FläktGroup LQVF Mixing section outdoor Installation guide

Type
Installation guide
Fläkt Woods 9139 GB 2011.10 1 Specifications are subject to alteration without notice
Installation instruction
Connection to duct
The return air damper in LQVF is connected to the
duct on the side (b = 1) or on the bottom (b = 2) using
the following accessories: fabric sleeve LQVZ-02,
transition piece LQVZ-03 and counterflange LQVZ-
04. Alternatively, an edged duct can be screwed
directly to the casing. Sealing strip LQAZ-10 is requi-
red in every case. Ensure that the ducts do not impose
a load on the casing.
Commissioning
Installation of damper actuators
Damper actuator LQAZ-11 (accessory) is installed in accor-
dance with the following installation.
Size 60 62 64 71 73 80 82 84
Torque, Nm
b = 1 15 + 12 2x12 + 13 2x14 + 14 2x15 + 14 2x15 + 15 2x14 + 15 2x16 + 16 2x18 + 18
b = 2 15 + 10 2x10 + 11 2x14 + 2x9 2x15 + 11 2x15 + 2x9 2x14 + 13 2x16 +2x10 2x18 + 2x11
Number of
damper motors
b = 1 2 3 3 3 3 3 3 3
b = 2 2 3 4 3 4 3 4 4
Mixing section, LQVF – outdoor execution
 IMPORTANT!
Ensure that the intake damper is open
during commissioning of the fan.
The maximum permissible pressure
difference over the damper = 1000 Pa.
Max. torque for damper actuator: 30 Nm.