Appendix
14
Installation
Please refer to the technical
guide ”Solar heating sys-
tems” for supplementary
notes on installation examples
and system types.
Important!
For installation purposes, use red
bronze fittings, brass fittings and
copper piping. Do not use galva-
nized pipes, galvanized fittings or gra-
phitized gaskets.
Hemp should be used only in conjunc-
tion with pressure and temperature-re-
sistant sealants*1.
The components used must be resis-
tant to the heat transfer medium (see
Service Instructions for composition).
The insulation*2 of external piping must
be resistant to temperature, UV radi-
ation and to destruction by birds (e.g.
through the use of metal sheathing).
Caution!
Do not stand on the collectors!
Do not carry out soldering work at or
near the collector!
HAt least one air vent valve should be
installed at the highest point of the
system.
Install an air separator at an acces-
sible point in the piping (e.g. in the
flow of the solar circuit, upstream of
the inlet to the indirect coil of the do-
mestic hot water cylinder).
HThe system should be equipped with
an expansion vessel, safety valve and
circulation pump.
HUse only a diaphragm expansion
vessel that is suitable for the applica-
tion as an expansion vessel.
HThe expansion vessel must be ap-
proved to DIN 4807 and must be con-
nected via a heat insulating loop.
The diaphragms and seals of the ex-
pansion vessel and safety valve must
be suitable for the heat transfer me-
dium.
Please refer to the ”Service
Instructions” in order to
calculate the inlet pressure
of the diaphragm expansion
vessel.
HFill the solar heating system with
Viessmann heat transfer medium ”Ty-
focor-HTL”. The blow-off and dis-
charge pipes must be run to an open
container capable of accommodating
the total capacity of the collectors.
HThe Solar-Divicon is equipped with a
safety valve designed for 120 ºC and
max. 6 bar.
HFor operation without the Solar-Divi-
con, use only safety valves rated for
120 ºC and max. 6 bar with a part des-
ignation containing the code letters
”D/G/H”, ”F” or ”H”.
On smaller solar heating systems
with a collector surface area up to
5m
2, Vitocell 300 cylinders with a pe-
ripheral heating system and a capacity
of 200 litres may also be used as solar
storage cylinders for preheating pur-
poses.
In this case, the Solar-Divicon must be
equipped with a 3 bar safety valve (ac-
cessory). The static head should be
7 metres max., the overpressure in the
collectors approx. 1 bar and the inlet
pressure of the diaphragm expansion
vessel approx. 1.5 bar.
In such cases, we recommend an ex-
pansion vessel with a capacity of 33
litres.
HTo guarantee the satisfactory oper-
ation of the solar heating system, in-
stall the pipes so that complete vent-
ing is assured.
HThe connecting lines must be pres-
sure and temperature-resistant (ob-
serve the max. shutdown tempera-
ture of the collector).
*1E.g. Viscotex solar paste supplied by Locher, CH-9450 Altstätten.
*2E.g. HT/Armaflex (temperature resistant up to 175 ºC) supplied by Armstrong Insulation Products GmbH, Robert-Bosch-Str. 10,
*2D-48153 Münster.
5492 780 GB