  • Hello! I have analyzed the provided Quick Installation Guide for Solplanet inverters ASW3000H-S2, ASW3680H-S2, ASW4000H-S2, ASW5000H-S2, and ASW6000H-S2. This document provides safety instructions, mounting guidelines, and connection details for AC, EPS, DC, battery, and communication setups. I'm ready to answer any questions you may have about the installation process or the features described in this guide.
  • What type of batteries are compatible with this inverter?
    What should I do before establishing electrical connections?
    What kind of communication cables should be used?
3
2
1
QuickInstallationGuide
ASW3000H-S2/ASW3680H-S2
ASW4000H-S2/ASW5000H-S2
ASW6000H-S2
English
I.SafetyInstruction
1.Thecontentsofthisdocumentwillbeupdatedirregularlyforproductversionupgradeorother
reasons.Unlessotherwisespecified,thisdocumentonlyworksasguide.Allstatements,
informationandsuggestionsinthisdocumentdonotconstituteanyguarantee.
2.Thisproductcanonlybeinstalled,commissioned,operatedandmaintainedbytechnicianswho
havecarefullyreadandfullyunderstoodtheusermanual.
3.ThisproductmustonlybeconnectedwithPVmodulesofprotectionclassII(inaccordancewith
IEC61730,applicationclassA).PVmoduleswithahighcapacitancetogroundmustonlybeused
iftheircapacitydoesnotexceed1.5μF.DonotconnectanysourcesofenergyotherthanPV
modulestotheproduct.
.Theproductmustonlybeoperatedinconnectionwithanintrinsicallysafelithium-ionbattery4
approvedbyAISWEI.Thebatterymustcomplywiththelocallyapplicablestandardsand
directivesandmustbeintrinsicallysafe.
5.Thecommunicationinterfaceofthebatteryusedmustbecompatiblewiththeproduct.The
entirebatteryvoltagerangemustbecompletelywithinthepermissibleinputvoltagerangeof
theproduct.ThemaximumpermissibleDCinputvoltageoftheproductmustnotbeexceeded.
6.ThePVmodulesgeneratedangeroushighDCvoltagewhichispresentintheDCcableconductors
andlivecomponents. heDCcablesconnectedtoabatterymaybelive.TouchingliveDCcableT
conductorsandlivecomponentscanresultinlethalinjuriesduetoelectricshock.
llcomponentsmustremainwithintheirpermittedoperatingrangesatalltimes7.A .
II.Mountingenvironment
III.Scopeofdelivery
Inverterx1 DCconnectorx2
Documentationx1
IV.Invertersmounting VI.Batteryconnection
V.AC&EPSconnection
DANGER
1
3
2
VII.DCconnection
Wallmountingbracketx1
Smartmeterx1
ACconnectorx2
Screwaccessoryx1
Batteryterminalcoverx1 WiFistick
RS485Communicationclientx2
▪Allelectricalinstallationsmustbedoneinaccordancewithalllocalandnationalrules.
▪MakesurethatallDCswitchesandACcircuitbreakershavebeendisconnectedbefore
establishingelectricalconnection.Otherwise,thehighvoltagewithintheinverter
mayleadtoelectricalshock.
▪Inaccordancewithsafetyregulations,theinverterneedbegroundedfirmly.When
poorgroundconnection(PE)occurs,theinverterwillreportPEgroundingerror.Please
checkandensurethattheinverterisgroundedfirmlyorcontactAISWEIservice.
DANGER
MakesurePVmoduleshavegoodinsulationagainstground.
▪Onthecoldestdaybasedonstatisticalrecords,theMax.open-circuitvoltageofthe
PVmodulesmustnotexceedtheMax.inputvoltageoftheinverter.
CheckthepolarityofDCcables.
EnsurethatDCswitchhasbeendisconnected.
DonotdisconnectDCconnectorsunderload.
300mm
300mm
500mm 500mm
500mm
3holesΦ10
1
4
2
5
3
M4PH22.5Nm
3
1.4Nm
M41.6Nm
4-6mm2
PE
PEmustbe2mmlongerthantheLandN
4-6mm2
Φ10-16mm
53mm
13mm
AC
3
2
11.4Nm
PE
PEmustbe2mmlongerthantheLandN
2.5-6mm2
Φ10-16mm
53mm
13mm
EPS
4
5
4
Thelithiumbattery(pack)capacityshouldbe50Ahorlarger.
Leadacidbatteriesarenotallowed.
batterytyp AISWEIThe emustbeapprovedby .
DANGER
1
4
20-25mm2
55mm
Φ10-12mm
2
M64.0Nm
3
M41.6Nm
IP66
4K4H
1 2
56
PV1-F/UL-ZKLA/USE2
2.5-6mm2
Φ5-8mm
12mm
4
1
1
Pin1=NC
Pin2=GND
Pin3=NC
Pin4=CANH
Pin5=CANL
Pin6=NC
Pin7=NC
Pin8=NC
Pin1Pin8
Pin1=TX_RS485A
Pin2=TX_RS485B
Pin3=NC
Pin4=GND
Pin5=NC
Pin6=NC
Pin7=NC
Pin8=NC
Pin1Pin8
4
IX.CommunicationsetupVIII.Smartmeterconnection
Notice
XI.EUDeclarationofConformity
X.Commissioning XII.Contact
6
5
Theconnectionrefersto GPRS/WiFi-stickUserManual”.
Checkthattheinverterisgroundedreliably.
Checkthattheventilationconditionsurroundingtheinverterisgood.
Checkthatthegridvoltageatthepointofconnectionoftheinverteriswithinthe
permittedrange.
CheckthatthesealingplugsinDCconnectorsandcommunicationcableglandsare
sealedtightly.
Checkthatgrid/batteryconnectionregulationsandotherparametersettingsmeet
safetyrequirements.
CheckthecorrectcommunicationconnectionbetweenthebatteryBMSandtheinverter.
Checkthecorrectcommunicationconnectionbetweenthesmartmeterandtheinverter.
1.SwitchonACcircuitbreakerbetweentheinverterandthegrid.
2.SwitchonDCswitch.
3.Switchonbattery.
4.LinktoinverterWiFi.
5.Setthecommunicationparametersofthesmartmeter.
6.SetparametersthroughApp(Safety,Smartmeter,Battery,Working-mode).
7. Clickpower-onbuttonthroughApp,Energystorageinverterwillstarttowork.
WithinthescopeoftheEUdirectives:
-Electromagneticcompatibility2014/30/EU(L96/79-106March29,2014)(EMC)
-Lowvoltagedirective2014/35/EU(L96/357-374March29,2014)(LVD)
-Radioequipmentdirective2014/53/EU(L153/62-106May22,2014)(RED)
AISWEITechnology(Shanghai)Co.,Ltd.confirmsherewiththattheinverters
mentionedinthisdocumentareincompliancewiththefundamentalrequirementsand
otherrelevantprovisionsoftheabovementioneddirectives.
TheentireEUDeclarationofConformitycanbefoundatwww.aiswei-tech.com.
Ifyouhaveanytechnicalproblemswithourproducts,pleasecontactourservice.
Werequirethefollowinginformationinordertoprovideyouwiththenecessaryassistance:
-Inverterdevicetype
-Inverterserialnumber
-Batterytype
-TypeandnumberofconnectedPVmodules
-Errorcode
-Mountinglocation
-Warrantycard
EMEA
Serviceemail:service.EMEA@solplant.net
APAC
Serviceemail:service.APAC@solplanet.net
LATAM
Serviceemail:service.LATAM@solplanet.net
AisweiGreaterChina
Serviceemail:service.china@aiswei-tech.com
Hotline:+864008019996
Taiwan
Serviceemail:service.taiwan@aiswei-tech.com
Hotline:+886809089212
https://solplanet.net/contact-us/
Foroutdooruse,thecommunicationcablesmustbeUV-resistant.
MakesureACcableistotallyisolatedfromACpowerbeforeconnecting.
DANGER
Connectiondiagram
N
L
Grid 12
3 4
L
N
11
22
3
4
5
6
6
5
RS485A
RS485B
PH00.7Nm
1.Smartmetercommunication
2.ACcableconnection
N
L
Grid
12L
N
34
PH21.6Nm
6
5
Separatecommunicationcablesfrompowercablesandseriousinterferencesources.
ThecommunicationcablesmustbeCAT-5Eorhigher-levelshieldcables.Pin
assignmentcomplieswithEIA/TIA568Bstandard.Foroutdooruse,thecommunication
cablesmustbeUV-resistant.Thetotallengthofcommunicationcablecannotexceed
1000m.
DANGER
1.BMScommunication
22
3
456
2.WiFi
22
3
1
/