FläktGroup MINIMASTER RDKS Installation guide

Category
Split-system air conditioners
Type
Installation guide
INSTALLATION, OPERATION, MAINTENANCE AND SPARE PARTS
HEAT RECOVERY UNIT
MiniMASTER RDKS
MiniMASTER RDKS - Installation & maintenance
2
FläktGroup DC_9295GB_20201102_R6
We reserve the right to make changes without prior notice
CONTENTS
NOTE! INSTALLATION, ADJUSTMENT AND COMMISSIONING AS DESCRIBED
IN THESE INSTRUCTIONS MUST BE CARRIED OUT BY AN INSTALLER OR SERVICE PERSONNEL.
OPERATION AND MAINTENANCE (FOR USER)
Functions, system design, electrical data, energy class ............................................... 3
ISYteq Basic control panel
Operation .................................................................................................................................... 4
Overview of symbols and functions ................................................................................ 5
ISYteq Touch 3.5 control panel .....................................................................................................
General information ................................................................................................................ 6
Cleaning of the display .........................................................................................................6
General buttons and symbols ............................................................................................6
Home screen ............................................................................................................................ 7
Operation ....................................................................................................................................8
Maintenance and cleaning of heat exchanger and fans ..............................................10
Filter alarm and filter replacement .........................................................................................11
Overheating protection, impeller alarm, temperature alarm, other alarms .......... 12
INSTALLATION (FOR INSTALLER AND SERVICE PERSONNEL)
Dimensions, installation measurements 13
Wiring and connection diagram.............................................................................................. 14
Duct connection, duct insulation .............................................................................................15
Installation options and duct definitions ..............................................................................16
Installation of unit with accessories .......................................................................................17
ADJUSTMENT, COMMISSIONING (FOR INSTALLER AND SERVICE PERSONNEL)
Settings, date/time, language ................................................................................................. 22
Login, settings ................................................................................................................................ 23
Adjustment .......................................................................................................................................24
Control panel operation, commissioning ............................................................................ 25
Parameter list ................................................................................................................................. 28
MISCELLANEOUS
Spare parts ..................................................................................................................................... 33
EC Declaration of Conformity ....................................................................................................34
Disposal of products and packaging materials ............................................................... 35
Declaration of Conformity .......................................................................................................... 36
WARNING! THE APPLIANCE MAY BE USED BY CHILDREN OVER THE AGE OF 8, PERSONS (INCLUDING CHILDREN) WITH PHYSICAL,
SENSORY OR MENTAL DISABILITIES OR LACK OF KNOWLEDGE OR EXPERIENCE, PROVIDED THEY HAVE RECEIVED INSTRUCTION
OR INFORMATION ON SAFE USE OF THE APPLIANCE AND UNDERSTAND THE POTENTIAL RISKS. CHILDREN MAY NOT PLAY WITH
THE APPLIANCE. CHILDREN MAY NOT CLEAN OR PERFORM MAINTENANCE ON THE APPLIANCE WITHOUT SUPERVISION.
MiniMASTER RDKS - Installation & maintenance
3
FläktGroup DC_9295GB_20201102_R6
We reserve the right to make changes without prior notice
OPERATION AND MAINTENANCE – FUNCTIONS, SYSTEM DESIGN, ELECTRICAL DATA, ENERGY CLASS
THE UNIT’S MAIN COMPONENTS
8
2
6, 10
5
41
3
121311
7
9
1. Outdoor air sensor
2. Extract air sensor
3. Supply air sensor
4. Preheater
5. Extract air fan
6. Heat exchanger
7. Supply air filter
8. Control unit
9. Casing
10. Heat exchanger motor
11. Extract air filter
12. Postheater
13. Supply air fan
FANS
The fans are powered by energy-efficient EC motors. They are easy to
remove for service and maintenance. The speed of the fans can be ad-
justed independently of each other.
HEAT RECOVERY AND SUPPLEMENTARY HEATING
In climates where the temperature seldom drops below -10 °C, there is
usually no need for supplementary heating. This is because the rotary
heat exchanger recovers enough thermal energy from the extract air (
85% h
temp
).
When the outdoor temperature is below -10 °C and the desired supply
air temperature cannot be achieved, a postheater is required, which is
controlled to maintain the set supply air temperature. In very cold are-
as, the unit can also be supplemented with a heater that preheats the
outdoor air. This heater starts preheating the air when the outdoor
temperature falls below -12 °C.
The electric heaters have an integrated overheating protection function.
NOTE! THE ELECTRIC POSTHEATER IS ONLY ACTIVATED IF THE
IMPELLER IS IN OPERATION.
FILTER
As standard the unit is fitted with a class (M5) ISO Coarse 85% bag fil-
ter. For filter replacement, see page 11.
DEFROSTING
During cold periods, when frost may form in the impeller, the integrat-
ed control unit automatically activates a defrosting function. The unit
defrosts for 15 minutes every 6 hours if the outdoor temperature is
below -10 °C. The supply air fan stops and the impeller moves forward
in sections.
COOLING RECOVERY
In the summer, if the extract air is cooler than the outdoor air, the rota-
ry heat exchanger starts to recover cooling from the cooler extract air.
This primarily applies if there is some type of cooling appliance in the
house.
ALARMS
The ISYteq Basic control panel (accessory) has a limited alarm
indicator function. The panel indicates, for instance, when there is a
temperature alarm or when the filter needs replacing.
If the ISYteq Touch 3.5 control panel (accessory) is used, the alarm will
be presented in plain text (see separate instructions).
MOISTURE CONTROL (OPTIONAL)
This function automatically limits the rotary heat exchanger’s moisture
recovery at high indoor humidity levels. This function can also be or-
dered retrospectively to supplement the unit.
CO2 CONTROL (OPTIONAL)
This function regulates towards a preset setpoint. The fan speed is
automatically adjusted to achieve the desired CO
2
level.
NOTE! CO
2
control requires a ISYteq Touch 3.5 control panel. This func-
tion can also be ordered retrospectively to supplement the unit.
ETHERNET CONNECTION (OPTIONAL)
This function can be used to connect the unit to an existing network.
In that case, the unit is equipped with an integrated web server, which
makes it possible to read and change certain parameters via a web
browser. The connection can also be used for connection to a superior
system via Modbus TCP/IP.
To optimize the performance of communication, please follow the rec-
ommendations below.
- Minimize the number of general broadcasts.
- Only send dedicated traffic to the controller.
- Do not attempt to access the web server when using Modbus TCP-IP.
- Maximum of one Modbus message per second is recommended.
Avoid data bursts.
- Only write to Modbus registers when values have been changed.
ELECTRICAL DATA
Voltage: 230V, single phase, 50 Hz
Code Fan motors
Rated output, W
Preheater
Electr., W
Postheater
Electr., W
Rated output
Electr., W1)
Rated output
with cooker hood
RDKS 2 x 83 500 500 1170 1210
1) Rated output applies when both the preheating and the postheating devices are
installed.
ENERGY CLASS
Compliant with energy class A+ in cold climate conditions (Scandinavia).
If configured for on-demand control, the unit is compliant with energy
class A in average climate conditions (Central Europe). Ecodesign
Directive 1254/2014.
MiniMASTER RDKS - Installation & maintenance
4
FläktGroup DC_9295GB_20201102_R6
We reserve the right to make changes without prior notice
The unit has a built-in control unit that controls the operation of the
fans, the rotary heat exchanger and any electric heaters.
The unit is controlled via an external ISYteq Basic or ISYteq Touch 3.5
control panel (accessory), see page 6. The control unit should be in-
stalled in a suitable place.
After being adjusted, the unit can also be operated without a control
panel, but only in one operating mode.
The user can select between the following operating
modes:
AWAY” is used when there is reduced need for ventilation, e.g.
when occupants are on holiday
“HOME” used for normal ventilation flow
“FORCED” is used when there is a greater need for ventilation (au-
tomatically reverts to normal after 120 minutes)
Use the arrow button to switch operating modes (see figure 2). A LED
shows the current operating mode.
Figure 1. Control panels.
Operating modes ISYteq Basic
HOME
AWAY FORCEDArrow button (for selecting
operating mode)
Forced via CPDJ cooker hood.
UNIT WITH COOKER HOOD
When the boost damper in the cooker hood is opened, the fan
speed increases. Forced mode continues while the boost damper
remains open. After that, the fans resume normal speed.
ISYteq BASIC CONTROL PANEL - OPERATION
Forced via CPTJ cooker hood.
x1 = 15 min
x2 = 30 min
x3 = 60 min
12315 30 60
15 30 60
Boost damper
(one press per
time setting)
BOOST
TRICKLE/NORMAL
14:35
21
14:35
21
ISYteq Touch 3.5ISYteq Basic
MiniMASTER RDKS - Installation & maintenance
5
FläktGroup DC_9295GB_20201102_R6
We reserve the right to make changes without prior notice
HOMEAWAY FORCED
SYMBOLS DURING NORMAL OPERATION
ISYteq BASIC CONTROL PANEL - OVERVIEW OF SYMBOLS AND FUNCTIONS
Symbol Description
AWAY mode
HOME mode
FORCED mode for 120 minutes
Defrosting mode. The unit resumes normal operation after 15 minutes
Switch operating modes between: AWAY, HOME and FORCED.
Disabled during defrosting
Min. 10 sec. Press * for a minimum of 10 seconds to reset an alarm. Also see pages 11 and 12.
Continuously flashing alarm symbol indicates filter alarm. See page 11.
Three flashes at intervals indicates rotor alarm. See page 12.
Steady illumination indicates temperature alarm. See page 12.
No symbols illuminated
indicates that unit has
stopped.
See Other alarms on page 12.
Figure 5. Symbol description ISYteq Basic.
+
MiniMASTER RDKS - Installation & maintenance
6
FläktGroup DC_9295GB_20201102_R6
We reserve the right to make changes without prior notice
ISYteq TOUCH 3.5 CONTROL PANEL
GENERAL
The control panel has a touch screen display. Use your finger or the
back of a pen to navigate in the menus.
When the power is switched on, all the menus will be imported into
the system. This will take about 20-30 seconds. After this, the home
screen will be displayed.
CLEANING OF THE DISPLAY
Disconnect the unit from the power supply by disconnecting the power
cord. Carefully wipe the display with a soft, dry, non-abrasive cloth.
If any marks remain, moisten the cloth slightly with a detergent spe-
cially designed for LCD or mobile screens and wipe the screen gently
from top to bottom.
Never use other detergents, as they may contain ammonia or other
additives that could damage the display.
IMPORTANT:
Never spray or pour liquids directly onto the display.
Never clean the control panel when the system is switched on.
GENERAL BUTTONS AND SYMBOLS
The following buttons and symbols are universal and available on
many menu pages.
Home button, to return to the home screen.
Back button, to cancel and return to the previous page.
Confirm button, to confirm and proceed.
Changing a value.
Option 1: Press the arrow keys to increase or decrease
the value.
Option 2: Press the displayed number to enter the cho-
sen value (see below).
Use the number keys to enter a value.
Confirm with or cancel with .
Read-only values (without a surrounding
window), cannot be changed.
Editable values (surrounded by a win-
dow), can be changed.
Some submenus have more than
one page. Click the upper
or lower part of the scroll list to
navigate between pages.
NOTE! The cursor cannot be
moved vertically.
14
MiniMASTER RDKS - Installation & maintenance
7
FläktGroup DC_9295GB_20201102_R6
We reserve the right to make changes without prior notice
ISYteq TOUCH 3.5 CONTROL PANEL - HOME SCREEN
ALARMS
No alarm
Alarm B
Alarm A
Heat recovery active
Postheater active
Preheater active
Defrosting in progress
Manual mode
Heating stove mode
CO2 control
Forced via cooker hood
Away mode
Home mode
Forced mode
STATUS LINE
OPERATING STATUS
OPERATING MODES
CLOCK
CURRENT SETPOINT,
SUPPLY AIR TEMPERATURE
The user can select between the following operating modes:
AWAY” used when there is reduced need for ventilation, e.g.
when occupants are on holiday
“HOME” used for normal ventilation flow
“FORCED” used when there is a greater need for ventilation
(automatically reverts to normal after 120 minutes)
MiniMASTER RDKS - Installation & maintenance
8
FläktGroup DC_9295GB_20201102_R6
We reserve the right to make changes without prior notice
ALARMS
See page 9.
SHORTCUT TO SETTING OF TEMPERATURE SETPOINT
See page 9 for more information on temperatures.
MENU
See page 9.
SHORTCUT TO SETTING OF
DATE AND TIME
SELECT OPERATING STATUS
See page 9.
AWAY MODE HOME MODE FORCED MODE
Press the relevant field to select operating mode.
The operating mode cannot be changed during defrosting,
or during forced operation with a cooker hood.
ISYteq TOUCH 3.5 CONTROL PANEL - OPERATION
MiniMASTER RDKS - Installation & maintenance
9
FläktGroup DC_9295GB_20201102_R6
We reserve the right to make changes without prior notice
SELECTING OPERATING STATUS
The symbol on the home screen shows the operating status. Press the
centre of the fan symbol to change the status.
Normal mode (manual)
Heating stove mode, makes it easier to light a heating stove
or open fireplace. Temporarily creates overpressure in the
house.
ALARMS
The symbol on the home screen shows the alarm status.
No alarm
Alarm B
Alarm A
Press the icon to enter the alarm screen.
MENU
TEMPERATURES
Here you set the desired supply air temperature (setpoint).
Note: This value is not to be confused with the desired in-
door temperature, which is managed by the domestic heat-
ing system. The recommended setpoint is 16–19 °C. The
factory setting is 18 °C. Temperatures, output signals etc.
are read-only values.
FAN STATUS
Supply and extract air fan speeds can be read from
30 –100 % or as 0 (off).
AIR QUALITY
Air quality (only available if optional moisture control or CO
2
control is activated). Relative humidity of the supply and
extract air can be read from 0-100% RH.
The setpoint and current CO
2
value (up to 2,000 ppm) can
be read.
SYSTEM OVERVIEW
Version control panel -- -- -- -- -- -- -- -- -- -- -- --IP Octet 1
Bootloader control panel --------------------IP Octet 2
Version control card ------------------------ IP Octet 3
Bootloader control card -- -- -- -- -- -- -- -- -- -- --IP Octet 4
Unit type
TIME SCHEDULES
(Not applicable to domestic ventilation).
SETTINGS
See pages 22–23.
Example 1 No alarm Example 2. Active alarms
ALARM HISTORY
ISYteq TOUCH CONTROL 3.5 PANEL - OPERATION
CLEARING ALARMS
To clear an individual alarm, press Acknowledge after the relevant
alarm. To clear all the alarms, press Acknowledge All button (top right).
If the alarm cannot be cleared, it will reappear on the display and the
underlying cause for this must be resolved before the alarm can be
cleared.
A built-in timer is normally set to provide a filter replacement reminder
(alarm) every six months. If a shorter replacement interval is required
(before the alarm is due) the filter alarm can be reset under the Set-
tings menu. See page 22, fig. 3.
MiniMASTER RDKS - Installation & maintenance
10
FläktGroup DC_9295GB_20201102_R6
We reserve the right to make changes without prior notice
Clean the impeller housing and the fan blades with a brush or a vacuum cleaner.
NOTE! Take care not to damage any impeller housing balancers, and ensure
that no cables are trapped during reassembly.
Mode
LED
Param.
Mode
LED
Param.
MAINTENANCE AND CLEANING OF HEAT EXCHANGER AND FANS
Before cleaning the heat exchanger, fans etc., the unit should always have the power
disconnected.
CLEANING OF FANS
Note that the fans must not be cleaned with water or other fluids; they
may only be vacuum cleaned or brushed.
Remove the unit’s front cover (if there is one). Remove the screws on the door and
open the door. The picture shows a unit with right-hand configuration (RDKS-1).
Remove the heat exchanger package from the unit. Disconnect the electrical con-
nection to the impeller motor.
Vacuum clean the heat exchanger or blow clean with compressed air.
Disconnect the impeller from the fan housing by unscrewing the screws on the side
of the fan housing.
GENERAL
The fans, filters and heat exchanger are very important for the opera-
tion and economy of the unit. For this reason, it is crucial for them to
be kept clean and in good condition.
We recommend a general check-up every 6 months. For safety rea-
sons, general caution should be observed during maintenance of the
unit. Be careful to avoid trapping any cables. If necessary, use protec-
tive gloves.
CLEANING OF THE HEAT EXCHANGER
Check that the surface of the rotor is not coated with dust. Clean with
a vacuum cleaner or by blowing through with compressed air. If vac-
uum cleaning is not sufficient, hand-spray with grease dissolving fluid
and then blow clean with compressed air. Use the compressed air to
blow away from the clean side towards the dusty side.
Note! Water, acetone or similar solvents must not be used.
Remove the fan from the unit. Disconnect the electrical connection.
The drive belt and seals may need replacing due to wear and tear.
Check them for damage and replace if necessary. For designations,
see spare parts list on page 33.
MiniMASTER RDKS - Installation & maintenance
11
FläktGroup DC_9295GB_20201102_R6
We reserve the right to make changes without prior notice
FILTER ALARM AND FILTER REPLACEMENT
B
A
Mode
LED
Param.
Mode
LED
Param.
The picture shows a bag filter. A flat filter may also be used.
3. Pull out the supply air and exhaust air filters. Dispose of used filters
according to local waste regulations.
4. Insert new filters.
2. Open the door of the unit by unscrewing the two screws on the front
(see below).
5. Close the door of the unit.
6. Connect the plug.
7. After replacing the filter, reset the filter alarm.
If a filter is replaced before the alarm is due, the filter replacement
timer cannot be reset via the ISYteq Basic control panel (accessory).
If there is no ISYteq Touch 3.5 control panel (accessory) on the unit
when the filter is replaced, the timer must be reset when the alarm is
due, i.e. when the set time is reached. For resetting, see page 22.
The supply air and exhaust air filters should normally be replaced
every six months. In dirty areas, the filters may need to be replaced
more frequently.
A built-in timer is normally set to provide a filter replacement reminder
every six months.
TO REPLACE THE FILTER, FOLLOW THE STEPS BELOW.
When replacing dirty filters, use of a face mask is recommended (low-
est class, FFP2).
1. Disconnect the unit from the power supply by pulling out the plug.
The reason for the alarm is shown under active alarms.
After replacing the filter, acknowledge the alarm.
FILTER ALARM ISYteq BASIC
When the filter needs replacing, a continuously flashing alarm light is
shown on the ISYteq Basic control panel.
FILTER ALARM ISYteq TOUCH 3.5
Press the Information/alarm button if the alarm is indicated.
A continuously flashing alarm
symbol indicates filter alarm.
After replacing the filter, reset the filter timer by pressing the * button on the
control panel for a minimum of 10 seconds.
MiniMASTER RDKS - Installation & maintenance
12
FläktGroup DC_9295GB_20201102_R6
We reserve the right to make changes without prior notice
OVERHEATING PROTECTION, ROTOR ALARM, TEMPERATURE ALARM, OTHER ALARMS
THERMAL OVERLOAD PROTECTION
The fan motors are equipped with thermal overload protection devices,
which are reset manually by briefly disconnecting the power.
The electric heaters have two thermal overload protection devices, one
automatic and one manual. The automatic overheating protection trips
before the manual one, which means it does not normally need to be
reset.
If the manual overheating protection for the electric heater has tripped
during operation, first the power to the unit should be switched off and
then the overheating protection should be reset by pressing the reset
button.
In order to access the button, the electric heater must be disconnect-
ed.
If the manual overheating protection trips again, call qualified service
personnel.
ROTOR ALARM
If the rotor motor stops and the Tacho signal disappears, five attempts
will automatically be made to restart the rotor (start/stop). If this does
not solve the problem, the unit will stop and the rotor alarm will be in-
dicated.
TEMPERATURE ALARM
Generates an alarm and stops operation if the supply air temperature
drops below +5 °C. The alarm is disabled during defrosting or dur-
ing forced operation with a cooker hood. A 10-minute delay ensures
that the supply air temperature has time to rise if operation has been
stopped.
OTHER ALARMS
The unit has various alarms that are not supported by the simple
ISYteq Basic control panel (accessory).
If any of these alarms are triggered, the unit will stop running and all
the LEDs on the ISYteq Basic will be extinguished. This also happens
in the event of power failure. A LED on the control card indicates that
the power is not switched off.
To reset these alarms, the unit must be restarted by pulling out and
reconnecting the plug.
If the ISYteq Touch 3.5 control panel (accessory) is used, the alarm will
be presented in plain text.
If the alarm recurs, service personnel will be called for assistance.
SENSOR ERROR
If any of the temperature sensors starts malfunctioning, the unit will
stop running. To reset, follow the instructions under Other alarms.
EXTERNAL ALARM
An external alarm can be connected to the unit. If this alarm is trig-
gered, the unit will stop running To reset, follow the instructions under
Other alarms.
MiniMASTER RDKS - Installation & maintenance
13
FläktGroup DC_9295GB_20201102_R6
We reserve the right to make changes without prior notice
RDKS-1 RIGHT
Outdoor air and supply air to the right. Right-hinged door.
INSTALLATION - DIMENSIONS, INSTALLATION MEASUREMENTS
Weight: 40 kg
600
595
115
70
95
UA
TF
78 183 265 285
203 240
83
188
595
32
380
115 70
78
183 265
95
285
203240
83 188
595
U
A
T
F
600
595
32
380
INSTALLATION MEASUREMENTS
RDKS-2 Left RDKS-1 Right
RDKS-2 LEFT
Outdoor air and supply air to the left. Left-hinged door.
Connection (female) T F U A
Diameter 125 100 100 125
Supply air Extract air1) Outdoor air1) Exhaust air
1) To be increased to Ø125 as soon as space allows.
RDKS
Kitchen
cabinet
Kitchen
cabinet
Kitchen
cabinet Max 385
Min 95 Adapter
section
Adapter
section
RDKS Kitchen
cabinet
Kitchen
cabinet
RDKS
Kitchen
cabinet
Kitchen
cabinet
Kitchen
cabinet Max 385
Kitchen
cabinet
Min 95 Min 95
RDKS
Min 95
Adapter
section
RDKS
Kitchen
cabinet
Adapter
section
RDKS
369 369
84 84
MiniMASTER RDKS - Installation & maintenance
14
FläktGroup DC_9295GB_20201102_R6
We reserve the right to make changes without prior notice
WIRING AND CONNECTION DIAGRAM
WIRING AND CONNECTION DIAGRAM, CONTROL CARD
230 V
L N PE
Max 24V,
200 mA
Timer 1 Timer 2
USB
N
MDI MDI
L
C
NO
N
L
N
L
N
L
Tacho
1 N
2 L
3 N
4 L
5 N
27
70 69 68 67 66 65 64
28 3732 33 34 3835 3613 14 15 16
51
50
49
48
47
46
6 L
7 N
8 L
11 N
12 L
0 V
+10 V
A
A
B
B
B A
GND
Output 0-10V
+24 V
GND
N
L
0 V
+10 V
N
L
board
Door switch
Sum alarm
Impeller
Extract air fan
CO
2
sensor
External alarm
(Volt free contact)
Supply air fan
Temp. outdoor
Temp. extract
Moisture sensor
extract air
Moisture sensor
supply air
Temp. supply
Post-heater
Pre-heater
Ethernet board
(accessory)
RS485
ISYteq Touch
ISYteq Basic
Cooker hood
MiniMASTER RDKS - Installation & maintenance
15
FläktGroup DC_9295GB_20201102_R6
We reserve the right to make changes without prior notice
DUCT CONNECTION
Exhaust air from the unit may only be connected to a ventilation
duct intended for this purpose. Connection must not be made to a
smoke or gas flue. In case of extract air ventilation in premises where
a smoke or gas flue is used (for instance, an open fireplace or heating
stove), an adequate supply air flow must be ensured A kitchen flue
must be installed in accordance with applicable regulations.
We recommend having a separate extract air device in the kitchen and
a boost damper with dense blades to ensure heat recovery from air in
kitchen.
DUCT CONNECTION, DUCT INSULATION
Note! During installation, the instructions regarding unit installation and duct insulation must be adhered
to without deviation. Otherwise, there is a risk of condensation and moisture resulting in major damage.
DUCT INSULATION
In order for the installation of the unit to be effective, it is crucial that
the installation of the ventilation ducts in the unit, as well as the instal-
lation of ducts through external walls containing insulation and vapour
barriers, roofs and joists, is executed in a professional manner. Other-
wise there is a risk of condensation, resulting in moisture damage.
If older units are replaced, it is also necessary to inspect ducts and
duct insulation for damage and ensure they are of adequate quality.
Supply air ducts (T) and extract air ducts (F), i.e. ducts containing
warm air, which are located in unheated spaces, must be insulated.
The insulation should be installed externally and have a wind-proof
surface.
Outdoor air ducts (U) and exhaust air ducts (A), i.e. ducts filled with
cold air, which are located inside the building’s vapour barrier, must be
insulated and have a diffusion-proof (moisture-proof) surface. Given the
high degree of heat recovery achieved by the unit, the exhaust air also
gets very cold and must be thermally insulated. Moreover, ducts which
run alongside each other must have a common vapour barrier.
For designations of the various ducts, see figure 15 on previous page.
The wall on which the unit is to be installed must be well insulated.
All figures in this table are recommended values which apply in central Sweden. Please check for local variations.
DUCTS IN WARM SPACES (INDOORS)
The temperature of the air
in the duct is above +10 °C The temperature of the air
in the duct is below +10 °C
No insulation
Supply air ducts (T)
Extract air ducts (F)
Outdoor air duct (U)
Exhaust air duct (A)
Supply air duct (T)
Extract air duct (F)
Fire protection
mesh mat 30 mm
with moisture-proof surface
DUCTS IN COLD SPACES
Supply air duct (T) Outdoor air duct (U)
Extract air duct (F) Exhaust air duct (A)
DUCTS IN LOOSE WOOL
RECOMMENDED INSULATION AND VAPOUR BARRIERS FOR DIFFERENT TYPES OF DUCTING
Ducting type Approved material and
location
Duct in a warm space
Insulation
Vapour
barrier Duct in a cold space Insulation Vapour barrier
Exhaust air (flue)
In kitchen Sheet metal, accessible for
inspection Armaflex AF3, 19 mm Yes – –
Between joists and in attic Sheet metal Fire protection E15, Yes Fire protection E15, Only inside
mesh mat 30 mm mesh mat 50 mm building's vapour barrier
Exhaust air (no flue) Sheet metal Mineral wool 25 mm Yes – –
Between joists and in attic Sheet metal Mineral wool 30 mm Yes Mineral wool 30 mm Yes
From tumble dryer Sheet metal Mineral wool 30 mm No Mineral wool 100 mm No
Outdoor air
In kitchen Sheet metal, accessible for
inspection Armaflex AF3, 19 mm Yes – –
Between joists and in attic Sheet metal Mineral wool 60 mm Yes Inside building’s vapour barrier Only inside
Mineral wool 60 mm building's vapour barrier
Supply air Sheet metal No requirements Mineral wool at least 80 mm No
Extract air or equivalent.
Roof truss
Moisture barrier
Moisture barrier
Moisture barrier
Moisture barrier
The sheet must be bound
tightly to the duct.
Min thickness 10 cm.
Roof truss
Moisture barrier
Moisture barrier
Moisture barrier
Moisture barrier
The sheet must be bound
tightly to the duct.
Min thickness 10 cm.
Min thickness 10 cm.
Moisture barrier
Roof truss
Roof truss
Moisture barrier
Moisture barrier
Moisture barrier
Moisture barrier
The sheet must be bound
tightly to the duct.
Min thickness 10 cm.
Min thickness 10 cm.
Moisture barrier
Roof truss
MiniMASTER RDKS - Installation & maintenance
16
FläktGroup DC_9295GB_20201102_R6
We reserve the right to make changes without prior notice
INTRODUCTION
If the unit is not installed immediately after delivery, it should be stored
well-protected under a roof in its original packaging. We recommend
that the unit always be lifted by two people. Protective gloves should be
worn.
INSTALLATION OPTIONS
The unit should be positioned as shown in the ventilation drawing. If no
ventilation drawing is available, installation should be done according to
one of the installation options below. The unit is intended for installation
indoors in a warm space.
The unit must be connected to an earthed power
outlet.
To prevent accidents and injury:
The unit must be connected to ducting and the door
must be closed before the power is switched on.
INSTALLATION OPTIONS AND DUCT DEFINITIONS
T
K
U
F
A
DUCT DEFINITIONS
Figure 15. Duct definitions.
T = Supply air
F = Extract air
U = Outdoor air
A = Exhaust air
K = Extract air device in kitchen (not above cooker).
Ducts U and F should be increased to Ø125 mm as
soon as space allows after the unit.
MiniMASTER RDKS - Installation & maintenance
17
FläktGroup DC_9295GB_20201102_R6
We reserve the right to make changes without prior notice
INSTALLATION OF UNIT WITH ACCESSORIES
If the unit is not installed immediately after delivery, it should be stored
well-protected under a roof in its original packaging. The unit is in-
tended for installation indoors in a warm space, and may only be used
* Adapt to fit relevant cupboards.
while connected to ducts. We recommend that the unit be lifted into
place by two people wearing protective gloves.
6501)
30
50
600
100
210
1) lower edge
of unit
1
3
2
4
*) Adapt to fit relevant cupboards.
NOTE! Distance from centre of upper
stud to lower edge of unit = 650 mm
Note! It is important from a sound perspective that the wall on which
the unit is to be installed is well insulated.
25
50
X mm
A x 2
X
12
A
A
A
A
USB
1 N
2 L
3 N
4 L
5 N
27
70 69 6867 66 65 64
28 37323334 383536
13141516
51
50
49
48
47
46
6 L
7 N
8 L
11 N
12 L
A
B
Plaster
Mineral wool
650
A
600
50
50
max 200
1350*
The unit must be connected
to an earthed power outlet
MiniMASTER RDKS - Installation & maintenance
18
FläktGroup DC_9295GB_20201102_R6
We reserve the right to make changes without prior notice
INSTALLATION OF UNIT WITH ACCESSORIES
8
7
3
2
1
RDKS
RDKS
4
5
4.1 4.2
7
6
The picture shows a unit with a right-hand configuration.
NOTE! If an Ethernet cable is used, make sure it is long enough to al-
low the unit door to be opened without problems.
65
1
2
(If applicable)
Ethernet cable
1
2
500
Make sure that the unit don’t fall of by folding out at least two of
the locking elements on the mounting plate, as well as securing the
unit at the bottom with the provided mounting angles.
MiniMASTER RDKS - Installation & maintenance
19
FläktGroup DC_9295GB_20201102_R6
We reserve the right to make changes without prior notice
9
10
INSTALLATION OF UNIT WITH ACCESSORIES
INSTALLATION OF FRONT COVER RDKZ-15-b-c-ddd-e (ACCESSORY)
INSTALLATION OF FRONT COVER RDKZ-15 WITH
OVER-CABINET PANEL ABOVE KITCHEN CABINETS
11
INSTALLATION OF EXTENSION UNIT TOWARDS THE
CEILING RDKZ-17 WITH FRONT COVER RDKZ-15 AND
SUSPENSION HOOKS RDKZ-16 (ACCESSORY)
An extension unit (kit) for the front cover is available to order. It is available in two
heights to ensure coverage all the way up to the ceiling (see figure above). It can be
adjusted to fit different cupboard depths and should be placed inside the front cover,
slightly overlapping. Note! The front cover must be installed with suspension hooks
in order to be able to fit the extension unit.
1) The measurement 90 refers to the distance from the outside of the unit door to
the outer edge of the curve on the cover plate.
For dismantling instructions, see www.flaktgroup.com
AA
A A
3
1
RDKZ-15
B
BB
B
2
3
9.1 9.2
Max 593
350
Overlap
ca 10 mm
Ceiling/Wall
Screw
Side panel
Front panel
Spacer
593
600
Kitchen
cabinet
Section
Over-cabinet panel
Over-cabinet panel
(not included in delivery)
Unit hatch (15 mm)
Front cover
RDKZ-14
Cover panel
90
1)
Cover panel (included in RDKZ-14-b-0)
RDKR
Max 593
350
Overlap
ca 10 mm
Ceiling/Wall
Screw
Side panel
Front panel
Spacer
593
600
Kitchen
cabinet
Section
Over-cabinet panel
Over-cabinet panel
(not included in delivery)
Unit hatch (15 mm)
Front cover
RDKZ-14
Cover panel
901)
Cover panel (included in RDKZ-14-b-0)
RDKR
MiniMASTER RDKS - Installation & maintenance
20
FläktGroup DC_9295GB_20201102_R6
We reserve the right to make changes without prior notice
19
99
1
2
1. Determine and mark the position of the bracket in the height of the
kitchen cabinet using the bracket.
4
4
43
3
3
3
4
99
99
99
INSTALLATION OF MOUNTING KIT FOR KITCHEN CABINET DOOR IN FRONT OF THE UNIT RDKZ-18-1
12
Mounting kit RDKZ-18-1
2. Determine the position of the brackets on the kitchen cabinet door
sideways through marking on the bracket, see the picture above.
3. Fit the brackets on the kitchen cabinet door using wood screws.
4. Fit the 4 set screws in the front hollow row of the side cabinets.
5. Hook on the cover, tighten the set screws if necessary.
INSTALLATION OF UNIT WITH ACCESSORIES
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40

FläktGroup MINIMASTER RDKS Installation guide

Category
Split-system air conditioners
Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI