Page 8 of 8 75.5892.05 UNIVERSAL KEYPADS FAMILY 20210407
BEA Inc., the sensor manufacturer, cannot be held responsible for incorrect installations or incorrect adjustments of the sensor/device; therefore, BEA Inc. does not
guarantee any use of the sensor/device outside its intended purpose.
BEA Inc. strongly recommends that installation and service technicians be AAADM-certifi ed for pedestrian doors, IDA-certifi ed for doors/gates, and factory-trained for the
type of door/gate system.
Installers and service personnel are responsible for executing a risk assessment following each installation/service performed, ensuring that the sensor/device system
performance is compliant with local, national, and international regulations, codes, and standards.
Once installation or service work is complete, a safety inspection of the system shall be performed and documented per the manufacturer’s recommendations or industry
guidelines. Examples of compliance may apply to ANSI 156.10, ANSI 156.19, ANSI/DASMA 102, ANSI/DASMA 107, UL294, UL325, and International Building Code.
BEA, INC. INSTALLATION/SERVICE COMPLIANCE EXPECTATIONS
Tech Support & Customer Service: 1-800-523-2462
©BEA | Original Instructions | PLEASE KEEP FOR FURTHER USE - DESIGNED FOR COLOR PRINTING
USER OPERATION
Simply enter the user code provided to you.
If 3 invalid consecutive keyboard input entries occur, the keypad will be disabled for 60 seconds.
FACTORY RESTORE
DOOR MODE
RESTORE TO FACTORY DEFAULTS
(clears all user codes, resets admin code length and admin code)
Enter “setup” mode.
Press the star (*) key and then “8”. Mode LED will flash red.
Press “9” twice. A long beep will sound. Mode LED will flash red.
Press “#” twice to exit “setup” mode. Mode LED turns green.
OPTIONAL PROGRAMMING
TAMPER ALARM
DOOR MODE
TURN ON TAMPER ALARM
To turn on the tamper alarm feature, enter “setup” mode.
Press the star (*) key and then “6”. Mode LED will flash red.
Press “0” and then “2”. A long beep will sound. Mode LED will turn red.
Press “#” again to exit “setup” mode. Mode LED turns green.
TURN OFF TAMPER ALARM
To turn off the tamper alarm, enter “setup” mode.
Press the star (*) key and then “6”. Mode LED will flash red.
Press “0” and then “1”. A long beep will sound. Mode LED will turn red.
Press “#” again to exit “setup” mode. Mode LED turns green.
This feature allows a built-in buzzer to activate if the keypad is removed from the wall. The alarm will stop
automatically in 60 seconds or if the admin code is entered before the 60-second timeout.
FACTORY DEFAULT: OFF