
FINS
Any deformed fins can be adjusted using fin comb EQAZ-14.
VENTING
The air must be properly vented from the system to ensure good
function. The venting is made through the pipe system.
Size 03 Size 04 Size 06
A238 A272 A304
B74 B79 B92
C110 C91 C111
DØ 22.5 DØ 22.5 DØ 22.5
A
B
C
D
AB
C
D
Left hand version
Right hand version
eCO TOP
®
with Rotary heat exchanger - Installation and maintenance
7
FläktGroup DC_10430GB_20221117_R4 Specifications are subject to alteration without notice
When installing a 3-way valve check as follows:
Mixture from A/B to AB
Diverting from AB to A/B
4.6 DAMPER
Duct mounted damper with a spring return on/off actuator. The
actuator has to be connected to the terminal block in the electri-
cal cabinet. Size 03 and 04 have circular duct connections and
size 06 has rectangular. The damper is designed for duct insula-
tion of up to 50 mm.
4.7 SILENCER, DUCT MOUNTED
Size 03 and 04 have circular duct connections and size 06 has
rectangular. Fire resistance rating EI30. The distance to the fan
has to be at least 300 mm.
4. CONNECTIONS
4.4 COOLING COIL, WATER
The cooling coils have circular duct connections with rubber
ring seals. For size 06 a converter from rectangular to circular
is available as an accessory (RDTZ-24). The cooler has to be
installed horizontally and the distance to nearest bend has to be
at least 600 mm. Venting and draining is carried out via the pipe
system. The pipe connection, Ø 22 mm, is located on the outlet
end, is smooth and is intended for a compression fitting. The
drainage tray is in stainless steel and has an R 1/2” connection.
Maximum operating pressure 1.0 MPa and maximum operating
temperature 150° C.
4.5 VALVE AND VALVE ACTUATOR
ACTUATORS FOR HEATING AND COOLING
Connected to terminal in electrical cabinet. Stroke length 5.5 mm.
Intended for assembly on 2-way and 3-way valves of the type
VVG44 or VXG44.
ACCEPTED INSTALLATION METHODS
VALVE FOR HEATING AND COOLING
The valve and valve actuator can be easily installed without
special tools. A particle filter should be fitted before the valve to
extend its service life.
2-WAY VALVE VVG
The flow is increased by turning the spindle inwards, the flow is
reduced by moving the spindle outwards. Note that the 2-way
valve cannot be used as a 3-way valve.
The flow direction is indicated by an arrow.
ACCEPTED INSTALLATION METHODS
3 -WAY VA LV E V XG
The bypass is closed by turning the spindle inwards, the bypass
is opened by turning the spindle outwards.
ACCEPTED INSTALLATION METHODS
eCO TOP
®
with Rotary heat exchanger - Installation and maintenance
8
FläktGroup DC_10430GB_20221117_R4 Specifications are subject to alteration without notice
5. ELECTRICAL CONNECTIONS
5.3 MAIN SUPPLY
Units with built-in electrical heater, main supply
3x400 VAC ±10%+N+PE, 50Hz.
Units with hot water coil can be supplied with
1x230 VAC ±10%+N+PE, 50Hz.
Units with duct mounted electrical heater can be supplied with
1x230 VAC ±10%+N+PE, 50Hz.
Units are not available for 3x230 VAC ±10%+N+PE, 50Hz.
Connect main supply to terminals U, V, W, N and PE, located on
the control plate.
The cables on the outdoor unit must enter the flange from below.
Maximum external fuse is 16A.
To be able to make the entire unit power less, an external safety
switch must be installed on main supply.
5.1 FUSE PROTECTION
Size Unit with Hot water coil Electrical coil
03 Supply 1x230 VAC±10%+N+PE,
50Hz
3x400 VAC±10%+N+PE,
50Hz
Fuse 10 A 10 A
04 Supply 1x230 VAC±10%+N+PE,
50Hz
3x400 VAC±10%+N+PE,
50Hz
Fuse 10 A 16 A
06 Supply 3x400 VAC±10%+N+PE,
50Hz
3x400 VAC±10%+N+PE,
50Hz1)
Fuse 10 A 10 A
1) Duct mounted heater size 06 has separate supply.
WARNING
Low voltage cables must be separated
from SELV cables in accordance with
local regulations.
WARNING
Main switch do NOT cut power between
main supply terminals and main switch.
5.2 ELECTRICAL DATA
MOTORS
Size Power, kW Current, A
03 0.50 x 2 2.2 x 2
04 0.75 x 2 3.3 x 2
06 1.05 x 2 1) 1.6 x 2
1)
3x400 VAC.
ELECTRICAL POST HEATER
Size Power, kW Current, A Voltage, VAC±10%+N+PE,
50Hz
03 41) 10 2x400
03 12 17.4 3x400
03 14 20.3 3x400
04 61) 15 2x400
04 16 23.3 3x400
04 19 27.5 3x400
06 913 3x400
06 23 33.3 3x400
06 27 39.1 3x400
1)
Unit mounted heater is powered from the control cabinet.
PE N L1
PE N L1
PE N L1
PE N L1
PE N L1
PE N L1 RHE
Size 03, 04 Size 06
eCO TOP
®
with Rotary heat exchanger - Installation and maintenance
9
FläktGroup DC_10430GB_20221117_R4 Specifications are subject to alteration without notice
6. CONNECTION OF EXTERNAL COMPONENTS
Use the cable flange on the top of the unit to connect all external
accessories. For information about how to connect available ac-
cessories see below.
From DDC To Remark
Terminal Terminal Component
X6:DO2 - 3 *DX1 digital output, NO:max.5A
X6:DO2 - 4 *
X7:DO6 - 9 *DX2 digital output, NO:max.5A
X7:DO6 - 10 *
X2:ID2 - 10 *DX Alarm 24V DC potential digital input
X2:ID2 - 2 *
* depends on customer's controller
From DDC To Remark
Terminal Terminal Component
X16:DO8 - 1 *Exhaust
damper
digital output, NO:max.5A,
NC:max.2A
X16:DO8 - 4 *
X16:DO8 - 10 *Outdoor
damper
digital output,NO:max.5A,
NC:max.2A
X16:DO8 - 3 *
* depends on customer's damper
From DDC To Remark
Terminal Terminal Component
X10:L1 L
H. Pump Supply 230 V, 50/60 Hz,
max.2A**
X10:N N
X10:PE PE
X6:DO1 - 1 *H. Pump/El Start digital output, NO:max.5A
X6:DO1 - 2 *
X2:ID1 - 9 *H. Pump/El
Alarm
24V DC potential digital
input
X2:ID1 - 1 *
X2:Y1 - 13 YValve/El Control 0-10V DC analog output
X2:Y1 - 5 M
X5:1 - 6 GValve Actuator 24V DC supply
X5:1 - 1 G0
* depends on customer's pump
** if powered from DDC, otherwise 10A
From DDC To Remark
Terminal Terminal Component
X9:L1 L
C. Pump Supply 230 V, 50/60 Hz,
max.2A**
X9:N N
X9:PE PE
X6:DO2 - 3 *C. Pump Start digital output,
NO:max.5A
X6:DO2 - 4 *
X2:ID2 - 10 *C. Pump Alarm 24V DC potential digital
input
X2:ID2 - 2 *
X2:Y2 - 14 YValve Control 0-10V DC analog output
X2:Y2 - 6 M
X5:2 - 7 GValve Actuator 24V DC supply
X5:2 - 2 G0
* depends on customer's pump
** if powered from DDC, otherwise 10A
6.1 POST HEATER, WATER/ELECTRICAL
Heating pump and valve actuator are connected according to the
table below.
6.2 COOLING COIL, WATER
Cooling pump and valve actuator are connected according to the
table below.
6.3 COOLING COIL, DX
The unit can manage cooling DX, 2-step. Note that the coil is not
included in the delivery of the unit. If 2-step DX is used water cool-
ing is no longer possible. For configuration see control functions.
6.4 DAMPER
On/off actuators with spring return, 15 NM, 24VAC/DC.
eCO TOP
®
with Rotary heat exchanger - Installation and maintenance
10
FläktGroup DC_10430GB_20221117_R4 Specifications are subject to alteration without notice
6. CONNECTION OF EXTERNAL COMPONENTS
From DDC To Remark
Terminal Terminal Component
X1:U9 - 19 S+ Room
Temperature Universal input, NTC/PT
X1:U9 - 9 S-
X17:U13 -18 ST+ Facade
Temperature Universal input, NTC/PT
X17:U13 - 8 ST-
X17:U16 -15 ST+ Supply Temp.
Duct
Universal input, NTC/PT
(if duct mounted coils)
X17:U16 - 5 ST-
From DDC To Remark
Terminal Terminal Component
X1:U8 - 18 AOU1 Room
Humidity Universal input
X1:U8 - 8 GND
X1:U9 - 19 AOU2 Room
Temperature Universal input, NTC/PT
X1:U9 - 9 GND
X16:5 - 5 UB+ Room
Humidity/
Temp. Supply
24V DC supply
X16:5 - 14 GND
From DDC To Remark
Terminal Terminal Component
X5:4 - 9 24V Duct extract
air power
supply
24V DC supply
X5:4 - 4 GND
X1:U6 - 16 0-10V Duct extract
air signal Universal input
X1:U6 - 6 GND
X5:3 - 8 24V Duct supply
air power
supply
24V DC supply
X5:3 - 3 GND
X1:U7 - 17 0-10V Duct supply
air signal Universal input
X1:U7 - 7 GND
6.5 TEMPERATURE SENSORS
The unit is provided with:
- Supply air sensor located at supply air spigot.
- Outdoor air sensor located at outdoor air spigot.
- When using cooling coil or duct mounted post heater a supply
temperature sensor is supplied for duct mounting.
The unit-mounted supply temperature sensor is then used to
measure the temperature before heaters or coolers.
- Room sensor is supplied when the unit is configured for room
temperature control. The unit-mounted extract temperarure
sensor is used for various functions depending on the
configuration of the unit.
- The room sensor is intended for wall mounting and needs to
have good air circulation and not direct sun light. Cable is not
included.
- A facade temperature sensor is supplied when chosen.
6.6 HUMIDITY SENSORS
Room sensor is supplied when the unit is configured for room
humidity control. The sensor measures also temperature and its
configured as shown below.
6.7 PRESSURE SENSORS
When configured for pressure control, two pressure sensors for
duct mounting are supplied.
ZERO POINT CALIBRATION, DUCT MOUNTED PRESSURE
SENSORS
4-20mA
LED
Jumper 1
Jumper 2
Jumper 3 24VDC
GND
0-10V
LED
Jumper 1
Jumper 2
Jumper 3
push-button
The sensors must be zeroed during commissioning. They should
then be zeroed annually. The sensors should have been energized
for approximately one hour before calibration is carried out. After
that, remove the hoses from the sensors. To start calibration,
press the push-button next to the pressure range jumpers. The
red LED lights up and goes out after about a second. Reassemble
the air hoses.
eCO TOP
®
with Rotary heat exchanger - Installation and maintenance
11
FläktGroup DC_10430GB_20221117_R4 Specifications are subject to alteration without notice
From DDC To Remark
Terminal Terminal Component
X5:3 - 8 +VDC CO2/VOC
supply 24V DC supply
X5:3 - 3 GND
X1:U7 - 17 0-10V CO2/VOC
signal Universal input
X1:U7 - 7 GND
From DDC To Remark
Terminal Terminal Component
X2:ID4 - 12 1External Stop 24V DC potential digital
input
X2:ID4 - 4 2
X1:U4 - 14 1External
Control 1 Universal input
X1:U4 - 4 2
X16:6 - 6 24V Supply External
Control 1 24V DC supply
X16:6 - 15 GND
X1:U5 - 15 1External
Control 2 Universal input
X1:U5 - 5 2
X16:7 - 7 24V Supply External
Control 2 24V DC supply
X16:7 - 16 GND
X1:U3 -13 1External Temp.
Setpoint Universal input, NTC/PT
X1:U3 - 3 2
From DDC To Remark
Terminal Terminal Component
X1:U2 - 12 1Alarm 1 (Fire) Universal input
X1:U2 - 2 2
X1:U3 - 13 1Alarm 2 Universal input
X1:U3 - 3 2
From DDC To Remark
Terminal Terminal Component
X7:DO3 - 1 1
Summary alarm A
NO:max.5A
X7:DO3 - 2 2 C
X7:DO3 - 3 3NC:max.2A
X7:DO4 - 1 1
Summary alarm B
NO:max.5A
X7:DO4 - 2 2 C
X7:DO4 - 3 3NC:max.2A
6. CONNECTION OF EXTERNAL COMPONENTS
6.8 AIR QUALITY SENSORS
Instead of external supply air duct pressure sensor an air quality
sensor can be connected to either measure the CO
2
or VOC.
6.9 EXTERNAL CONTROL/EXTENDED FUNCTIONS
The unit can be controlled by an external source, e.g. push buttons
to activate profiles and profile bypasses. External control inputs
can also be used to vary fan speed from a remote source. For
configuration see chapter 9, control functions.
If configured, External Stop is a NC circuit which lets the unit oper-
ate according to the current profile number. If the contact is open,
the unit is switched off and a message is shown on the HMI.
External Control contacts are used as
1. NO circuits activating configured profiles with Ext. Control 1
being low and Ext. Control 2 high priority.
2. Push button circuits activating a profile bypass for a configured
time with Ext. Control 1 being low and Ext. Control 2 high
priority.
3. External setpoints for fan control (manual/volume flow/
pressure) with Ext. Control 1 being fan control 2 and Ext.
Control 2 fan control 1.
Please note that only two functions can be configured at the same
time for external controls.
6.10 FIRE PROTECTION FUNCTION
Two external fire alarms can be connected to the unit to stop it in
case of fire by using universal analogue inputs. Smoke detectors
and fire dampers cannot be connected directly to the air handling
unit, a separate fire system is needed.
Several functions which are activated if fire alarm is triggered can
be implemented. Therefor the fan speeds can be set independent-
ly or completely stopped if needed.
6.11 SUMMARY ALARM
There are two separate alarm outputs for indicating A- and
B-alarms. Both can be connected as either NO or NC potential free
contacts.
6.13 7" HMI CONNECTION
Note: The HMI display is IP20. Link 2 is a Power over Ethernet port (PoE).
DDC Link2 Link1
Ethernet cable
6.12 UNIT OPERATION ON/OFF INDICATION
There is a digital output on the DDC that indicates whether the unit
is on/off.
From DDC To Remark
Terminal Terminal Component
X7:DO5 - 7 *Operation Indi-
cation
NO: max. 5A
X7:DO5 - 8 * C
* depends on customer's indicator device
eCO TOP
®
with Rotary heat exchanger - Installation and maintenance
12
FläktGroup DC_10430GB_20221117_R4 Specifications are subject to alteration without notice
STARTING THE UNIT
When the electrical connections are made and all the accessories
are mounted the unit is ready to start up.
1. Turn the safety switch to 1 (ON).
2. Start the unit (see chapter 8).
DAMPERS
Check that all dampers opens and closes correctly.
VALVE ACTUATORS
Check that valve actuators for heating and cooling works correctly.
AIR FLOW MEASUREMENT
The eCO TOP has measuring nipples for air flow measurement.
Using a measuring pressure Dpm (Pa) and a constant (k) the air
flow q
20
at 20 °C can be calculated using the following equation:
NOTE! When the unit is supplied with
Constant Air Volume Control there will be
no measuring nipples on top of the unit.
pm
TEMPERATURE CORRECTION
The air flow formula above applies to air with a temperature of
+20 °C. At other air temperatures the air flow must be corrected
using the formula:
The value of the constant (k) is shown in the table below.
q
20
= 1000
k
Dp
m
x
The measuring pressure, Dpm, is the difference between the pres-
sure in the empty section at the fan inlet and the pressure inside
the inlet cone. A manometer (RDTZ-56) can be connected to view
the measuring pressure. This is used as a reference for monitoring
the unit. Connect hoses with 4 mm diameter between the nipples
on the top of the unit and the manometer, see figure.
If the unit is supplied with Constant Air Volume control the air flow
can be read in the control panel.
Location of measuring nipples on the unit.
q = q
20
(273 + t)
293
, m3
/s
7. TESTING OF FUNCTIONS
q = actual air flow
q
20
= calculated air flow in formula above
t = current temperature in °C
FILTER, FINAL PRESSURE DROP
It is time to replace the filters when the final pressure drop is
reached, see table below.
SIZE 03
Air flow m3/s 0.15 0.25 0.35
Supply air/Extract air 90 150 170
SIZE 04
Air flow m3/s 0.20 0.35 0.50
Supply air/Extract air 54 96 138
SIZE 06
Air flow m3/s 0.30 0.55 0.75
Supply air/Extract air 90 154 174
FILTER MONITOR
For the filter monitors use the values in the table above. If the unit
is supplied with Constant Pressure control, activate the adoptation
function to handle the pressure drop variations.
The unit is equipped with pressure sensors for outdoor and
extract filter. It is possible to connect a third pressure sensor to
measure an extra filter in supply
Size 03 04 06
k-value air fan 58.4 51.5 49.2
eCO TOP
®
with Rotary heat exchanger - Installation and maintenance
13
FläktGroup DC_10430GB_20221117_R4 Specifications are subject to alteration without notice
8. CONTROL PANEL, OPERATIONS, COMMISSIONING
8.1 GENERAL
HMI
This section introduces the touchscreen control panel and the
web configurator, also known as the ‘Human Machine Interface’,
or simply HMI.
The HMI serves two main purposes: To provide information about
the current operational state of the unit. To allow the unit to be
setup and configured.
TOUCH SCREEN TIPS
To select an item, touch the centre of the icon or option. Do not
press too hard, the touch screen is sensitive enough to pick up
light, firm touches. Use the tip of your finger or the back of a pen-
cil to touch the required option. Be careful not to touch any other
options.
CLEANING THE SCREEN
Disconnect the power cord (this is in most cases the ethernet
which provides PoE). Gently wipe the screen with a soft, dry
non-abrasive cloth. If the marks remain, moisten the cloth slightly
with a detergent that is designed for touchscreens and wipe the
screen gently from top to bottom. Never use other detergents, as
these may contain ammonia or other additives.
IMPORTANT:
• Never spray or pour liquids directly on to the screen.
• Do not clean the screen while the system is on.
CONVENTIONS USED WITHIN THIS MANUAL
The following buttons and symbols are universal and available on
many menu pages.
Use the wheel to change any time
settings.
Home button, leads back to highest menu of
current view.
Time schedules, edit profile switching times and
summer/winter changeover.
Down button, scroll down the menu bar.
Up button, scroll up the menu bar.
Trend logs, view and export sensor and actua-
tor history.
Operating data, configure assemblies, control
functions and operations. Available with Opera-
tor rights or higher.
Settings, configure general device and user
settings. Main settings of the device for commu-
nication, User, Hardware and Diagnosis.
Active alarms, recognize and acknowledge
alarms. Press this symbol if it indicates alarms
with a red marker (also indicating number of
alarms). Critical errors, marked red, will stop
the unit, while non-critical will still appear but
will not stop the unit from its normal function
(marked orange).
Tile menu, overview of setpoints and actual
values. Easy and quick setting of setpoints and
control types.
User login, higher access rights available. This
will offer more screens, configurations and set-
tings if access rights are high enough.
Use the calendar to change any date
settings.
eCO TOP
®
with Rotary heat exchanger - Installation and maintenance
14
FläktGroup DC_10430GB_20221117_R4 Specifications are subject to alteration without notice
8. CONTROL PANEL, OPERATIONS, COMMISSIONING
8.2 COMMISSIONING, SETUPWIZARD
The Setup wizard can be run on the touch display or via a web
browser on a computer with Ethernet connection to the unit. Type
the IP address 192.168.0.1 in the address bar of the web browser.
TO LOG IN AND SELECT LANGUAGE
Enter user name ”Admin” and password ”Admin” and select
”LOGIN”.
If the entered information is incorrect, a notification appears. If the
entered information is correct, the Setup wizard starts.
TO NAVIGATE THE SETUP WIZARD
At the bottom of the screen there are four navigation buttons.
A B DC
To confirm all settings in the current step of the Setup wizard
and go to the next step, select save (A).
To skip to the next step in the Setup wizard without saving any
changed settings, select skip (B). It is recommended to use the
skip function if you want to use the preconfigured settings and
be sure that you do not change anything.
To cancel the changes made in the current step of the Setup
wizard and restore the previous settings, select cancel (C).
As you go through the Setup wizard, the headings in the list
on the left side of the screen become green. To go back and
change already made settings, select a green heading.
To exit the Setup Wizard, select exit (D).
LANGUAGE SETTINGS
Select a flag to select the corresponding language and select
save to go to the next step.
COMPONENTS
A C D E
B
This step in the Setup wizard lets you select and configure the
components that are installed in the unit. The first tab (A) is
selected automatically. To move between the tabs, select save or
skip. Tabs with completed settings become a darker color. Click a
completed tab to go back and change already made settings.
1. Select the correct sensor settings from each dropdown
menu.
2. Click the pencil icons (B) to do additional settings for those
sensors.
Note: If you continue the Setup wizard without selecting the
pencil icons and changing the settings, the default settings from
the factory are used. When there are pencil icons in the Setup
wizard, always select the pencil icons and make sure that you
have the correct settings.
3. Select save or skip to go to the next tab, (C), to configure
external controls such as push buttons or similar devices.
External controls can trigger a single command like a profile
bypass or alarm.
a. Select the pencil icon for additional settings. For example,
you can set a bypass timer or change the notification class
and the alarm text of an external alarm input.
4. Select save or skip to go to the next tab, (D), to adjust the
settings for the coils.
a. Select the dropdown menu to select the type of coil.
b. Select the pencil icon to do additional settings for the
selected coil.
5. Select save or skip to go to the next tab, (E), to configure
one or two fire inputs and up to three scenarios for what will
happen if one or both input sensors are triggered.
6. Select save. There is no option to skip to the next step.
eCO TOP
®
with Rotary heat exchanger - Installation and maintenance
15
FläktGroup DC_10430GB_20221117_R4 Specifications are subject to alteration without notice
8. CONTROL PANEL, OPERATIONS, COMMISSIONING
CONTROL SETTINGS
1. Select the dropdown menus and select the correct
alternatives for your unit regarding supply- and extract fan
controls and temperature, humidity and air quality controls.
2. Select save.
TIME, DATE AND UNITS
BA
The first tab (A) is selected automatically.
1. Select the dropdown menus to select time zone.
2. Select the clock icon to set the time.
3. Select the calendar icon to select date.
4. Select save or skip to go to the next tab, (B).
5. Select the dropdown menus to select the applicable units.
6. Select save.
EDIT PROFILES
You can configure up to five profiles. There are separate profiles
for Boost and Standby/Off. You can create individual time
schedules for each profile.
You can change the name on all profiles except the Boost
profile. The Boost profile starts the unit before the set start time
to make sure that the temperature is correct at the start time.
It is necessary to have a profile for night operation. In the night
profile, set the temperature control mode to Nightpurge and
select to enable the unit via temperature control.
The profile tab on the far right is for Standby/Off. To activate
room frost protection for Standby/Off, select to enable the unit
via temperature control.
1. Configure the profiles as is necessary for your unit
application.
2. Select save.
UNIT OPERATION SCHEDULER
This step lets you create a weekly schedule where you can select
different profiles for different time periods. The profile for unit off is
applied to the whole week until you add other profiles.
1. Select the week day for which you want to add a profile. A
popup with three icons appear.
A C
B
a. Select (A) to add a profile and select time period for that
profile.
b. Select (B) to edit the profile.
c. Select (C) o close the icons popup without making any
changes.
2. To edit an already added profile, select that profile. A popup
with six icons appear.
D E F G H J
a. Select (D) to add a different profile to the time period.
b. Select (E) to edit the currently selected profile.
c. Select (F) to copy the profile and apply it to another time
period.
d. Select (G) to delete the profile from the weekly schedule.
e. Select (H) to change the start and stop time for the profile.
f. Select (J) to close the icons popup without making any
changes.
3. Select the right tab (K) to set up exceptions for specific days,
weeks or months.
K
4. When the weekly schedule is finished, select save.
eCO TOP
®
with Rotary heat exchanger - Installation and maintenance
16
FläktGroup DC_10430GB_20221117_R4 Specifications are subject to alteration without notice
8. CONTROL PANEL, OPERATIONS, COMMISSIONING
START UP SETTINGS
This step lets you configure how the unit starts depending if it
is summer or winter. You can set the temperature threshold, the
startup delays and the damper delay. Make sure that the settings
are correct for the local weather conditions.
When the start up settings are finished, select save.
If you are not sure how to do these settings correctly, select
skip.
TO SET DEFAULT PAGE AND FINISH THE SETUP WIZARD
1. Select Control schematics or Dashboard to select the default
page for the user interface.
2. Select save. A notification asks you to restart the unit to
apply all settings.
3. Select save to restart the unit and load the selected default
page.
eCO TOP
®
with Rotary heat exchanger - Installation and maintenance
17
FläktGroup DC_10430GB_20221117_R4 Specifications are subject to alteration without notice
8. CONTROL PANEL, OPERATIONS, COMMISSIONING
8.3 HOME SCREEN
It comes in handy to have the tile menu set as home screen
as setpoints can be easily edited here. Nevertheless, also the
flow chart of the system could be the default page so note that
following descriptions are related to tile menu. From the Home
screen it is possible to determine how the unit is operating as
well as navigating to further screens, from which additional needs
can be configured.
BASIC FUNCTIONS
The following figures show the basic settings a user can control
from the tile menu if he is logged into an account with Operator or
Admin rights. Rectangle tiles shown in this description will further
be categorized as control tiles, while square tiles will be called
auxiliary tiles.
Setpoint for supply air volume flow/pressure. Also displays
current air volume flow/pressure and fan control loop. Press to
change setpoint manually.
Setpoint for extract air volume flow. Also displays current air
volume flow and fan output signal. Press to change setpoint
manually.
Setpoint for temperature control. Also displays current
temperature. Depending on configuration this view might change
(e.g. separate setpoints for heating and cooling). Also shows
the control type at which temperature the unit is controlling (e.g.
extract air).
Controller mode. Can be set to only heating/cooling, night purge
or automatic. Automatic will react to profile and summer/winter
changeover settings.
Current active profile. Also displays next switch in time schedule
and corresponding profile. Set to automatic to use time schedule
or select a profile manually.
Setpoint for humidity control. Also displays current humidity.
Depending on configuration this view might change.
Setpoint for outdoor air amount (damper state). Also displays
current value. Depending on configuration this may react to air
quality.
Setpoint for air quality. Also displays current air quality. Depending
on configuration this can be active or passive control.
eCO TOP
®
with Rotary heat exchanger - Installation and maintenance
18
FläktGroup DC_10430GB_20221117_R4 Specifications are subject to alteration without notice
8. CONTROL PANEL, OPERATIONS, COMMISSIONING
Bypass current profile for a certain number of minutes by another
profile.
Change configuration of profiles. Unit needs a switch of profile
before applying changes to current operating profile.
The home screen will always contain at least 3x3 tiles. If the
configuration doesn’t include enough settings this tile will be used
as a placeholder.
CHANGING CONTROL TILE VALUES
To change the basic settings mentioned above there can be two
different ways. Press a control tile and one of the following menus
show up.
Setpoints are changed by using the control wheel, which can
easily be dragged to the desired value. Also, the up and down
arrows allow accurate setting by predefined steps. The amount
of each step depends on the control value that is edited (e.g. air
volume flow steps are 100 m³/h, regarding this is the determined
unit for air volume flow).
Control types are changed by using an option dialog, from which
the user can choose a preconfigured number of behaviours.
USING AUXILIARY TILES
Auxiliary tiles do not allow individual changes to the current
operation of the unit but most of them have a temporary or
permanent effect on its behaviour.
Profile bypass Allows to run another profile for up to 60 min
(5 min steps) and switching automatically back
to time scheduled profile afterwards.
Edit profiles Change profile settings as shown before in the
SetupWizard.
FläktGroup Placeholder tile.
8.4 TIME AND DATE, LANGUAGE, BASIC SETTINGS
If you want to change time and date, language and basic settings
as shown in the SetupWizard there are two ways of doing so.
First way is easy but limited in possibilities of detailed settings.
1. Log into an account at Operator level or higher.
2. Press the Settings button in the menu bar.
3. Select Configuration.
4. Run the SetupWizard again by using the description above.
The second way will not lead through each desired setting but
allows additional detailed settings.
TIME AND DATE, LANGUAGE
1. Log into an account with admin rights
2. Press the Settings button in the menu bar.
3. Select Configuration.
4. Press Device.
5. In this menu you can set Device information, language,
synchronize time with your pc or an interface and change
web configuration.
eCO TOP
®
with Rotary heat exchanger - Installation and maintenance
19
FläktGroup DC_10430GB_20221117_R4 Specifications are subject to alteration without notice
8. CONTROL PANEL, OPERATIONS, COMMISSIONING
INTERFACES AND COMMUNICATION
1. Log into an account with admin rights
2. Press the Settings button in the menu bar.
3. Select Configuration.
4. Press Network.
5. In this menu you have the possibility to change the settings
of several protocols/interfaces such as TCP/IP, Modbus,
BACnet, Fieldbus and RS485.
USER SETTINGS
1. Log into an account with admin rights
2. Press the Settings button in the menu bar.
3. Select Configuration.
4. Press User.
5. In this menu you can change user settings of lower or equal
access level and edit your own user account by changing to
the next tab.
CONTROL TYPES
See chapter 9 for detailed information about configuration of
control functions.
TIME SCHEDULE
1. Log into an account with admin rights
2. Press the Time Schedule button in the menu bar. Depending
on your HMI and the screen size it might be necessary to use
the Down button.
3. Select Unit Operation Mode Schedular with the symbol on the
right to open another window. In the web HMI this may
require to manually allow a popup to open, depending on your
browser settings.
4. Configure the profile time schedule easily by clicking a period
and selecting the profile to be active. The following menu bar
will appear.
a. Press ‘+’ to add a new changeover at the point you clicked.
b. Press the pencil to edit the currently selected time schedule.
c. Press the two sheets to copy currently selected time
schedule to another day.
d. Press ‘-‘ to delete currently selected profile from the time
schedule.
e. Press the arrows to quickly change the start of currently
selected profile.
f. Press ‘x’ to close the menu bar.
5. Use the Exception tab to plan dates or even date ranges with
different behaviour to your normal time schedule.
6. Save your configuration with the green checkmark and close
the window with the red ‘x’.
7. Similar functions are available for a winter/summer
changeover by selecting Change Over Schedular in the Time
Schedule menu.
eCO TOP
®
with Rotary heat exchanger - Installation and maintenance
20
FläktGroup DC_10430GB_20221117_R4 Specifications are subject to alteration without notice
Alarms
Object name
SUP Electric heater 1
Protection Fault 101 2019-12-10
12:00:00
Alarmtext Priority Came
i
SELECT NOTIFICATION CLASSESACKNOWLEDGE SELECTION
1
i
2019-12-10
12:00:00
FläktGroup
Alarms
i
2019-12-10
12:00:00
No active alarms!
FläktGroup
Alarms
Object name
SUP Electric heater 1
Protection Fault 101 2019-12-10
12:00:00
Alarmtext Priority Came
i
SELECT NOTIFICATION CLASSES
1
i
2019-12-10
12:00:00
FläktGroup
Alarms
Object name
SUP Electric heater 1
Protection Fault 101 2019-12-10
12:00:00
Alarmtext Priority Came
i
SELECT NOTIFICATION CLASSES
1
i
2019-12-10
12:00:00
FläktGroup
8. CONTROL PANEL, OPERATIONS, COMMISSIONING
If an alarm occurs, it is indicated by a red marker at the alarms
symbol in the menu bar. Also, the number of alarms is displayed.
Pressing the alarm button leads to the alarms overview.
Select the blue info button on the right to see more details about
the alarm. Critical alarms automatically stop the unit until they are
fixed. If the issue is solved in alarms menu the error is scored out.
By clicking the checkbox of the alarm, you can now acknowledge
it, which sets the unit back to normal operation.
After solving and acknowledging all errors the alarms menu
should show no active alarm anymore.
8.5 ALARMS
See section 12.9 for a complete list of alarms, their causes and
what actions to take.
UNIT CONVERSION
In order to change e.g. from m3/s to m3/h or l/s you should
click first the settings icon and then go to
Configuration g Network g BACnet g Unit conversion
Choose desired unit and press START button.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48

FläktGroup eCO TOP Installation and Maintenance Manual

Category
Split-system air conditioners
Type
Installation and Maintenance Manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI