Trend T/PC Installation guide

Type
Installation guide
T/PC PRT Contact Temperature Sensor Installation Instructions TG100508A Issue 5, 28/08/09
1
Installation Instructions
T/PC
PRT Contact Temperature Sensor
Important: Retain these instructions
T / P C
M A N U F A C T U R E D I N E U
T R E N D C O N T R O L S Y S T E M S
L T D U K
Dimensions
INSTALLATION
1
T/PC Installation
Instructions TG100508
97 mm (3.82”)
UNPACKING
117 mm (4.61”)
57 mm (2.24”)
2 m (6’6”) cable
Requirements
2
H O
2
0 %RH 95 %RH
Protection :IP67, NEMA6
measurement range
/-40 -40 °C to +50 °C
(-40 °F to +122 °F)
/40 -10 °C to +40 °C
(+14 °F to +104 °F)
/110 -10 °C to +110 °C
(+14 °F to +230 °F)
/160 -10 °C to +160 °C
(+14 °F to +320 °F)
T / P C
M A N U F A C T U R E D I N E U
T R E N D C O N T R O L S Y S T E M S
L T D U K
2 m (6’6”) max
-40 °C to +50 °C
(-40 °F to +122 °F)
T/PC Installation Instructions
T/PC PRT Contact Temperature Sensor Installation Instructions TG100508A Issue5, 28/08/09
2
Mount on Wall
INSTALLATION (continued)
3
ab
85 mm (3.35”)
Mount Probe
4
either use jubilee clip (provided)
or use cable tie(s) (not provided)
recommended use of thermally conductive paste (not provided)
Remove Lid
5
a
b
Drill 2 pilot holes
Tighten 2 screws
2 off No 6 (M3.5) screws
Remove Connector
6
Caution: This unit contains static
sensitive devices. Suitable
anti-static precautions
should be taken throughtout
the operation to prevent
damage to the units. BS EN100015/
1 Basic Specification: protection of
electrostatic sensitive devices.
Ø203 mm (8”) max.
T/PC PRT Contact Temperature Sensor Installation Instructions TG100508A Issue 5, 28/08/09
3
Installation Instructions T/PC
INSTALLATION (continued)
Wire to Controller
8
Insert Cable
7
either use M20 flexible conduit
or use M16 cable gland
IQ1xx, IQ2xx
polarity independent
Sensor
24 Vdc
IN
Terminate screen at IQ end only
Analogue input
channel linked
for current (I)
I
IQ system TP/I/22/HF/200 (Belden
8761) cable recommended.
Terminal size 0.5 to 2.5 mm
2
(20 to
14 AWG)
IQ3
Sensor
0 (0 V)
N (in)
Note that if connecting to an IQ22x controller (including /ADL or /OC), do not connect directly to C (+24V),
instead connect to AUX+ (+24V).
+ (24 V)
Replace Connector
9
Replace Lid
10
a
b
Note that IP67 (NEMA6) rating is only achieved if the sensor is correctly installed with
cable or conduit connection fully tightened.
N
T/PC Installation Instructions
T/PC PRT Contact Temperature Sensor Installation Instructions TG100508A Issue 5, 28/08/09
4
Please send any comments about this or any other Trend technical publication to [email protected]
© 2009 Honeywell Technologies Sàrl, ECC Divison. All rights reserved. Manufactured for and on behalf of the Environmental and Combustion Controls
Division of Honeywell Technologies Sàrl, Z.A. La Pièce, 16, 1180 Rolle, Switzerland by its Authorized Representative.
Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content hereof
without obligation to notify any person of such revisions or changes.
Trend Control Systems Limited
Albery House, Springfield Road, Horsham, West Sussex, RH12 2PQ, UK. Tel:+44 (0)1403 21888 Fax:+44 (0)1403 241608 www.trendcontrols.com
Trend Control Systems USA
6670 185th Avenue NE, Redmond, Washington 98052, USA. Tel: (425)897-3900, Fax: (425)869-8445 www.trendcontrols.com
T / P C
M A N U F A C T U R E D I N E U
T R E N D C O N T R O L S Y S T E M S
L T D U K
WEEE Directive :
At the end of their useful life the
packaging and product should be
disposed of by a suitable recycling
centre.
Do not dispose of with normal household waste.
Do not burn.
Set up IQ Sensor Type
12
It is recommended to use SET (Software Tool) for the setting of the sensor type module.
For all IQ2 series controllers with firmware version 2.1 or greater, or IQ3 series controllers,
the following SET Unique Sensor References should be used:
(T/PC/-40) PRT I -40+50 (°C) PRT I -40+122 F (°F)
(T/PC/40) PRT I -10+40 (°C) PRT I +14+104 F (°F)
(T/PC/110) PRT I -10+110 (°C) PRT I +14+230 F (°F)
(T/PC/160) PRT I -10+160 (°C) PRT I +14+320 F (°F)
Alternatively set scaling mode to 5 (characterise) and enter scaling manually as detailed in
appropriate table below. Note that for IQ3 the scaling mode and exponent (E) do not need
to be set up.
For all other IQ controllers see Sensor Scaling Reference Card TB100521A
INSTALLATION (continued)
Configure IQ
11
I Q
I Q
or
IQ Configuration Manual
90-1533
Test System
13
IQ
tinU04-/04/011/061/
Y
epyttupni)tnerruc(2)tnerruc(2)tnerruc(2)tnerruc(2
E
tnenopxE 3333
stinUC°F°C°F°C°F°C°F°
U
reppU05221044010110320610
23
L
rewoL04-04-01-4101-4101-41
P
stnioP 22222222
x
xIxOxOxOxOxOxOxOxO
1
404-04-01-4101-4101-41
2
020522104401011032061023
T
DISPOSAL
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

Trend T/PC Installation guide

Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI