Rockwell Automation Allen-Bradley 1756-EWEB User manual

Type
User manual
ControlLogix EtherNet/IP Network Devices
Catalog Numbers 1756-EN2F, 1756-EN2T, 1756-EN2TK, 1756-EN2TP, 1756-EN2TPK, 1756-EN2TPXT, 1756-EN2TR, 1756-
EN2TRK, 1756-EN2TRXT, 1756-EN2TSC, 1756-EN2TXT, 1756-EN3TR, 1756-EN3TRK, 1756-EN4TR, 1756-EN4TRK, 1756-
EN4TRXT, 1756-ENBT, 1756-ENBTK, 1756-EWEB
User Manual
Original Instructions
Important User Information
Read this document and the documents listed in the additional resources section about installation, configuration, and
operation of this equipment before you install, configure, operate, or maintain this product. Users are required to
familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws,
and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are
required to be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may
be impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from
the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
Labels may also be on or inside the equipment to provide specific precautions.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous
environment, which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
IMPORTANT Identifies information that is critical for successful application and understanding of the product.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to
potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL
Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).
Rockwell Automation Publication 1756-UM004A-EN-P - March 2019 3
Table of Contents
Table of Contents
Preface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Conventions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Chapter 1
ControlLogix EtherNet/IP
Network Device Overview
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
ControlLogix Network Device Features. . . . . . . . . . . . . . . . . . . . . . . . . . 7
EtherNet/IP Network Specifications. . . . . . . . . . . . . . . . . . . . . . . . 10
Electronic Keying . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Protected Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Enabling Explicit Protected Mode . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Disabling Explicit Protected Mode . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Secure Digital Card. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Secure Digital Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Disable Secure Digital Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
CIP Security . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Chapter 2
Connect to the EtherNet/IP
Network
Set the IP Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Set the IP Address with Rotary Switches . . . . . . . . . . . . . . . . . . . . . . . . 18
Other Methods to Set the IP Address . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Reset the Module IP Address to Factory Default Value . . . . . . . . . . . 19
Appendix A
ControlLogix Network Device
Status Indicators
Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Single-Port Module Status Indicators . . . . . . . . . . . . . . . . . . . . . . . 24
Dual-Port Module Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . 25
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
4 Rockwell Automation Publication 1756-UM004A-EN-P - March 2019
Table of Contents
Notes:
Rockwell Automation Publication 1756-UM004A-EN-P - March 2019 5
Preface
This manual describes how you can use ControlLogix® EtherNet/IP
communication modules with a Logix 5000™ controller and communicate with
various devices on the Ethernet/IP network.
Use this manual if you program applications that use EtherNet/IP networks
with these Logix 5000 controllers:
CompactLogix™ controller
•ControlLogix controller
Conventions
Be sure to understand these concepts and tools:
•FactoryTalk® Linx
Logix Designer
•ControlFLASH Plus
•HMIs
•SNMP tools
Additional Resources
These documents contain additional information concerning related products
from Rockwell Automation.
Resource Description
1756 ControlLogix Communication Modules Specifications,
publication 1756-TD003
Specifications for ControlLogix communication
modules.
Ethernet Design Considerations Reference Manual,
publication ENET-RM002
Provides details about how to use EtherNet/IP
communication modules with Logix 5000 controllers
and communicate with other devices on the
EtherNet/IP network.
EtherNet/IP Network Devices User Manual,
publication ENET-UM006
Describes how to install, configure, and operate the
Compact 5000™ I/O EtherNet/IP adapters.
EtherNet/IP Modules Installation Instructions,
publication ENET-IN002
Provides information about how to complete these
tasks with EtherNet/IP communication modules in a
Logix 5000 control system:
Install the module
Configure initial application setup
Troubleshoot application anomalies that are
related to EtherNet/IP communication module use
EtherNet/IP Media Planning and Installation Manual
This manual is available from the Open DeviceNeVendor
Association (ODVA) at: http://www.odva.org.
Provides details about how to install, configure, and
maintain linear and Device Level Ring (DLR) networks
by using Rockwell Automation EtherNet/IP devices
that are equipped with embedded switch technology.
EtherNet/IP Embedded Switch Technology Application
Guide, publication ENET-AP005
Provides details about how to install, configure, and
maintain linear and Device Level Ring (DLR) networks
by using Rockwell Automation EtherNet/IP devices
that are equipped with embedded switch technology.
EtherNet/IP Device Level Ring Application Technique,
publication ENET-AT007
Describes DLR network operation, topologies,
configuration considerations, and diagnostic
methods.
6 Rockwell Automation Publication 1756-UM004A-EN-P - March 2019
Preface
You can view or download publications at
http://www.rockwellautomation.com/global/literature-library/overview.page
.
To order paper copies of technical documentation, contact your local
Allen-Bradley distributor or Rockwell Automation sales representative.
EtherNet/IP Socket Interface Application Technique,
publication ENET-AT002
Describes the socket interface that you can use to
program MSG instructions to communicate between a
Logix5000 controller via an EtherNet/IP module and
Ethernet devices that do not support the EtherNet/IP
application protocol, such as bar code scanners, RFID
readers, or other standard Ethernet devices.
Troubleshoot EtherNet/IP Networks Application Technique,
publication ENET-AT003
Provides details about how to assign IP addresses to
and how to troubleshoot EtherNet/IP networks and
devices.
Industrial Automation Wiring and Grounding Guidelines,
publication 1770-4.1
Provides general guidelines for installing a Rockwell
Automation industrial system.
Product Certifications website, http://
www.rockwellautomation.com/global/certification/
overview.page
Provides declarations of conformity, certificates, and
other certification details.
Resource Description
Rockwell Automation Publication 1756-UM004A-EN-P - March 2019 7
Chapter 1
ControlLogix EtherNet/IP Network Device
Overview
Overview
EtherNet/IP™ networks are communication networks that offer a
comprehensive suite of messages and services for many automation
applications.
This open network standard uses commonly available Ethernet
communication products to support real-time I/O messaging, information
exchange, and general messaging.
ControlLogix Network Device
Features
The ControlLogix® EtherNet/IP network devices:
Facilitate high-speed data transfer between some Logix 5000™
controllers and remote I/O modules.
Connect to multiple EtherNet/IP network topologies.
Topic Page
Overview 7
ControlLogix Network Device Features 7
Electronic Keying 11
Protected Mode 12
Secure Digital Card 13
CIP Security 15
8 Rockwell Automation Publication 1756-UM004A-EN-P - March 2019
Chapter 1 ControlLogix EtherNet/IP Network Device Overview
Figure 1 shows how Rockwell Automation EtherNet/IP communication
modules fit into a control system.
Figure 1 - EtherNet/IP Communication Modules in a Control System
STATUS
NET
LINK 1
LINK 2
5094-AENTR
EtherNet/IP
Adapter
FLEX 5000
TM
I/O
PRP
DLR
POWER
X100
X10
X1
IP ADDRESS
STATUS
POWER
DIGITAL 16 INPUT 24 VDC
5094-IB16
1
1
TB3
FLEX 5000
TM
I/O
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
STATUS
POWER
DIGITAL 16 OUTPUT 24 VDC
5094-OB16
1
2
TB3
FLEX 5000
TM
I/O
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
STATUS
POWER
RELAY 8 OUTPUT ISOLATED
5094-OW8I
2
2
TB3W
FLEX 5000
TM
I/O
0 1 2 3 4 5 6 7
Logix5575
Redundancy Module
EtherNet/IP
PRI COM OK
ControlNet
EtherNet/IP
ControlNet
OKFORCE SDRUN
R
U
N
R
E
M
P
R
O
G
1 2
LNK1 LNK2 OK
10/100 BASE T
LNK NET OK
EtherNet/IP
LNK NET OK
Switch
Distributed I/O
1756-EN4TR
1756 I/O Modules
1794-AENT
1794 I/O Modules
Workstation
ControlLogix 5580 Controller
1756 I/O Modules
1769-L27ERM
1769 I/O Modules
5069-AEN2TR
5069 I/O Modules
5069-L340ERM
5069 I/O Modules
1783-ETAP
PanelView™ Terminal
1783-ETAP
Workstation
Stratix® 5400
5094-IB16
FLEX 5000™ I/O
1734-AENTR
1734 I/O Modules
1738-AENTR
1738 I/O Modules
PowerFlex®
Drive
Kinetix® 6500
Servo Drive
Star Topology
1769-L18ERM
1734 I/O Modules
DLR Topology
1756-EN4TR
ControlLogix Controller
Rockwell Automation Publication 1756-UM004A-EN-P - March 2019 9
ControlLogix EtherNet/IP Network Device Overview Chapter 1
Table 1 - EtherNet/IP Communication Modules
Cat. No.
(1)
Description Media Communication
Rate
Integrated
Motion on the
EtherNet/IP
Network Axes,
Max
TCP
Connections
Logix
Connections
1756-EN2F EtherNet/IP bridge, fiber Fiber 10/100 Mbps 8 128 256
1756-EN2T
1756-EN2TK
EtherNet/IP bridge, copper Copper 10/100 Mbps 8 128 256
1756-EN2TR,
1756-EN2TRK
EtherNet/IP bridge, embedded switch, copper Dual copper 10/100 Mbps 8 128 256
1756-EN2TXT ControlLogix-XT™, extended temperature
EtherNet/IP bridge, copper, for extreme
environments
Copper 10/100 Mbps 8 128 256
1756-EN2TRXT ControlLogix-XT, extended temperature
EtherNet/IP bridge, embedded switch, copper
Dual copper 10/100 Mbps 8 128 256
1756-EN2TSC EtherNet/IP secure communication module Copper 10/100 Mbps 128 256
1756-EN3TR,
1756-EN3TRK
EtherNet/IP bridge, embedded switch, copper Dual copper 10/100 Mbps 128 128 256
1756-EN4TR,
1756-EN4TRK
EtherNet/IP bridge, embedded switch, copper Copper 10/100 Mbps
1 Gbps
256 512 1000 I/O
528 Messaging
1756-EN4TRXT ControlLogix-XT, extended temperature
EtherNet/IP bridge, embedded switch, copper
Copper 10/100 Mbps
1 Gbps
256 512 1000 I/O
528 Messaging
1756-ENBT,
1756-ENBTK
EtherNet/IP bridge, copper Copper 10/100 Mbps 64 128
1756-EWEB Ethernet web server module Copper 10/100 Mbps 64 128
(1) A catalog number ending in a K denotes a conformal coating.
10 Rockwell Automation Publication 1756-UM004A-EN-P - March 2019
Chapter 1 ControlLogix EtherNet/IP Network Device Overview
EtherNet/IP Network Specifications
Table 2 - EtherNet/IP Network Specifications
Cat. No. Connections CIP Unconnected
Messages
(backplane +
Ethernet)
Ethernet Node
Count, Max
Packet Rate Capacity (packets/second)
(3)
SNMP Support
(password
required)
TCP CIP I/O HMI and MSG
1756-ENBT 64 128
(1)
64 + 64 5000 900 Yes
1756-EN2F 128 256
(1)
128 + 128 IMPORTANT: Packet rates for
ControlLogix EtherNet/IP
communication modules
depend on series and firmware
revision.
2000 Yes
1756-EN2T 128 256
(1)
128 + 128 2000 Yes
1756-EN2TXT 128 256
(1)
128 + 128 2000 Yes
1756-EN2TR 128 256
(1)
128 + 128 2000 Yes
1756-EN2TRXT 128 256
(1)
128 + 128 2000 Yes
1756-EN2TSC 128 256
(1)
128 + 128 1800 without
encryption
930 with
encryption
Yes
1756-EN3TR 128 256
(1)
128 + 128 2000 Yes
1756-EN4TR 512 1000 I/O
528
(2)
256+256 50,000 without CIP Security
25,000 with integrity
15,000 with integrity and
confidentiality
3,700 without CIP
Security
•2,700 with
integrity
•1,700 with
integrity and
confidentiality
Yes
1756-EN4TRXT 512 1000 I/O
528
(2)
256+256 50,000 without CIP Security
25,000 with integrity
15,000 with integrity and
confidentiality
3,700 without CIP
Security
•2,700 with
integrity
•1,700 with
integrity and
confidentiality
Yes
1756-EWEB 64 128
(1)
128 + 128 900 Yes
(1) CIP connections can be used for all explicit or all implicit applications. For example, a 1756-ENBT module has a total of 128 CIP connections that can be used for any combination of connections.
(2) There are 1000 CIP I/O connections and 528 CIP messaging connections.
(3) Total packet rate capacity = I/O Produced Tag, max + HMI/MSG, max. Packet rates vary depending on packet size. For more detailed specifications, see the EDS file for a specific catalog number.
Rockwell Automation Publication 1756-UM004A-EN-P - March 2019 11
ControlLogix EtherNet/IP Network Device Overview Chapter 1
Electronic Keying
Electronic Keying reduces the possibility that you use the wrong device in a
control system. It compares the device that is defined in your project to the
installed device. If keying fails, a fault occurs. These attributes are compared.
The following Electronic Keying options are available.
Carefully consider the implications of each keying option when selecting one.
For more detailed information on Electronic Keying, see Electronic Keying in
Logix 5000 Control Systems Application Technique, publication LOGIX-
AT001.
Attribute Description
Vendor The device manufacturer.
Device Type The general type of the product, for example, digital I/O module.
Product Code The specific type of the product. The Product Code maps to a catalog number.
Major Revision A number that represents the functional capabilities of a device.
Minor Revision A number that represents behavior changes in the device.
Keying Option Description
Compatible
Module
Lets the installed device accept the key of the device that is defined in the project when the
installed device can emulate the defined device. With Compatible Module, you can typically
replace a device with another device that has the following characteristics:
Same catalog number
Same or higher Major Revision
Minor Revision as follows:
If the Major Revision is the same, the Minor Revision must be the same or higher.
If the Major Revision is higher, the Minor Revision can be any number.
Disable Keying Indicates that the keying attributes are not considered when attempting to communicate with
a device. With Disable Keying, communication can occur with a device other than the type
specified in the project.
ATTENTION: Be cautious when using Disable Keying; if used incorrectly, this option can lead
to personal injury or death, property damage, or economic loss.
We strongly recommend that you do not use Disable Keying.
If you use Disable Keying, you must take full responsibility for understanding whether the
device being used can fulfill the functional requirements of the application.
Exact Match Indicates that all keying attributes must match to establish communication. If any attribute
does not match precisely, communication with the device does not occur.
IMPORTANT
Changing Electronic Keying parameters online interrupts connections to the device
and any devices that are connected through the device. Connections from other
controllers can also be broken.
If an I/O connection to a device is interrupted, the result can be a loss of data.
12 Rockwell Automation Publication 1756-UM004A-EN-P - March 2019
Chapter 1 ControlLogix EtherNet/IP Network Device Overview
Protected Mode
The1756-EN2T, 1756-EN2TP, 1756-EN2TR, and 1756-EN4TR support
explicit protected mode.
(1)
When in this mode, the module does not allow any
configuration changes.
Enabling Explicit Protected Mode
To enable the module in an “explicit protected mode state”, follow these steps.
1. Set the rotary switches
to position ‘900’.
2. Power up the device, and wait for the display to scroll, “Protected Mode
– Change Switch Settings”.
3. Power down the device.
4. Set the switches for normal operation.
5. Power up the device.
6. The device is now in Explicit Protected Mode.
Operation in Explicit Protected Mode
While working in protected mode, the module rejects any CIP™ explicit
messages that would change the configuration of the module. For example, you
cannot change the IP address, speed, or duplex settings when the module had
Explicit Protected Mode enabled.
Disabling Explicit Protected Mode
To disable the “explicit protected mode state”, follow these steps.
1. Set the rotary switches on position ‘000’.
2. Power up the device, and wait for the display to scroll, “Unprotected
Mode – Change Switch Settings”.
3. Power down the device.
4. Set the switches for normal operation.
5. Power up the device.
6. The device is now in Unprotected Mode.
(1) Versions 11.001 and later.
Rockwell Automation Publication 1756-UM004A-EN-P - March 2019 13
ControlLogix EtherNet/IP Network Device Overview Chapter 1
Secure Digital Card
Secure Digital Card
The 1756-EN4TR EtherNet/IP Bridge supports the use of a Secure Digital
(SD) card to store configuration data, for example, the IP address or network
communication rate for each port.
The SD card slot is inside the front panel of the module.
When the card is powered up, the device uses the configuration from the card if
the configuration does not exist in the device. When a blank card is inserted, or
powered up, the configuration is copied from the device to the card that was
inserted.
If the module powers up with a configuration that does not match the
configuration on the already inserted SD card, the configuration on the SD
card is used.
If the module is already powered, and an SD card is inserted, a warning message
is displayed.
To change these results, do one of two things. One option is to do an out of box
reset on the module, if you want to use the configuration on the SD card. A
second option is to modify one of the configuration settings on the device, if
you want to use the configuration on the device.
TIP To see other potential error messages, see Table 4 on page 25
.
SD Card inside front panel.
14 Rockwell Automation Publication 1756-UM004A-EN-P - March 2019
Chapter 1 ControlLogix EtherNet/IP Network Device Overview
Enable/Disable Secure Digital Card
To enable or disable the SD card, use one of the following methods.
Using a CIP Generic Message
To enable, set Attribute 4 (‘SOCKET DISABLED’) to ‘0’ (‘False’) of
Removable Media Socket Object instance (0x3A4, 932 decimal)
To disable, set Attribute 4 (‘SOCKET DISABLED’) to ‘1’ (‘True’)
of Removable Media Socket Object instance (0x3A4, 932 decimal).
Enable/Disable using the Add-on Profile.
The adapter supports the use of a 1784-SD1 (1 GB) and 1784-SD2 (2 GB)
card. You can use third-party SD cards with the controller. You can use SD
cards with as much as 32 GB of memory.
If you use an SD card other than those cards that are available from
Rockwell Automation, unexpected results can occur. For example, you can
experience data corruption or data loss.
SD cards that are not provided by Rockwell Automation can have different
industrial, environmental, and certification ratings as those cards that are
available from Rockwell Automation. These cards can have difficulty with
survival in the same industrial environments as the industrially rated versions
available from Rockwell Automation.
IMPORTANT Rockwell Automation does not test the use of third-party SD cards with the
device.
Rockwell Automation Publication 1756-UM004A-EN-P - March 2019 15
ControlLogix EtherNet/IP Network Device Overview Chapter 1
CIP Security
CIP Security™ is a standard, open-source communication method that helps to
provide a secure data transport across an EtherNet/IP network.
The secure data transport is used between certain connected devices to help
protect the devices from threats posed by unauthorized users with malicious
intent.
CIP Security uses encryption to secure communication on an EtherNet/IP
network, resulting in greater data integrity and confidentiality.
Rockwell Automation uses the following products to implement CIP Security:
FactoryTalk® Policy Manager
•FactoryTalk Linx
Studio 5000® Design Environment
CIP Security-enabled Rockwell Automation® products, for example, the
product described in this publication
(1)
For more information on CIP Security, including which products support CIP
Security, see the CIP Security Application Technique, publication SECURE-
AT001.
(1) In this document, CIP Security is applicable to 1756-EN4TR, 1756-ENRTRK, and 1756-EN4TRXT modules.
16 Rockwell Automation Publication 1756-UM004A-EN-P - March 2019
Chapter 1 ControlLogix EtherNet/IP Network Device Overview
Notes:
Rockwell Automation Publication 1756-UM004A-EN-P - March 2019 17
Chapter 2
Connect to the EtherNet/IP Network
EtherNet/IP™ networks are communication networks that offer a
comprehensive suite of messages and services for many automation
applications.
The following are examples of applications that use EtherNet/IP networks:
•Real-Time Control
Time Synchronization
•Motion
This open network standard uses commonly available Ethernet
communication products to support real-time I/O messaging, information
exchange, and general messaging.
EtherNet/IP networks also support CIP Safety™, which makes the
simultaneous transmission of safety and standard control data and diagnostics
information over a common network possible.
Topic Page
Set the IP Address 18
Set the IP Address with Rotary Switches 18
Other Methods to Set the IP Address 19
Reset the Module IP Address to Factory Default Value 19
18 Rockwell Automation Publication 1756-UM004A-EN-P - March 2019
Chapter 2 Connect to the EtherNet/IP Network
Set the IP Address
The following conditions are required to set the IP address.
Requirements
To set the IP address, have the following:
EtherNet/IP or USB drivers that are installed on the programming
workstation
MAC ID from the device, which is on the label on the side of the device
Recommended IP address for the device
Set the IP Address with
Rotary Switches
This graphic shows the rotary switches on a 1756 EtherNet/IP communication
module. The three rotary switches at the bottom of the module, labeled X, Y,
and Z, can be used for setting the IP address. The rotary switch in the upper
left corner of the module is reserved for future configuration.
At powerup, the module reads the rotary switches to determine if they are set
to a valid number for the last portion of the IP address. Valid numbers range
from 001…254.
32794 M
Rockwell Automation Publication 1756-UM004A-EN-P - March 2019 19
Connect to the EtherNet/IP Network Chapter 2
If the settings are a valid number, these conditions result:
IP address = 192.168.1.xxx (where xxx represents the switch settings)
Subnet mask = 255.255.255.0
Gateway address = 0.0.0.0
The module does not have a host name that is assigned to it, nor does it
use any Domain Name System
We recommend that you set the rotary switches to a valid number before
installing the module.
If the rotary switches are not set to a valid number, the module attempts to use
the BOOTP/DHCP server to set the IP address.
Other Methods to Set the IP
Address
The 1756-EN4TR module supports the following additional methods to
change the IP address:
BOOTP/DHCP utility
RSLinx® Classic software
Using Secure Digital Card
For more information on how to use these methods, see EtherNet/IP
Network Configuration Manual, publication ENET-UM006
.
Reset the Module IP Address
to Factory Default Value
You can reset the configuration of the module to its factory default value with
the following methods:
If the module has rotary switches, set the switches to 888 and cycle
power.
TIP Some modules now provide a gateway address of 192.168.1.1 when the
network address is set with rotary switches.
IMPORTANT For more information on how to use the BOOTP/DHCP server to set the IP
address, see EtherNet/IP Network Configuration Manual,
publication ENET-UM006
20 Rockwell Automation Publication 1756-UM004A-EN-P - March 2019
Chapter 2 Connect to the EtherNet/IP Network
Notes:
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32