4. Feed the control cable into the electronics module.
5. Connect the cable to X535 1, in accordance with the wir-
ing diagram.
6. Screw the wall holder onto the electronics module, the
junction box or against the wall.
cEnsure that the wall behind the wall holder is even.
2.7 Installing sensors for control (accessory)
For some controls, a sensor is required to provide the input:
•automatic CO
2 control
Connect the sensor that is to be used to the appropriate con-
nection point in the electronics module.
2.7.1 Installing CO2 sensor
With automatic CO2 control, the CO2 level is supplied by the
building management system (BMS). If this information is not
available, a CO2 sensor must be connected.
1. Place the CO2 sensor (accessory) in extract channel 1, in
accordance with the supplied instructions.
2. Connect the sensor to X3 (G UI 24VAC) 2in the elec-
tronics module in accordance with the wiring diagram.
nThe CO2 level in the room must be optimal at least
once per week so that the sensor can maintain a
good calibration level.
If this situation does not occur naturally, you can
make it happen by (for example) having the unit start
up an hour earlier once per week.