12 Setup Guide RI.8A.L3.02 © Danfoss 02/2002 Override
P0 Optimisation
Principle The override function makes it possible for you to optimise the suction pressure so that it will be
adapted to the system’s actual load. During the optimisation data are collected that tell you
which refrigeration points are most heavily loaded.
The individual controllers handle the temperature control in the refrigeration appliances. Some
controllers control two, others three refrigeration points in the same appliance. The load and
operating condition of each refrigeration point are continuously uploaded to the gateway via the
data communication. The collected data are accumulated here and the ”most heavily loaded”
refrigeration point identified. An adaptation will now be made of the suction pressure so that the
air temperature at the refrigeration point is maintained. Only after a period of, say, 20 minutes,
or if the operating condition of the refrigeration point is changed (defrost, cutout, etc.) can
another refrigeration point be designated as the ”most heavily loaded one”.
It is the gateway that collects data from the refrigeration points and it is the gateway that
transmits an offset signal to the compressor control so that the suction pressure reference is
changed to suit the needs at the ”most heavily loaded” refrigeration point.
The set min./max. limits for the suction pressure will of course be observed.
The time during which a refrigeration point has been designated ”the most heavily loaded one”
will be summed up in a log (history) in the shape of minutes. These data can be presented in a
display containing ”the last 24 hours” and ”the last 168 hours (one week)”. The oldest values
will continuously be overwritten.
It will typically be the same pattern that is formed on the two charts, but if ”new ones” emerge
and differ from the rest this should be examined more closely.
The function can only be obtained with controllers from 1995 and later, i.e.: controllers types
AKC 114, 115 and 116 plus variants with indices A, B, D and F, AKC 121A/B and AKC 72A, as
well as a few AKC 14-16 controllers.
Gateway types AKA 243 and 244 with version 5.4 or newer (a gateway can control three
groups). Compressor control AKC 25H1 with version 1.32.
AKC 25H3 with version 1.1x.
AKC 25H5 with version 1.32.
Max. 60 refrigeration points (sections) in one group.
Max. three groups.
Data should max. be uploaded from 100 refrigeration points in one DANBUSS connection. Too
many will create too much traffic on the data communication.
Coming controllers:
The AKM programme must know the controllers that are used in the P0 optimisation. The code
number and software version for these controllers are described in a file named ”akctype.ini”.
This file is continuously updated at Danfoss.
If you install a new controller in the refrigerating system and the AKM programme does not
know this controller, it may be necessary to update the mentioned file. Please contact Danfoss.
System requirements