Sunricher SR-2300TS-CCT-DT6 User manual

  • Hello, I'm your chat assistant. I've reviewed the user manual for the Sunricher's Touch Controller 09.230TC6.04064. This manual provides details on how to operate its touch-sensitive interface, DALI signal output, control the 4 light zones, adjust CCT color and brightness, and set addresses using rotary switches. I am ready to answer your questions about this device.
  • What is the operating temperature range?
    What is the power supply requirement?
    How many light zones are available?
    How many DALI addresses can each zone control?
    Does the controller support saving scenes?
DALI Dual Color Touch Controller 09.230TC6.04064
DALI Master/
DALI Master software
via computer
Function introduction
Important: Read All Instructions Prior to Installation
19.4 mm
60.3 mm
DALI Wall
Panel Controller
Front side
Back side
52.0 mm
60.3 mm
52.0 mm
Wiring diagram
12-24VDC
PSU AC 100-240V
Output Signal DALI signal
Power Supply 12-24VDC
Power consumption 200 mA
Operating temperature 0-40°C
Relative humidity 8% to 80%
Dimensions 86x86x29.1mm
Product Data
DO NOT install with power applied to device.
DO NOT expose the device to moisture.
Safety & Warnings
012
3
4
5
6
7
89
012
3
4
5
6
7
89
(x10)
(x1)
D1 D2V+V-
DC Power input
DALI signal output
DALI Wall
Pane l Controlle r
012
3
4
5
6
7
89
012
3
4
5
6
7
89
(x10)
(x1)
D1 D2V+V-
123
4
GND
AC Power
50/60Hz
L
N
G
V+
V-
OUTPUT
INPUT
12V/24V/36V
CV PSU
123
4
GND
ON/OFF button
V+ V+
WW WW
CW CW
WW WW
CW CW
Connect with Du al C ol or LED Stri p
V+ V+
WW WW
CW CW
WW WW
CW CW
Connect with Du al C ol or LED Stri p
CCT color slider CCT brightness slider
4 light zones, click to
select, press and hold
down to turn ON/OFF
Click to switch between
CCT color slider and
brightness slider
Scene button, press and
hold down to save a
scene, click to recall
1*(0~9) for setting
units position
10*(0~9) for setting
tens position
Rotary switches for setting start DALI address number (0-63),
the number equals to tens position plus units position
Touch sensitive.
• Glass interface(white & black).
• Comply to DALI standard protocol IEC 62386-102, IEC
62386-207 and in compliance with DALI products from
other international incorporation.
• 4 light zones are available for switch, dimming and CCT
control, each zone can control 2 DALI addresses.
• Enable to set start DALI address number (0-63) for the 4
zones by rotary switches on the back.
• Enable to save 2 scenes
Installation
12-24VDC
Power Supply
Operation
Set start DALI address number for the zones by rotary switches on the back:
Set the number as X (0-63):
Zone number Z1 will control DALI addresses X and X+1,
Zone number Z2 will control DALI addresses X+2 and X+3,
Zone number Z3 will control DALI addresses X+4 and X+5,
Zone number Z4 will control DALI addresses X+6 and X+7,
Note: if X is set as 63, zone 1 will control DALI address 63 and 00, zone 2 will control address 01 and 02, zone 3
will control address 03 and 04, zone 4 will control address 05 and 06.
/