meitav-tec PS-2500-P-3S-FC-Super Product information

Category
Thermostats
Type
Product information
Date:
Title:
File name: PS2500-P-3S-FC-SUPER.VSD
Print name:Drawn: M.Ruchansky
Checked: O.Volovitch
Approved: E.Roy
PS2500-P-3S-FC-SUPER
04.02.08
PS2500-PM2-3S
Pump 13 12 11
F6
0 Y 1 2 3 8 7 0 B A1
2
3
8
7
Wall Panel (Option)
ETN/X500 ; FMH/X500 ; IRP/X500
~
N
GND
0
T3
0
T2
0
T1
P1
P2
P3
+12V
-12V
IR
230Vac
Change Over Sensor /
Discharge sensor
Return Air Sensor
Not in use
CONTROLLER
POWER
SUPPLY
+-
Fuse
8A
220Vac
JP5
JP4
Not in use
Not in use
Occupancy
Sensor
12Vdc
RS485
On/Off Mode Fan
BACnet MSTP Protocol
RS485
BACnet MSTP Protocol
Indoor Coil Sensor
ID2001
F5 – Short – Fan Only mode available
(Selectable through thermostat)
F5 – Open – Fan Only mode not available
Indoor Coil Sensor (T3) Indoor
Fan in heat mode
With Indoor Coil Sensor
T3 > 32ºC Fan ON
T3 < 28ºC Fan OFF
Without Indoor Coil Sensor
The Indoor Fan will operate when
there is a demand for heating (with
30 seconds time delay)
Jumpers – JP4 & JP5
JP4 – SHORT (4-Pipe System)
Auto change over active
2 separate outputs for Cool and Heat
T2 – for monitoring only
JP4 – OPEN (2-Pipe System)
Auto change over not active
1 output for Cool and Heat
T2 – Logic selection
JP5 - SHORT
In Cool mode – Auto Fan
In Heat mode Always Auto Fan
JP5 - OPEN
In Cool mode – Fan ON
In Heat mode Always Auto Fan
Occupancy Sensor
When the IR (N.C.)
input is open for 10
minutes, all outputs
turn Off.
Short the (-12V) and
(IR) connectors, only
when an occupancy
sensor is not
connected
Change Over Sensor (T2) in 2-
Pipe system:
With Change Over Sensor
T2 < 20ºC Cool
T2 > 30ºC Heat
20ºC < T2 > 30ºC = Fan Only
Without Change Over Sensor
Manually select the mode using
the wall panel or computer.
F4 – Fault 1 input (N.C.)
When open – all outputs OFF (no delay)
Not in use
JP1
oT Ambient reading from panel or from Main Board
FMH-X500 – JP2
“A” position – read temperature from main board.
“B” position – read temperature from panel.
ETN-X500 – JP2
OPEN – read temperature from main board.
SHORT – read temperature from panel.
JP1
End of Network jumper
– Jumper Short
(Resistance 120 )
JP1 JP1
Open Short
B
A
12387
0
F5
0
F4
0
F3
0
F2
0
F1
0
PR
0
FAN (3A)
+-
Device Instance Number ( DIN)
F1,0 F2,0
Unshort Unshort
Short Unshort
Unshort Short
F3,0 DIN
EEPROM
Unshort DIN=
MAC+1200
Unshort
Short Short Unshort DIN=
MAC+800
Unshort
Unshort Unshort
Short Unshort
Unshort Short
DIN=
MAC+600
Short DIN=
MAC+400
Short DIN=
MAC+200
Short Short Short DIN=MAC
Short
Device Instance
Number ( DIN)
DIN=
MAC+1000
MAC Phisical address of Device
(DIPSWITCH)
(Temperature through
the protocol)
Important !
Disconnect power to the main board
before making any changes to DIP
switches/Jumpers, wiring the unit
and/or connecting the wall panel.
Shielded cable - Connect the
shield to the “8” terminal of
the main board.
5x0.5 12VDC
meitav-tec
Tel: +972-3-9626462
Fax: +972-3-9626620
e-mail: support@meitavtec.com
Software: 2001V7
Checksum: EB7E
Twisted pair cable (Shielded,22AWG )
Connect the shield to ground at one
end of communication line
W
Y
0
0
OUT 0-10V
(Cool)
OUT 0-10V
(Heat)
Pump Output –
230Vac , 1A
Will be active only
when the Cool output
is also active
Not in use
No.Revision Date
1 Original 26.07.06
  • Page 1 1

meitav-tec PS-2500-P-3S-FC-Super Product information

Category
Thermostats
Type
Product information

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI