OPERATION MANUAL
Table of Contents
CAIRfricostar®
2FläktGroup DC-2009-0019-GB R10/09-2020 • Specifications are subject to alteration without notice
1 Unit Type Code .................................................................................. 4
2 Safety and User Instructions ........................................................... 5
2.1 Availability of the operation manual ................................................................ 5
2.2 Scope of the operation manual ....................................................................... 5
2.3 Symbols used .................................................................................................. 5
2.4 Identification of safety instructions .................................................................. 8
2.5 Safety-conscious work procedures ................................................................. 9
2.6 Proper use ....................................................................................................... 9
2.7 Safety devices ............................................................................................... 10
2.8 Modifications and changes ............................................................................ 10
2.9 Spare parts .................................................................................................... 10
2.10 Disposal ........................................................................................................ 10
2.11 Selection and qualification of personnel ........................................................ 10
3 Technical Description ..................................................................... 11
3.1 Performance scope ....................................................................................... 11
3.2 Modular unit configuration and operation of FläktGroup CAIRfricostar ......... 11
3.3 Unit configuration and operation of CAIRfricostar Micro compact units ........ 14
3.4 Technical specifications ................................................................................ 16
4 Shipping and Storage ..................................................................... 19
4.1 Delivery ......................................................................................................... 19
4.2 Transport ....................................................................................................... 19
4.3 Storage .......................................................................................................... 22
5 Mounting .......................................................................................... 23
5.1 Unit placement .............................................................................................. 23
5.2 Assembling the unit ....................................................................................... 26
6 Installation ....................................................................................... 37
6.1 Requirements ................................................................................................ 37
6.2 Installing air-conveying components ............................................................. 37
6.3 Installing air-handling components with coil connections .............................. 37
6.4 Installing accessories .................................................................................... 43
7 Electrical Connection ..................................................................... 44
7.1 Requirements ................................................................................................ 44
7.2 Connecting unit ............................................................................................. 45
8 Commissioning ............................................................................... 51
8.1 Requirements ................................................................................................ 51
8.2 General considerations ................................................................................. 52
8.3 Fan assembly and drives .............................................................................. 52
8.4 Direct-driven fan assembly ............................................................................ 53
8.5 Filter assembly .............................................................................................. 53
8.6 Heater assembly ........................................................................................... 54
8.7 Cooler assembly ........................................................................................... 55
8.8 Evaporator / condenser ................................................................................. 55
8.9 Heat pipe ....................................................................................................... 56
8.10 Liquid-coupled energy recovery coil .............................................................. 56
8.11 Plate-type heat exchanger ............................................................................ 56
8.12 Damper blades and shut-off dampers ........................................................... 56
Table of Contents
CAIRfricostar®
FläktGroup DC-2009-0019-GB R10/09-2020 • Specifications are subject to alteration without notice 3
9 Maintenance ................................................................................... 57
9.1 Routine cleaning and maintenance ............................................................... 58
9.2 Maintenance frequency (checklist) ................................................................ 59
9.3 General considerations .................................................................................. 62
9.4 Fan assembly and drives ............................................................................... 62
9.5 Filter assembly ............................................................................................... 66
9.6 Heater assembly ............................................................................................ 67
9.7 Cooler assembly ............................................................................................ 67
9.8 Evaporator / condenser ................................................................................. 68
9.9 Heat pipe ....................................................................................................... 68
9.10 Liquid-coupled energy recovery coil .............................................................. 69
9.11 Plate-type heat exchanger ............................................................................. 69
9.12 Damper blades and shut-off dampers ............................................................ 69
9.13 Sound attenuator ........................................................................................... 69
10 Disassembly and Disposal ............................................................. 70
10.1 Dismantling .................................................................................................... 70
10.2 Disposal ......................................................................................................... 70
11 Troubleshooting .............................................................................. 71
12 Appendix .......................................................................................... 72
12.1 Maintenance log book for your CAIRfricostar –
Dehumidifier Units for indoor pools 72
– Original operation manual –
Copyright note
Disclosing, copying, distributing or taking any action in reliance on the contents of this document is strictly
prohibited without express prior consent. Violations entail liability for any damages or other liability arising.
All rights in relation to patents, utility patents or design patents are reserved.
Unit Type Code
CAIRfricostar®
4FläktGroup DC-2009-0019-GB R10/09-2020 • Specifications are subject to alteration without notice
1 Unit Type Code
A096096BBKG
Unit part 2 *
Example: CAIRfricostar X1FSIHUEZ096096BBKGCAM083SUKS
Prefix General Unit part 1 Type identification
Product family
Product group
Series
Casing configuration class
Thermal separation of casing
Type of application
Installation site
Air flow direction
Arrangement
Casing type
Air flow function
Unit width
Unit height
Material of internal skin
Material of external skin
Material of components
Material of profiles
Type identification
Nominal air volume x 100
Type of application
Arrangement
Material quality of components
Designation of controls
CAIR
fricostar (dehumidification of swimming pools)
XSX Unit
1Standard without accessories
2Standard with accessories
3Special design
TComplete
FFixed
PHigh-Performance swimming pool
SStandard swimming pool
VHigh-Performance swimming pool as of VDI 6022
IIndoor installation
HHorizontal
NSide-by-side
UDouble-deck
ESingle unit
ZSupply air
AReturn air
Unit width (internal size in cm)
Unit height (internal size in cm)
BRAL 9002 coated
4Stainless steel V4A (steel type 1.4571)
BRAL 9002 coated
KCoated with enhanced corrosion protection
HCoated for brine pools < 3 %
PCoated for brine pools > 3 %
BRAL 9002 coated
CAU
CMU
CAM
CWR
CAT
CWT
SStandard swimming pool
PHigh-Performance swimming pool
VHigh-Performance swimming pool as of VDI 6022
UDouble-deck
NSide-by-side
KCoated with enhanced corrosion protection
HCoated for brine pools < 3 %
PCoated for brine pools > 3 %
SStandard
GGKA
* Unit part 2 – additional with arrangement types side-by-side, double-deck or straight-through
Safety and User Instructions
CAIRfricostar®
FläktGroup DC-2009-0019-GB R10/09-2020 • Specifications are subject to alteration without notice 5
2 Safety and User Instructions
The FläktGroup CAIRfricostar units are constructed using the state-of-the-art technol-
ogy and according to recognized safety regulations.
Use the unit when it is in a technically sound condition for the intended purpose observ-
ing current operation manual, taking safety aspects and potential hazards into account!
Otherwise failure to follow these instructions may result in death or injury to the user,
third persons or damage to the FläktGroup unit, connected units or other equipment!
Have all faults repaired by an authorized specialist without delay!
Consider the safety instructions provided by the manufacturers of individual compo-
nents!
2.1 Availability of the operation manual
This operation manual contains important instructions regarding safe and correct oper-
ation of the FläktGroup unit.
This operation manual applies to installation companies, operators, building techni-
cians, technical personnel or instructed persons as well as electricians.
This operation manual must be available at the location of the unit at all times. When
working on the equipment, observe all instructions and precautions in the current oper-
ation manual, in particular the chapter on safety.
2.2 Scope of the operation manual
This operation manual provides information about the following:
Shipping and Storage
– Mounting
Installation and Electrical Connection
Commissioning and Maintenance
Disassembly and Disposal
2.3 Symbols used
The following symbols are used to highlight particular text sections in this operation
manual:
This symbol is used to indicate normal lists.
This symbol indicates handling instructions.
9This symbol indicates the result of an action.
NOTICE!
This symbol denotes additional instructions on using the FläktGroup unit.
RECYCLING!
This symbol is used to highlight instructions for the recycling of packaging material
and disused unit components, which must be separated depending on the material
type.
PROPER BOOTS REQUIRED!
This symbol points out that you must wear proper protective boots.
WEAR GLOVES!
This symbol points out that you must wear proper gloves.
Safety and User Instructions
CAIRfricostar®
6FläktGroup DC-2009-0019-GB R10/09-2020 • Specifications are subject to alteration without notice
Danger symbols are specified in section „Identification of safety instructions“ on
page 8.
2.3.1 Special warning and danger symbols
The following warning and instruction signs can be secured on the unit:
To connect - counter hold with a pipe wrench.
Attention: fire risk. Dust-laden filters are inflammable.
Before opening, use the main isolator to disconnect power.
Risk of injury. Wait until complete stop before opening.
Type sheet and assembly instructions attached to unit inside. Remove these docu-
ments before the unit commissioning.
Do not start up the fan against closed dampers.
Potential equalisation. To equalize potentials the unit must be connected to an exter-
nal protective conductor at the designated points on the base frame.
Safety and User Instructions
CAIRfricostar®
FläktGroup DC-2009-0019-GB R10/09-2020 • Specifications are subject to alteration without notice 7
2.3.2 Function signs
Air flow is generally indicated for
fan or compressor Air cooler air/refrigerant
Sound attenuator in unit
Air heater/cooler with heat
recovery function
Air/water ECOFLOW
General air filter
indicating air flow direction
Air heater/cooler with heat recov-
ery function Air/ECOSTAT
Opposed-blade dampers
Air heater/cooler with heat recov-
ery function air/air ECOPLAT
Air heater air/water General controller
Electric air heater Droplet separator
Air cooler air/water
Safety and User Instructions
CAIRfricostar®
8FläktGroup DC-2009-0019-GB R10/09-2020 • Specifications are subject to alteration without notice
2.4 Identification of safety instructions
To designate the safety instructions the following symbols and notices are provided in
appropriate places throughout this document:
HAZARDOUS VOLTAGE!
This symbol indicates a risk of electric shock when working on the equipment.
PERSONAL INJURY!
This section specifies procedures and precautions for the prevention of personal
injury.
WARNING: RISK OF ROTATING COMPONENTS!
This section specifies procedures and precautions for preventing personal injury
as a result of rotating unit parts.
DANGER OF OVERHEAD LOADS!
This section specifies procedures and precautions for the prevention of personal
injury and damage to units through falling components.
DANGER OF HOT SURFACES!
This section specifies procedures and precautions for preventing personal injury
due to hot surfaces.
DANGER OF SCALDING!
This section specifies procedures and precautions for the prevention of personal
injury resulting from scalding by steam.
DANGER OF INFLAMMABLE MATERIALS!
This section specifies procedures and precautions for the prevention of personal
injury resulting from fire risk.
DANGER – SHARP CUTTING EDGES!
This section specifies procedures and precautions for preventing personal injury
due to cutting on thin metal fins.
ENVIRONMENTAL DAMAGE!
This section specifies procedures and precautions for preventing environmental
damage with reference to the valid national regulations on environmental protec-
tion.
EQUIPMENT DAMAGE!
This section specifies procedures and precautions regarding the prevention of
equipment damage.
Safety and User Instructions
CAIRfricostar®
FläktGroup DC-2009-0019-GB R10/09-2020 • Specifications are subject to alteration without notice 9
2.5 Safety-conscious work procedures
Observe the following instructions when carrying out installation, adjustment or repair
jobs:
When working within range of mains voltage:
For all kinds of work:
Jobs on the unit can only be carried out if
all poles for the power supply are disconnected
the unit is secured to prevent inadvertent energising (also refer to "Electrical haz-
ard")
all moving components - in particular - fan impeller, motor, rotary heat exchanger,
control and shut-off dampers have come to a standstill: wait at least 5 minutes after
deactivating the unit
the heat exchangers have cooled down to reach ambient temperature
Upon completion of jobs on the unit ensure that
all protective devices are operating properly – for example, the fan safety devices
(door protection grille, contact guard) are locked
no persons are present in danger areas.
2.6 Proper use
The FläktGroup CAIRfricostar units are only designed for dehumidification, ventilat-
ing, heating and filtration of air and are generally used in privately-owned and public
swimming pools.
Proper use also includes observance of the operation manual and the inspection and
maintenance conditions stipulated by FläktGroup.
Improper use Any use other than that described above is considered improper. The manufacturer/
supplier is not liable for any damages arising from improper use. The user alone bears
the risk.
HAZARDOUS VOLTAGE!
Disconnect all electric power of the unit and ensure the power cannot be inadvert-
ently switched on, earth, short-circuit and block off all neighboring live parts. Non-
compliance can lead to death or serious injury.
PERSONAL INJURY!
An operating unit poses a risk of injury:
Danger of impacts by opening doors arranged on the discharge side
Danger of crushing resulting from negative pressure applied to doors on the
suction side
Danger resulting from rotating parts such as fans etc.
EQUIPMENT DAMAGE!
If dampers are abruptly shut during unit operation, the unit can be damaged
beyond repair as a result of negative pressure or overpressure.
DANGER – SHARP CUTTING EDGES!
No matter what kind of jobs are performed on the unit, there is always a risk of
cuts by thin sheet metal and heat exchanger fins. In particular, this aspect
applies when carrying out maintenance and cleaning work on the surfaces of
heating and cooling coils.
Safety and User Instructions
CAIRfricostar®
10 FläktGroup DC-2009-0019-GB R10/09-2020 • Specifications are subject to alteration without notice
Only indoor installation of units is allowed.
2.7 Safety devices
Depending on the unit design
panels and doors are secured by locks/lockable handles of the switch box
fan sections are secured by door protection grilles
V-belt drives are secured by belt guards
2.8 Modifications and changes
You are not allowed to change, add to or modify the FläktGroup unit in any way. Tam-
pering with the FläktGroup unit, its misapplication or modifications will invalidate the
CE conformity and void warranty.
2.9 Spare parts
Only original FläktGroup spare parts are allowed, since FläktGroup is not liable if third-
party spare parts are used.
2.10 Disposal
Dispose of main and operating supply materials as well as other components and fil-
ters according to their material type in a safe and environmentally-friendly manner, also
refer to chapter „Disassembly and Disposal“ on page 70.
2.11 Selection and qualification of personnel
Ensure that every person working on the FläktGroup unit has read and understood
entire operation manual.
All jobs must only be carried out by qualified licensed staff or other individuals with
proper professional training and experience in the following areas:
Occupational health and safety regulations
Accident prevention regulations
Directives and recognized codes of practice
All skilled staff must be able to assess the entrusted work and must be able to recog-
nize and avoid all associated dangers.
PERSONAL INJURY AND EQUIPMENT DAMAGE!
It is not allowed to operate the unit:
In areas subject to explosion risk,
in environment with conductive dust,
in environment with strong electromagnetic fields,
in environment with aggressive atmosphere that may attack plastics or cause
corrosion (especially in atmospheres where zinc is particularly susceptible to
corrosion) or under conditions violating the requirements of the VDI 2089.
Technical Description
CAIRfricostar®
FläktGroup DC-2009-0019-GB R10/09-2020 • Specifications are subject to alteration without notice 11
3 Technical Description
3.1 Performance scope
FläktGroup CAIRfricostar units are used for energy-efficient air dehumidification in
swimming pools and humid rooms. Due to their modular design, units can be config-
ured individually to meet particular air-handling requirements and specifications. The
transported air can be filtered, heated, cooled and dehumidified, depending on the
application for each case. The aim is to meet the customer specifications concerning
required air volume and conditions.
FläktGroup CAIRfricostar units are used at a central point for comfort air conditioning
on commercial and industrial premises for the transportation and treatment of “normal”
air (according to VDI 2089).
A range of unit components is available for energy-saving purposes: plate-type heat
exchangers, heat pipes, liquid-coupled heat exchangers and heat pumps with a heat
recuperation function.
Units are performed in different sizes and have various capacities. Depending on the
application for each case, FläktGroup CAIRfricostar units are designed for horizontal
air flow and are arranged as double-deck and side-by-side models. Units are only
designed for indoor installation. Units for outdoor installation need have special design.
Thanks to their modular design FläktGroup CAIRfricostar units ship as complete
assemblies or sub-assemblies that can pass through the available on-site openings in
the course of installation. FläktGroup CAIRfricostar units are also suitable for the mod-
ernisation and retrofitting of existing buildings due to the number of available unit sizes
and a unit ordering option providing for delivery in small shipment units.
3.2 Modular unit configuration and operation of FläktGroup CAIRfricostar
Thanks to the modular design of the units and various applications for each case, a
customer can select a wide range of unit configurations.Refer to the following exam-
ples demonstrating the basic unit design and its operating principles.
3.2.1 CAU units
The FläktGroup CAIRfricostar CAU is designed for private swimming pools and are
available in 4 sizes. The unit's function is to dehumidify and heat air in swimming pools
in recirculating-air mode. The unit is fitted with a fully electronic control system that
automatically regulates system functions.
Fig. 3-1: FläktGroup CAIRfricostar CAU
In recirculating-air mode without dehumidification the air is recirculated in the swim-
ming pool. The multifunction humidistat that is installed in the swimming pool switches
the unit into dehumidification mode as soon as the humidity setpoint has been
exceeded. At this point the fan is operated at nominal air-flow volume and the refriger-
ation system is activated. Dehumidification is active until the humidity setpoint is
reached. Subsequently the fan is switched back and the circuit compressor is stopped.
Using an optional pool water condenser a certain amount of excess energy produced
by the refrigeration cycle can be fed back into swimming pool water.
Technical Description
CAIRfricostar®
12 FläktGroup DC-2009-0019-GB R10/09-2020 • Specifications are subject to alteration without notice
3.2.2 CMU units
The FläktGroup CAIRfricostar CMU is designed for private and small public swimming
pools. The series is available in 6 sizes. The unit's function is to dehumidify and heat
air in swimming pools in mixed air mode. The unit is delivered with a DDC controls
which regulates all functions of the system on a fully automated basis.
Fig. 3-2: FläktGroup CAIRfricostar CMU
When in stand-by mode without dehumidification the air is recirculated in the swimming
pool. When the humidity setpoint has been exceeded the unit switches into dehumidi-
fication mode. At this point the supply-air fan is operated at nominal air flow and the
extract-air fan maintains the proper air movement. The refrigeration unit is activated in
order to start dehumidification. Using the bypass damper a certain part of return air is
mixed without further treatment with dehumidified air that has passed through the
refrigeration cycle. The dehumidification stage continues until the actual humidity value
lies below that of the humidity setpoint. Then the refrigeration unit is deactivated.
When in active hours swimming pool mode the fresh and exhaust air dampers are
opened, the bypass damper is closed. To start dehumidification the refrigeration unit is
activated.
Using an optional pool water condenser a certain amount of excess energy produced
by the refrigeration cycle can be fed back into swimming pool water.
3.2.3 CAM units
The FläktGroup CAIRfricostar CAM is designed for various kinds of private and public
swimming pools. This unit series can deliver air flow rate from 750 up to 45.000 m³/h.
The unit's function is to dehumidify and heat air in swimming pools in mixed air mode.
Besides a refrigeration unit (heat pump) this unit type is additionally equipped with an
efficient heat recovery system. The unit is delivered with a DDC controls which regu-
lates all functions of the system on a fully automated basis.
Fig. 3-3: FläktGroup CAIRfricostar CAM
Technical Description
CAIRfricostar®
FläktGroup DC-2009-0019-GB R10/09-2020 • Specifications are subject to alteration without notice 13
When in stand-by mode without dehumidification the air is recirculated in the swimming
pool. When the humidity setpoint has been exceeded the unit switches into dehumidi-
fication mode. At this point the supply-air fan is operated at nominal air flow and the
extract-air fan maintains the proper air movement. The refrigeration unit is activated in
order to start dehumidification. Using the bypass damper a part of return air is mixed
with air dehumidified through the refrigeration unit. The dehumidification stage contin-
ues until the actual humidity value lies below that of the humidity setpoint. Then the
refrigeration unit is deactivated.
When in active hours swimming pool mode the fresh and exhaust air dampers are
opened, the bypass damper is closed. Then the refrigeration unit is activated. In the
event of overheated swimming pool the refrigeration unit is deactivated and the bypass
dampers are opened to divert the heat recovery system.
Using an optional pool water condenser a certain amount of excess energy produced
by the refrigeration cycle can be fed back into swimming pool water.
3.2.4 CWR units
The FläktGroup CAIRfricostar CWR is designed for various kinds of private and public
swimming pools. This unit series can deliver air flow rate from 750 up to 45.000 m³/h.
The unit's function is to dehumidify and heat air in swimming pools in mixed air mode.
These units are equipped with an efficient heat recovery facility. The unit is delivered
with a DDC controls which regulates all functions of the system on a fully automated
basis.
Fig. 3-4: FläktGroup CAIRfricostar CWR
When in stand-by mode without dehumidification the air is recirculated in the swimming
pool. When the humidity setpoint has been exceeded the unit switches into dehumidi-
fication mode. For this purpose outside air is supplied continuously. The dehumidifica-
tion stage continues until the actual humidity value lies below that of the humidity
setpoint. After that continuously operating outside air/extract air dampers are closed.
In the pool mode outside air and extract air dampers are opened to ensure a pre-set
minimum rate for outside air for hygienic reasons, the opening of the mixed-air damper
is reduced accordingly. Depending on the swimming pool humidity the outside air rate
is regulated automatically.
In the event of overheated swimming pool the bypass dampers are opened to divert
the heat recovery facility.
Technical Description
CAIRfricostar®
14 FläktGroup DC-2009-0019-GB R10/09-2020 • Specifications are subject to alteration without notice
3.3 Unit configuration and operation of CAIRfricostar Micro compact units
Thanks to the modular design of the units and various applications for each case, a
customer can select a wide range of unit configurations.
Refer to the following examples demonstrating the basic unit design and its operating
principles.
3.3.1 CAT units
The FläktGroup CAIRfricostar CAT is a dehumidifier with compact configuration
designed for private and hotel swimming pools as well as therapeutic baths. This unit
series can deliver air flow rate from 750 up to 6,500 m³/h. The series is available in 5
model sizes. The unit operates to dehumidify and heat air in swimming pools in mixed
air mode and is equipped with a high-efficiency heat recovery facility and a compressor
unit to enable dehumidification. The unit is equipped with an integrated DDC control
system which regulates all functions on a fully automated basis.
Fig. 3-5: FläktGroup CAIRfricostar CAT
When in stand-by mode without dehumidification the air is recirculated in the swimming
pool. When the humidity setpoint has been exceeded the unit switches into dehumidi-
fication mode. For this purpose the refrigeration unit is activated. Part of return air is
mixed with dehumidified air using the bypass damper. The dehumidification stage con-
tinues until the actual humidity value lies below that of the humidity setpoint. Subse-
quently the refrigeration unit stops and air is recirculated in the swimming pool, all
values are monitored.
When in active hours swimming pool mode the fresh and exhaust air dampers are
opened, the bypass damper is closed. To start dehumidification the refrigeration unit is
activated. The unit operates to deliver the pre-set hygienic minimum rate of outside air.
Depending on the swimming pool humidity the latter is regulated continuously.
In the event of overheated swimming pool the bypass damper is opened to divert the
heat recovery facility.
Using an optional pool water condenser a certain amount of excess energy produced
by the refrigeration cycle can be fed back into swimming pool water.
Technical Description
CAIRfricostar®
FläktGroup DC-2009-0019-GB R10/09-2020 • Specifications are subject to alteration without notice 15
3.3.2 CWT units
The FläktGroup CAIRfricostar CWT is a dehumidifier with compact configuration
designed for private and hotel swimming pools as well as therapeutic baths. This unit
series can deliver air flow rate from 750 up to 6,500 m³/h. The series is available in 5
model sizes. The unit's function is to dehumidify and heat air in swimming pools in
mixed air mode. These units are equipped with a highly efficient heat recovery facility.
The unit is delivered with a DDC controls which regulates all functions of the system
on a fully automated basis.
Fig. 3-6: FläktGroup CAIRfricostar CWT
When in stand-by mode without dehumidification the air is recirculated in the swimming
pool. When the humidity setpoint has been exceeded the unit switches into dehumidi-
fication mode. Supplementary outside air is continuously added to supply air. The
dehumidification stage continues until the actual humidity value lies below that of the
humidity setpoint. Subsequently the unit operates to deliver the pre-set hygienic mini-
mum rate of outside air. Depending on the swimming pool humidity the latter is regu-
lated continuously.
In the event of overheated swimming pool the bypass damper is opened to divert the
heat recovery facility.
Technical Description
CAIRfricostar®
16 FläktGroup DC-2009-0019-GB R10/09-2020 • Specifications are subject to alteration without notice
3.4 Technical specifications
Refer to the order-related documentation for the specific configuration of your Fläkt-
Group CAIRfricostar Micro unit (unit drawing with dimensions and technical data).
3.4.1 Operating limits and range of application
3.4.2 Ambient conditions
Outside air from -25 °C to +60 °C
Air humidity depending on temperature max. 18 g/kg of dry air
Max. operating pressure
and temperature Heating/cooling coil 16 bar / 90 °C
Minimum operating
temperature Heating/cooling coil 6 °C
3.4.3 Allowable storage conditions / allowable air condition for non-installed units
Air temperature 5 °C to 50 °C
Air humidity Store units in a dry, non-condensing atmosphere
3.4.4 Supply voltage
The required supply voltage is specified in the order-related documentation,
e.g. 3 phases 400 V (50 Hz) + N + PE.
NOTICE!
Please carefully observe the unit type plate and the operation manuals for the sup-
plied accessories.
Please refer to the enclosed documentation for the operating limits of special built-
in components.
In frost-risk cases use antifreeze agents for heating and cooling media.
Operating limits for FläktGroup CAIRfricostar special units are available on
request.
Note on extreme conditions!
Temperature/humidity of the ambient air plays an important role apart from air
temperature/air humidity of the transported medium. Observe the condensation
limits.
EQUIPMENT DAMAGE!
The switch box with control display, frequency inverter with control display and
other temperature-sensitive instruments are designed for indoor installation in
frost-free conditions.
Technical Description
CAIRfricostar®
FläktGroup DC-2009-0019-GB R10/09-2020 • Specifications are subject to alteration without notice 17
3.4.5 Condensation limits
Please pay due attention to condensation limits!
The following diagrams illustrate condensation limits depending on the temperature
and relative humidity at the installation site - for series CAIRfricostar and CAIRplus SX
T and SX K.
The diagrams are based on normal air values and are calculated using a model box.
The given values are approximate figures and can not be used as a guarantee for
avoiding condensation. Depending on different casing components, deviations are
possible.
Read example:
Air temperature on unit external side in °C
Air temperature on unit internal side in °C
Technical Description
CAIRfricostar®
18 FläktGroup DC-2009-0019-GB R10/09-2020 • Specifications are subject to alteration without notice
CAIRplus SX K
= without thermal separation Condensation diagram for kb-value: 0.5
CAIRplus SX M
= partial
thermal separation
Condensation diagram for kb-value: 0.62
Air temperature on unit external side in °C
Air temperature on unit internal side in °C
Air temperature on unit external side in °C
Air temperature on unit internal side in °C
Shipping and Storage
CAIRfricostar®
FläktGroup DC-2009-0019-GB R10/09-2020 • Specifications are subject to alteration without notice 19
4 Shipping and Storage
4.1 Delivery
FläktGroup CAIRfricostar unit can ship as a single piece or multiple individual shipment
units. Delivery is done on transport pallets.
When the unit is delivered, check that the shipment is correct according to the
despatch note, and also check for completeness.
What steps should I take in
case of shipping damage? External side of the packaging is damaged
1 Unpack the equipment in the presence of the lorry driver and document the
damage in the shipping order.
2 Inform the FläktGroup office immediately.
External side of the packaging is O.K., the contents is damaged.
1 Once you have established the extent of the damage, report the damage to the
FläktGroup office in writing.
2 Take photographs of the damaged parts.
3 Possible shipping damage must be reported no later than 4 days following the
delivery.
Processing of claims will not be possible, if the above-mentioned steps are not fulfilled.
In both cases, before installing the units - consult the FläktGroup office.
4.2 Transport
For shipping and rigging the FläktGroup unit use the lifting lugs or lifting points
provided by the manufacturer.
For safety reasons wear gloves and safety footwear when lifting or shipping the unit.
NOTICE!
Consider instructions relating to the procedures in case of shipping damage on the
unit packaging or in despatch documents!
NOTICE!
For unit shipment use the original packing only. Remove the original packaging
only before installation.
DANGER OF OVERHEAD LOADS!
Never stand beneath suspended loads, there is always a risk that the lifting gear,
tackle, ropes or slings could be damaged. Failure to follow safety precautions
could result in death or serious injury.
Shipping and Storage
CAIRfricostar®
20 FläktGroup DC-2009-0019-GB R10/09-2020 • Specifications are subject to alteration without notice
Before lifting or shipping the unit, make sure that all doors, dampers and panels are
fixed and secured.
Only use lifting gear with sufficient load-bearing capacity.
Never use damaged lifting equipment.
Ropes/chains must not be knotted and/or be exposed to sharp edges.
Only use ropes/chains of the same length.
Move the unit carefully without jerky movements.
Do not set the unit down abruptly or bump it.
Do not tilt or place on side units or modules with an integrated refrigeration system
(compressor).
4.2.1 Lifting the unit – lifting lugs on roof (provided with shipment units weighing up to 1500 kg)
Lifting lugs are designed for vertical loads only.
Do not use lifting lugs for lateral loads (pulling of unit on si-
des).
Suspension angle between diagonal lifting slings must be
within range of 70 - 110° as shown in Fig. 4-1.
Lifting lugs may only be used once.
Do not use lifting lugs for permanent suspension of units.
Do not lift any other loads together with the shipment unit.
With units for outdoor installation, ensure that the roof sheets
are not damaged by the lifting gear.
The maximum weight of the lifted shipment unit must not ex-
ceed 1,500 kg.
Use all four lifting lugs for unit shipment.
PERSONAL INJURY!
Use only the lifting lugs provided by FläktGroup! Make sure that equipment is firmly
seated before lifting the equipment.
max.1500kg
Fig. 4-1: Lifting lugs for shipment units weighing up to
1500 kg
allowed angle
range 70-110°
allowed diagonal
angle range
70-110°
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76

FläktGroup CAIRfricostar Operating instructions

Category
Split-system air conditioners
Type
Operating instructions

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI