Installation instruction
FläktGroup DC_9134GB 20180417_R0 Specifications are subject to alteration without notice
CONNECTION TO THE DUCTING
Connection accessories: LQVZ-02 flexible connection, LQVZ-03
connection piece and LQVZ-05 protective screen are supplied
mounted on the unit section. The LQVZ-04 counterflange is delivered in
unmounted condition and should be fitted as shown in Figs. 6 and 7.
PG-JOINT
DAMPER ACTUATION
ACTUATOR
The damper can be actuated by means of the LQVZ-01 lever actuator
(accessory) or the LQAZ-11 damper actuator motor (accessory) as
shown in Fig. 1 and 3.
ISULATION
External dampers are supplied with a cover over the lever actuator
system. This permits external insulation of the damper.
TORQUE
The table below specifies the necessary torque.
COMMISSIONING
Fig.5 Fig. 6
FLANGE CONNECTION
Fig. 7 Fig. 8
COLLARED DUCT
Fig. 9 Fig. 10
Gasket
Flexible
connection
Connection
piece
Flexible
connection
Connection
piece Gaskey
Gasket
Collared
duct
Gasket
Counter-
flange Counter-
flange
CAUTION!
When starting the fan, make sure that the intake
damper is open. The maximum permissible
pressure differential when the damper is closed
is 1000 Pa.
Maximum torque loading on the damper: 30 Nm.
Numbers of actuators Torque, Nm Sizes
115 60
212 62
214 64
213 71
215 73
214 80
216 82
219 84