17
Configuring and calibrating inputs
Most OpenBAS controllers have universal inputs which allow users to connect either an analog or binary
signal into them. There is no need (or option) to specify in software that a universal input is being used
as either a binary or analog input, just calibrate and name the respective point. For example, when there
is a voltage of 3V DC on universal input 1, analog input 1’s (AI_1) present value (if calibrated as a 0-10V
input) will read 3 Volts but binary input 1’s (BI_1) present value will read 0 (zero). For more information
on wiring and connecting different types of inputs, see the installation manual (for any OpenBAS
controller with universal inputs).
• Go to Configuration->Inputs Outputs and select the Universal input option from the main
dropdown box.
• Under the Analog input calibration header, users can select input types, define units,
and further calibrate an analog input’s present value property with either an offset
value or multiplier depending on the input type.
▪ When changing the offset or multiplier, the respective analog input’s present
value property will be updated at a faster rate to allow a user to better match
the real time value of a multimeter or other measuring device.
• For noisy or unstable inputs, under the Universal input averaging header, the universal
inputs 1 through 8 can be averaged over a multiple of 200ms for analog inputs, and a
multiple of 50ms for binary inputs. In addition, there is a “global AI averaging”
calibration parameter located in Configuration->Inputs outputs->General which affects
all 40 analog inputs. When analog inputs 1 through 8 have their individual input
averaging calibration parameters set to 0 (zero), they will use the global AI calibration
parameter instead.
• The “Invert local binary input logic” option will change binary input 1 through 8 to use
“active-low” logic which is useful when all of the universal inputs (which are being used
as binary inputs) have their internal pull up resistor enabled and are wired through
equipment status relays to ground. The internal pull up resistors can be enabled with
dipswitches or jumper pins (depending on the controller) and are referenced in the
OpenBAS controller installation manuals (under the section for connecting resistive
temperature sensors).
• “OpenBAS-HV-NXSF CT input noise level” within Configuration->Inputs outputs-
>General, will subtract a raw 12 bit number from the AI_1 to AI_8 raw input values (that
are configured as “Current Transformer (1000:1)” type inputs) on the OpenBAS-HV-NXSF
controller. This is useful for current metering applications where the connected CTs
have some noise due to large nearby electrical currents. This setting can take a value
between 0 (zero) and 50 otherwise it will be disabled. After installation, configure all AI’s
that are connected to CTs as “12-bit ADC” type inputs and find the maximum of their
present values, while the measured circuits are off. Use this maximum value as the
“OpenBAS-HV-NXSF CT input noise level” and then don’t forget to configure each Analog
input back to “Current Transformer (1000:1)” type inputs.