  • Hello! I am an AI chatbot trained to assist you with the meitav-tec PS-2500-3S-FC-Super Product information. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
Date:
Title:
File name: PS2500-3S-FC-SUPER.VSD
Print name:Drawn: M.Ruchansky
Checked: O.Volovitch
Approved: E.Roy
PS2500-3S-FC-SUPER
15.03.07
PS-2500
X2 X1 16 15 14 13 12 11
0
F1
0
PR
0
F3
F4
0
F5
0
F6
Indoor Fan
(230Vac,3A)
0 Y 1 2 3 8 7 0 B A1
2
3
8
7
ETN/X500 ; FMH/X500 ; IRP/X500
Thermostat (Option)
~
N
GND
0
T3
0
T2
0
T1
P1
P2
P3
+12V
-12V
IR
230Vac
Change Over Sensor
Return Air Sensor
(See the operating
manual - #4)
Not in use
CONTROLLER
POWER
SUPPLY
+- Fuse
8A
JP5
JP4
0
F2
Not in use
Not in use
Occupancy
Sensor
12Vdc
RS485
On/Off Mode Fan
BACNET (Alerton) MSTP
Protocol
RS485
BACNET (Alerton) MSTP
Protocol
Indoor Coil Sensor
ID2014
F5 – Short – Fan Only mode available
(Selectable through thermostat)
F5 – Open – Fan Only mode not available
Indoor Coil Sensor (T3) Indoor Fan in heat mode
Auto Fan = ON :
With Indoor Coil Sensor
T3 > 32ºC Fan ON
T3 < 28ºC Fan OFF
Without Indoor Coil Sensor
The Indoor Fan will operate when there is a demand for
heating (with 30 seconds time delay)
Heat – Connector 14
For Valve only ! Do not connect an electrical heater !
Jumpers – JP4 & JP5
JP4 – SHORT (4-Pipe System)
Auto change over active
2 separate outputs for Cool and Heat (14 & 15)
T2 – for monitoring only
JP4 – OPEN (2-Pipe System)
Auto change over not active
1 output for Cool and Heat (15)
T2 – Logic selection
JP5 - SHORT
In Cool mode – Auto Fan
In Heat mode – Auto Fan
JP5 - OPEN
In Cool mode – Fan ON
In Heat mode – Fan ON
Occupancy Sensor
When the IR (N.C.) input is open
for 10 minutes, all outputs turn Off.
Short the (-12V) and (IR)
connectors, only when an
occupancy sensor is not connected
Change Over Sensor (T2) in 2-Pipe system:
With Change Over Sensor
T2 < 20ºC Cool
T2 > 30ºC Heat
Without Change Over Sensor
Manually select the mode using the wall panel or computer.
0
F4 – Fault input (N.C.)
When open – all outputs OFF (no delay)
F6 – Fault 2 input (N.C.)
Only for indication through the protocol
Pump Output –
230Vac , 1A
Will be active only
when the Cool output
is also active
Not in use
(Temperature through
the protocol)
JP1
JP1
End of Network jumper
– Jumper Short
(Resistance 120 )
JP1 JP1
Open Short
Device Instance
Number ( DIN)
F1,0 F2,0
Unshort Unshort
Short Unshort
Unshort Short
F3,0 DIN
EEPROM
Unshort DIN=
MAC+1200
Unshort
Short Short Unshort DIN=
MAC+800
Unshort
Unshort Unshort
Short Unshort
Unshort Short
DIN=
MAC+600
Short DIN=
MAC+400
Short DIN=
MAC+200
Short Short Short DIN=MAC
Short
Device Instance
Number ( DIN)
DIN=
MAC+1000
MAC Phisical address of Device
(DIP SWITCH)
0,PR -Open thermostat
work in ºC.(Default from
factory)
0,PR -Close thermostat
work in ºF.
meitav-tec
Tel: +972-3-9636462
Fax: +972-3-9626620
e-mail: support@meitavtec.com
Important !
Disconnect power to the main board
before making any changes to DIP
switches/Jumpers, wiring the unit
and/or connecting the wall panel.
Shielded cable - Connect the
shield to the “8” terminal of
the main board.
5x0.5 12VDC
/