meitav-tec PS-1800-FC-SUPER Product information

  • I'm a chat assistant and have reviewed the PS1800-FC-SUPER datasheet. This document provides instructions for wiring and configuring the controller, including details on sensor inputs, jumper settings for 2-pipe and 4-pipe systems, and fault indication. I can help you with questions regarding the device's wiring and its functionalities, also I'm ready to answer your questions based on this datasheet.
  • How do I manually select the mode without a changeover sensor?
    What happens when the IR input is open for 10 minutes?
    What is the function of the F4 fault input?
    what are the operating modes when JP5 is shorted?
Date:
Title:Print name:
17.01.08
PS2500
13 12 11
0
F1
0
PR
0
F3
F4
0
F5
0
F6
0 Y 1 2 3 8 7 0 B A
~
N
0
T3
0
T2
0
T1
P1
P2
P3
+12V
-12V
IR
Main Input
230Vac
Changeover Sensor
Return Air Sensor
Not in use
CONTROLLER
POWER
SUPPLY
+-
Fuse
8A
JP5
JP4
0
F2
Occupancy
Sensor ( F8 )
12Vdc
RS485
MAXINET
Protocol
RS485
MAXINET
Protocol
Indoor Sensor
0
Not in use
JP1
Tel: +972 (3) 962 6462
Fax: +972 (3) 962 6620
e-mail: support@meitavtec.com
meitav-tec
PS1800-FC-SUPER
File name: PS1800-FC-SUPER.VSD
Drawn: A.Star
Checked: O.Volovich
Approved: E.Roy
1
2
3
8
7
ETN/X500 or FMH/X500
Thermostat / IR Panel (Option)
On/Off Mode Fan
~
F
16 15 14X2 X1N.C1N.O1
Indoor Fan
(230Vac,3A)
Not in use
Not in use
Indoor Coil Sensor (T3) :
( In Heat mode )
With Indoor Coil Sensor !
T3 > 36ºC → Fan ON
T3 < 32ºC → Fan OFF
Without Indoor Coil Sensor
The Indoor Fan will operate when there is a demand for
heating (with 30 seconds time delay)
Jumpers – JP4 & JP5
JP4 – SHORT (4-Pipe System)
Auto change over mode active
2 separate outputs for Cool and Heat (14 & 15)
T2 – for monitoring only
JP4 – OPEN (2-Pipe System)
Auto change over mode not active
1 output for Cool and Heat (15)
T2 – Logic selection (see above)
JP5 - SHORT
In Cool mode – Auto Fan
In Heat mode – Auto Fan
JP5 - OPEN
In Cool mode – Fan ON
In Heat mode – Auto Fan
Occupancy Sensor
When the IR (N.C.) input is open
for 10 minutes, all outputs turn Off.
Short the (-12V) and (IR)
connectors, only when an
occupancy sensor is not connected
Change Over Sensor (T2) in 2-Pipe system:
With Change Over Sensor
T2 < 20ºC → Cool
T2 > 30ºC → Heat
Without Change Over Sensor
Manually select the mode using the wall panel (IRP-X500)
or computer.
JP1
End of Network jumper
– Jumper Short
(Resistance 120 Ω)
JP1 JP1
Open Short
F5 – Short – Fan Only mode available
(Selectable through thermostat)
F5 – Open – Fan Only mode not available
F4 – Fault 4 input (N.C.)
When open – all outputs OFF (no delay)
F6 – Fault 6 input (N.C.)
Only for indication through the protocol
Important !
Disconnect power to the main board
before making any changes to DIP
switches/Jumpers, wiring the unit
and/or connecting the wall panel.
Shielded cable - Connect the
shield to the “8” terminal of
the main board.
5x0.5 12VDC
17.01.0801 Original
Shielded,twisted pair cable 120Ω @ 1MHz
Checksum: 643C
Software name:08400506
F1 – Fault 1 input (N.C.)
Only for indication through the protocol
F2 – Fault 2 input (N.C.)
Only for indication through the protocol
F3 – Fault 3 input (N.C.)
Only for indication through the protocol
/