Skov Dynamic Air Kit Mounting Guide

Type
Mounting Guide
2021.02.25 • 603006
Dynamic Air Kit
Mounting Guide
English: For other language variants of this document we refer to:
Español: Para otras variantes del idioma de este documento, visite:
Français: Pour les versions dans d'autres langues de ce document veuillez consulter:
http://docs.skov.com/1171
Mounting Guide 2
Dynamic Air Kit
Product and Documentation Revision
SKOV A/S reserve the right to change this document and the product herein described without further notice.
In case of doubt, please contact SKOV A/S.
Date of change appears from the front and back of this manual. It was released in 2012.
IMPORTANT
NOTE CONCERNING ALARM SYSTEM
Where climatic control is used in livestock buildings, breakdowns, malfunctions or faulty settings may cause
substantial damage and financial losses. It is therefore most important to install a separate, independent alarm
system, which monitors the climate in the livestock house concurrently with the climate computer. According
to EU-directive No. 98/58/EU an alarm system must be installed in all mechanically ventilated houses.
SKOV A/S would like to draw your attention to the fact that the product liability clause of general terms and
conditions of sale and delivery from SKOV A/S specifies that an alarm system must be installed.
In case of operating error or improper use, ventilation systems can result in production loss or
cause loss of lives among animals.
SKOV A/S recommend that ventilation systems should be mounted, operated and serviced only
by trained staff and that a separate emergency opening unit and an alarm system be installed as
well as maintained and tested at regular intervals, according to SKOV A/S terms and conditions
of sale and delivery.
Note
All rights reserved SKOV A/S. No part of this manual may be reproduced in any manner whatsoever
without the express written permission from SKOV A/S.
SKOV A/S have made all reasonable efforts to ensure the accuracy of the information contained in this
manual. Should any mistakes or imprecise information occur in spite of this, SKOV A/S would
appreciate being notified thereof.
Irrespective of the above, SKOV A/S shall not accept any liability with regard to loss or damage caused
or alleged to be caused by reliance on any information contained herein.
Copyright 2012 by SKOV A/S.
Mounting Guide 3
Dynamic Air Kit
1 Product Description................................................................................................. 4
2 Mounting Guide ....................................................................................................... 4
2.1 Checking Parts .................................................................................................................... 4
2.2 Remove Cabinet Cover ....................................................................................................... 5
2.3 Placing of the Sensor ......................................................................................................... 5
2.3.1 DA 600 / DA 820 Chimney ...................................................................................................................... 5
2.3.2 DA 920 Chimney with Swivel Shutter Module ......................................................................................... 8
2.4 Mounting Tube for Reference Pressure .......................................................................... 11
2.5 Mounting the Cabinet Cover............................................................................................. 12
3 Electric Connection ................................................................................................12
3.1 Circuit Diagram ................................................................................................................. 13
4 Setting of Dynamic Air Sensor ..............................................................................13
5 Control .....................................................................................................................14
6 Maintenance Instructions .......................................................................................14
7 Trouble Shooting Instructions ...............................................................................14
8 Technical Data ........................................................................................................15
4 Mounting Guide
Dynamic Air Kit
1 Product Description
The Dynamic Air sensor is available in two different versions with different measuring ranges: one for use on
chimneys and one for use on take-offs in connection with a central duct for central exhaust.
When using Dynamic Air, a pressure sensor is placed in one or more of the stepless air outlets. The climate
computer uses the measurement of the current pressure in the chimney to calculate the air output and thus to
optimise the air change in the house without the use of any moving mechanical components and without
increasing air resistance in the air outlet.
Dynamic Air - kit for bell mouth/chimney
Pressure sensor for retrofitting in chimneys in houses where measurement of pressure levels in air outlets is
desired. The pressure sensor is mounted on the bell mouth in one or several stepless chimneys.
This kit is used together with a software update for the DOL 53X, DOL 63X and DOL 234/DOL 234F climate
computers (versions 6.1/7.1or later).
Dynamic Air - kit for bell mouth/duct
Pressure sensor for retrofitting on take-offs in houses with central exhaust.
When a Dynamic Air bell mouth/duct sensor is installed per section, the actual volume of air can be measured
per section, and it can be regulated via fan revolutions/shutter position in the take-offs.
This kit is used together with a software update for the DOL 53X, DOL 63X and DOL 234F climate computer
(version 7.2 or later).
2 Mounting Guide
If only one sensor is used to regulate two stepless air outlets, the positions of these outlets must be comparable
in relation to wind impacts as climate computer will then base its control on a calculated output.
2.1 Checking Parts
Check that the ordered parts have been received and that they are in undamaged condition before the
installation process is initiated.
Cabinet including sensor
Distance piece
One terminal block 4P
Four 5x40 screws
Four 3.5x10 screws
Four 4x16 screws
Four rawlplugs
Mounting template 600 chimney
Mounting Guide
Mounting Guide 5
Dynamic Air Kit
2.2 Remove Cabinet Cover
Open the cover by getting a grip on one side and
pulling.
2.3 Placing of the Sensor
IMPORTANT!
The cabinet must always be
placed vertically, as the sensor
membrane only function
correctly if it is placed
vertically.
2.3.1 DA 600 / DA 820 Chimney
The cabinet should be placed on
the face of the bell mouth on the
side where the swivel shutter
opens downwards.
OK
OK
Dynamic air
sensor
6 Mounting Guide
Dynamic Air Kit
Figure 1
Dynamic Air mouth/chimney
Place the cabinet base on the distance piece and
the socket piece through the centre hole and fasten
it with the included four 5x40 screws.
Dynamic Air bell mouth/duct
Figure 2
Dynamic Air mouth/chimney
Please note that the cabinet must be turned so
the pressure sensor turns the socket piece
downwards.
Dynamic Air bell mouth/duct
Mounting Guide 7
Dynamic Air Kit
Figure 3
See paragraph 2.5 for mounting of cabinet cover.
8 Mounting Guide
Dynamic Air Kit
2.3.2 DA 920 Chimney with Swivel Shutter Module
The sensor cabinet should be
placed on the face of the swivel
shutter module on the side where
the swivel shutter opens
downwards.
Figure 4
Pressure sensor mounted on a 920 exhaust unit
with swivel shutter module.
Figure 5
Measure and mark out the centre between two ribs
on the bell mouth.
Figure 6
Measure 11cm from the edge of the bell mouth at
the centre marker.
Dynamic air sensor
Mounting Guide 9
Dynamic Air Kit
Figure 7
Make a pilot orifice with a smaller drill bit.
Drill an Ø11mm hole.
Figure 8
Cut the four supports off the cabinet base.
Be careful not to damage the socket piece.
Figure 9
Place the cabinet base so the socket piece is in the
hole.
Figure 10
Please note that the cabinet must be turned so
the pressure sensor turns the socket piece
downwards.
11 cm
10 Mounting Guide
Dynamic Air Kit
Figure 11
Mount the cabinet base using the four enclosed
4x13mm chipboard screws.
Figure 12
Pressure metering point seen from the inside of
the exhaust duct.
Figure 13
See paragraph 2.5 for mounting of cabinet cover.
Mounting Guide 11
Dynamic Air Kit
2.4 Mounting Tube for Reference Pressure
Run a plastic tube for reference pressure from the sensor to the house section, when the Dynamic Air pressure
sensor is mounted outside the house section.
Figure 14
Cut off the recess in the cover so there is space to
run the tube out of the cabinet.
Figure 15
Mount the tube on the light grey nozzle (P1).
Figure 16
Run the tube down into the hole and click on the
cover.
Figure 17
Drill a hole in the covering of the ceiling/roof and
run the tube through the hole without jamming the
tube.
12 Mounting Guide
Dynamic Air Kit
2.5 Mounting the Cabinet Cover
Figure 18
Click on the cover.
Figure 19
Check that the arrow on the cabinet cover is
pointing upwards.
Figure 20
Fix the cable to the chimney pipe.
3 Electric Connection
Connect the pressure sensor to the house
computer, perhaps via the swivel shutter motor.
Use a four-core cable unshielded (4x0.25 mm2).
See circuit diagram below.
Run the blue and black wire separately to the
climate computer where the wires should be
connected in a negative terminal.
Do not connect the wires to other earth wires on
the way to the computer
Mounting Guide 13
Dynamic Air Kit
3.1 Circuit Diagram
4 Setting of Dynamic Air Sensor
Select the menu Technical/Setup/Installation/Climate/Outlet/
Side outlet/Stepless/Dynamic Air stepless
(1) Number of stepless air outlets connected to 1-1.
(2) Number of units installed with Dynamic Air on 1-1.
Select the menu Technical/Setup/Adjustment/Climate/Dynamic
Air
In livestock houses with direct exhaustion, the fan speed is
regulated.
In livestock houses with a duct system, the flap is regulated
(according to a curve value).
Select operation mode:
Dynamic Flow: Measurement of the actual air
volume.
Dynamic Control: Measurement and control
according to the actual air volume.
Ex. of terminal number
For correct connection,
see the setup menu
Show Installation in climate computer
Run the blue and black wire separately
to the climate computer where the wires
should be connected in a negative
terminal.
Do not connect the wires to other earth
wires on the way to the computer.
(1)
(2)
14 Mounting Guide
Dynamic Air Kit
Choose chimney type:
DA 600 (with fan)
DA 600 no fan
DA 820 (with fan)
DA 820 no fan
DA 920 (with fan)
DA 920 no fan
5 Control
Check the Dynamic Air value in the menu
Climate/Ventilation/Info/Ventilation status/Dynamic Air stepless
6 Maintenance Instructions
The Dynamic Air sensor is maintenance-free and does not require calibration.
It stands high-pressure cleaning. Avoid spraying on the edge of the cover from the back.
Clean the socket piece carefully with an Ø8mm drill bit, in case it lutes.
7 Trouble Shooting Instructions
If the sensor measures less than expected:
Check the measurement by setting the system to manual control and running it at max. and min. air
output.
Check if the read-out on the house computer corresponds to what is expected.
Check if the flap opening corresponds to what is expected.
Check if the socket piece inside the exhaust unit has luted.
Mounting Guide 15
Dynamic Air Kit
8 Technical Data
Dynamic Air kit
Dynamic Air
mouth/chimney
Dynamic Air
bell mouth/duct
Electrical Setup
Supply voltage
24 V (18-30 VDC)
24 V (10-33 V DC)
Power consumption
2,6 W / 0,11 A
1.0 W / 0.04 A
Min. voltage
0.5V
0 V
Max. voltage
4.5V
10 V
Mechanical Design
Cable
4 x 0.25 mm2 unshielded
4 x 0.25 mm2 unshielded
Measuring range
0-300 Pa
0-100 Pa
Air quantity with completely open shutter
5,000-16,000 m3/h
3,500-10,000 m3/h
Program version in the computer
DOL 234
6.1 or newer
DOL 234F
7.1 or newer
7.2 or newer
Environment
Ambient temperature, operation
0 to +70°C (+ 32 to 158°F)
-17.8 til +60 °C (0 til 140 °F)
Ambient temperature, storage
-30 to +70°C (- 22 to +158°F)
-17.8 til +60 °C (0 til 140 °F)
Shipping
Dimensions
H × W × D: 115 x 128 x 105 mm
H x B x D: 115 x 128 x 105 mm
Dimensions when packed
H × W × D: 220x135x140 mm
H x B x D: 220x135x140 mm
Shipping weight
2850 g
2850 g
Figure 21: Dimension Dynamic Air sensor.
SKOV A/S • Hedelund 4 • Glyngøre • DK-7870 Roslev
Tel. +45 72 17 55 55 • Fax +45 72 17 59 59 • www.skov.com • E-mail: [email protected]
2021.02.25 • 603006 04.02.00 • EN • Made in Denmark
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6