Functional description of the unit
Typ CAU CAIRfricostar CAU Controller
4FG_DC-2013-0109-GB_R2-2018-08 • Subject to modufications
1.2 System and controls scheme
Control and regulation
system – Consists of a separate switch box for mounting on units with all necessary compo-
nents for control functions, wired according to VDE specifications.
– Electrical connection (via plug or screw terminals) between switch box and unit
using factory prepared lines.
– Power supply for controlling the mixing valve and re-heater pump (including controls).
– Possible output for pool water pump.
– The switch box is supplied loose, including fixing material for mounting on the unit.
– All electronic control and regulation components can be easily replaced.
The switch box is supplied
with the following main
components:
– Main isolating switch for all pole downtime of the electrical unit.
– Group fuses for fan and compressor; safety fuse for pump re-heater circuit 230V,
control fuse and control voltage supply unit 24V (safety extra-low voltage or SELV);
control of supply-air fan using motor full protection device via PTC temperature
sensor and electronic motor-protection trigger device.
– Control compressor motor with thermal motor protection and interlock for safety
chain and control card, control of icing protection, ND, HD.
– Electronic control card for compressor regulation with minimum run and standstill
time as clock protection, service reset button, status messages for timer control and
light diode for faults of the refrigeration circuit.
– Hydrostatic humidity control as a remote control for mounting in the swimming pool,
with status, malfunction indicator light and operation switch; operation with protec-
tive extra-low voltage; setpoint setting 30-90% r.h.; white colour; surface mounting,
dimensions: W/H/D 145/80/30 (mm); supplied separately.
– Electronic three-point PI-controller for extract-air temperature control with setpoint
setting on the switch box including installed NTC extract-air temperature sensor.
– Output 230V for modulating 3-way valve motor in re-heater circuit.
– If necessary FläktGroup pool water temperature control for controlling pool water
pump consisting of an integrated immersion thermostat, interlocking with compres-
sor operation and output for pool water pump 230V (only control output max. 2A)
and time control for registration of actual values (only in combination with pool water
condenser).
– Output for collective error message signal (floating change-over contact).
– Control possibility of an extract air fan by others, 2-speed, 230 V/max. 150 W
DI
AI
DO
AO
M
M
P
P
MM
M
MM
MM
pp
ppp
M1