Danfoss AKC 55 System Installation guide

Type
Installation guide
AKCESS System Manual RC.IU.B1.22 4/99.1 3 - 1
Chapter 3 Installing and Setting Up the Components
This section of the AKC 55 manual will explain, for each network component:
(1) Description and Identification (5) Network connections
(2) Mounting (6) Load connections
(3) Setting the component’s network address (7) Power connections
(4) Hardware Options (8) Inspection of the installed
component
Chapter 3 - 1 Installing an AKC 55 Controller
The AKC 55 is assembled from two circuit boards: the Central Processing Unit, or CPU (which includes
the display sub-assembly) and the Power Supply & Communications Board (PS/COMM).
The AKC 55 is available “packaged” two ways: (1) as a panel-mount for OEM installation, and (2) in a
box enclosure with a hinged door. Either package may be ordered with or without an LCD display.
3 - 2 System Manual RC.IU.B1.22 4/99.1 AKCESS
AKC 55 Addressing
The AKC 55’s in a network are addressed by setting two rotary switches (shown in the following
illustration) on the CPU board. There is a cut out on the lower left side of the CPU shield plate through
which the switches can be set with a small screwdriver. Each AKC 55 must have a unique address. The
host network must havean AKC 55 addressed “00." After the address is set or changed, power to the
unit must be interrupted and restored for the new address to take effect and be stored.
AKC 55 with Enclosure
Mounting Using the pre-drilled holes, mount the AKC 55 securely to a solid surface. Operating temperature must
be in the range from 32
o
F to 122
o
F, and relative humidity in the range from 0% to 95% (non-condensing).
Avoid mounting the unit where it could be subject to excessive vibration.
akc55box.dwg 2/99
AKCESS System Manual RC.IU.B1.22 4/99.1 3 - 3
Modem Installation
Install the modem inside the AKC 55 box, or choose a location for the modem close enough to an AKC
55 so that the 3 foot connecting power cable supplied with the modem can be used. Connect the modem
to the modem data port on the PS/COMM board. Then, connect the modem power cable to the PS/
COMM board terminals labeled “MODEM POWER” using the power cord supplied. (A modem can be
added after the initial installation, but only modems supplied by Danfoss can be used in an AKCESS
system.)
Telephone Line
Installation For best results, the telephone line used should be a dedicated voice grade two-wire central office line.
Bring the telephone cable to the modem location and terminate it to a standard RJ-11 jack. Then connect
the modem to the RJ-11 jack with the modular telephone cord supplied with your modem. If a PBX line
must be used, the PBX vendor should be consulted for proper wiring.
Ethernet Adapter
Connection There are two Danfoss ethernet adapter kits: COMM-E-120 and COMM-E-220, for 120 and 220 VAC
respectively. Connect the ethernet adapter (using one of the cables in the kit) to the serial port connector
on the bottom of the AKC 55 box. Then follow the instructions that accompany the adapter kit to
establish commuincations.
HEY! Enable your
AKC 55 battery,
or youll lose your
confi
g
uration!!
CPU Battery Enable
Before the AKC 55 is put in service, make sure that the BATTERY ENABLE Berg jumper is put in the
ON position. A clearly labeled opening is provided in the CPU shield so that the battery enable jumper
can be moved.
If the battery is not enabled, the controller will lose its configuration whenever the power is interrupted.
3 - 4 System Manual RC.IU.B1.22 4/99.1 AKCESS
Host Network
Cabling & Termination Connect the AKC 55 using RS-485 host network cable (3-conductor stranded shielded AWG 18) at the
Host Network Connection terminals on the PS/COMM board. Connect the shield to the “SHIELD” or
“GND” terminal
ONLY at the first AKC 55. At each controller between the first and last ones on the
network, wirenut the shields together so that the shield is continuous, and insulated from ground, for the
entire length of the network. Leave the shield loose at the last controller, but insulate it from ground.
If there is more than one AKC 55 in the host network, make sure that the termination jumpers are set in
the “OFF” position for all AKC 55’s in the host network except for the first and the last ones in the
physical “chain.” Make sure the termination jumpers for the first and last AKC 55’s are set to the
“ON” position.
The drawing immediately below should make clear that the correct setting of an AKC 55’s termination
jumpers does not depend on its address but rather on its physical location in the host network.
Remember, set
termination ON
for the first and
last AKC 55's,
and
OFF for all
the rest !!
AKCESS System Manual RC.IU.B1.22 4/99.1 3 - 5
I/O Network
Cabling & Termination Up to five I/O network cables can be connected to an AKC 55 at the terminals labeled “I/O Network”
on the PS/COMM board. There is no polarity to observe; connect the two signal wires to the terminals
labeled “A” and ”B”, and the cable shield to the terminal.
R
emem
b
er to
terminate the last board or
other node on each main
cable run, as we showed you
on
p
a
g
e 2-2 !
Power Wiring Power selection jumpers are located on the PS/COMM board. The unit is shipped with the jumpers
positioned for 220 VAC. Before connecting power, position the jumpers as shown in the illustration for
the appropriate supply voltage. Power connection is then made to the terminals labeled “POWER IN,”
observing the terminal labeling, where G = ground, N = neutral, and L = line. When the PS/COMM
board has power, its red LED labeled “POWER ON” will light.
3 - 6 System Manual RC.IU.B1.22 4/99.1 AKCESS
AKC 55 Installer
Final Inspection When an AKC 55 is completely installed, you will see:
First, the CPU side...
(1) The CPU shield is in place, secured by its six nylon cap nuts.
(2) The BATTERY ENABLE Berg jumper has been put in the ON position.
(3) The CPU STATUS LED is lighted. (See #6 below)
(4) The address is correctly set (00 for master, 01, 02, 03, etc. for other AKC 55’s).
Now, look at the PS/COMM board...
(5) The main power selector jumper (110 VAC-220 VAC) is correctly set.
(6) Power of the correct voltage is connected to the POWER IN terminals.
(7) The power LED is lighted.
(8) If a system modem is to be connected to this AKC 55, the modem is connected to the modem data
port by the cable furnished. Make sure that the modem has power as required.
(9) The RS 485 cable to other AKC 55’s in the host network is connected and if this is the first or last
AKC 55 in the host network, the termination jumper is in the “ON” position.
(10) All I/O cables are connected, and each main I/O run is terminated using one of the terminators
shipped with the AKC 55, and a terminator remains in place across each unused set of A & B
network connections on the PS/COMM board.
AKCESS System Manual RC.IU.B1.22 4/99.1 3 - 7
AKC 55 Addressing The AKC 55’s in a network are addressed by setting the two rotary switches on the CPU board. There
is a cut out on the lower left side of the CPU shield plate through which the switches can be set with a
small screwdriver. Each AKC 55 must have a unique address. The host network must have an AKC 55
addressed “00.”
CPU Battery Enable Before the AKC 55 is put in service, make sure that the BATTERY ENABLE Berg jumper is put in the
ON position. It is necessary to remove the metal CPU shield with the PS/COMM board attached, then
set the jumpers as shown in the following illustration. The jumper location is indicated in the drawing
with the shield and PS/COMM board attached.
If the battery is not enabled, the controller will lose its configuration if there is a power failure.
Installing an AKC 55
Panel Mount
Mounting The AKC 55 PM should be mounted through a solid control panel in an opening 10 inches wide by
12.5" high. To provide adequate ventilation for the AKC 55, insure that a minimum depth of 6" is
provided. Operating temperature must be in the range from 32
o
F to 122
o
F, and relative humidity in the
range from 0% to 95% (non-condensing). Locations subject to excessive vibration should be avoided.
3 - 8 System Manual RC.IU.B1.22 4/99.1 AKCESS
Modem Installation Choose a mounting location for the modem where neither it nor the ribbon cable connecting it to the PS/
COMM board is subject to interference from high voltage devices. Mount the modem using the
mounting plate provided with it. Connect the modem to the modem data port on the PS/COMM board
using the furnished ribbon cable. Connect the modem power cable to the modem and to the PS/COMM
board’s MODEM POWER terminals.
H
EY!
E
na
bl
e
your AKC 55
battery, or
youll lose your
configuration.
Telephone Line
Installation The telephone line used should be a dedicated voice grade two-wire central office line for best results.
Terminate the telephone line to an RJ-11 jack near the modem location, then connect the modem to the
RJ-11 jack with the modular phone cord furnished with your modem. If a PBX line must be used, the
PBX vendor should be consulted for proper wiring.
Ethernet Adapter
Connection There are two Danfoss ethernet adapter kits: COMM-E-120 and COMM-E-220, for 120 and 220 VAC
respectively. Connect the ethernet adapter (using one of the cables in the kit) to the AKC 55’s serial
port connector. Then follow the instructions that accompany the adapter kit to establish
commuincations.
AKCESS System Manual RC.IU.B1.22 4/99.1 3 - 9
Host Network
Cabling & Termination Connect the AKC 55 using RS-485 host network cable (3-conductor stranded shielded AWG 18) at the
Host Network Connection terminals on the PS/COMM board. Connect the shield to the “SHIELD” or
“GND” terminal ONLY at the first AKC 55. At each controller between the first and last ones on the
network, wirenut the shields together so that the shield is continuous, and insulated from ground, for the
entire length of the network. Leave the shield loose at the last controller, but insulate it from ground.
If there is more than one AKC 55 in the host network, make sure that the termination jumpers are set in
the “OFF” position for all AKC 55’s in the host network except for the first and the last ones in the
“chain.” Make sure the termination jumpers for the first and last AKC 55’s are set to the “ON”
position.
The drawing immediately below should make clear that the correct setting of an AKC 55’s termination
jumpers does not depend on its address but rather on its physical location in the host network.
Remember, set
termination ON
for the first and
last AKC 55's,
and
OFF for all
the rest !!
3 - 10 System Manual RC.IU.B1.22 4/99.1 AKCESS
Youve got to
terminate the last
board on every main
I/O cable run !
I/O Network
Cabling & Termination Up to five I/O network cables can be connected to an AKC 55 at the terminals labeled “I/O Network” on
the PS/COMM board. There is no polarity to observe; connect the two signal wires to the terminals
labeled”A” and “B”, and the cable shield to the terminal labeled “shield”.
Power Wiring Power selection jumpers are located on the PS/COMM board. The unit is shipped with the jumpers
positioned for 220 VAC. Before connecting power, position the jumpers as shown in the illustration for
the appropriate supply voltage. Power connection is then made to the terminals labeled “POWER IN,”
observing the terminal labeling, where G = ground, N = neutral, and L = line. (For 208-240 VAC service,
connect L1 & L2 to the “POWER IN” terminals labeled “L” & “N.”)
When the PS/COMM board has power, its red LED labeled “POWER ON” will light.
AKCESS System Manual RC.IU.B1.22 4/99.1 3 - 11
AKC 55 Installer
Final Inspection When an AKC 55 is completely installed, you will see:
First, the CPU side...
(1) The CPU shield is in place, secured by its six nylon cap nuts.
(2) The BATTERY ENABLE Berg jumper has been put in the ON position.
(3) The CPU STATUS LED is lighted. (See #6 beelow)
(4) The address is correctly set (00 for master, 01, 02, 03, etc. for other AKC 55’s).
Now, look at the PS/COMM board...
(5) The main power selector jumper (110 VAC-220 VAC) is correctly set.
(6) Power of the correct voltage is connected to the POWER IN terminals.
(7) The power LED is lighted.
(8) If this AKC 55 is address 00, and if the system includes a modem, the modem is connected to the
modem data port by the cable furnished. Make sure that the modem has power as required.
(9) The RS 485 cable to other AKC 55’s in the host network is connected and if this is the first or last
AKC 55 in the host network, the termination jumper is in the “ON” position.
(10) All I/O cables are connected, and each main I/O run is terminated using one of the terminators
shipped with the AKC 55, and a terminator remains in place across each unused set of A & B
network connections on the PS/COMM board.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11

Danfoss AKC 55 System Installation guide

Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI