ICM Controls ICM334 Application/Install Guide

  • Hello! I am an AI chatbot trained to assist you with the ICM Controls ICM334 Application/Install Guide. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
Installation of the ICM334 shall be performed by trained technicians only. Adhere to all local and national electric codes.
Disconnect all power to the system before making any connections.
Caution!
• Line Voltage:120-600VAC
• Maximum Load Current:10A
• Control Voltage:18-30VAC
• Frequency:50-60Hz
• Operating Temperature:-40ºFto+140ºF(-40°Cto+60°C)
• Probes:
Temperature Sensors: P/NICM379
–Pressure transducer:P/NICM380
• Reversing Valve:24VACNominal
Specifications
• Heat Pump Override:24VACN.C.orN.O.
• Weight:12ounces(341grams)
Mounting:
– Surfacemountusing(2)#8screws
– TheICM334shouldbesurfacemountedtoacleanmetalorotherthermallyconductive
surfaceformaximumheatdissipation
– ItisrecommendedthattheICM334bemountedawayfromthecondenserexhaustair
inordertomaintainloweroperatingtemperatures
1.For non-heat pump applications,theheatpumpselectjumpermustbeintheDefault(N.O.)position,andtheREV. VALVE
terminalmustbeleftunconnected.
Connections for Air Conditioning Only
N.C.
C
Y1
Y2
REV. VALVE
P1&P2 BLK
HEAT
PUMP
N.O.
T AMBIENT
P1&P2 RED
P2 B.W.G.
P1 B.W.G.
Y1
Y2
T’STAT
24 VAC
COMMON
Installation, Operation & Application Guide
For more information on our complete range of American-made products – plus
wiring diagrams, troubleshooting tips and more, visit us at www.icmcontrols.com
ICM334
Head Pressure Control with
Optional Heat Pump Override
Regulates head pressure
via pressure input
1.Uptotwotransducerscanbeused,inwhichcasethecontrolwill
respondtothetransducerthatsensesthehighestpressure.
2.Installthepressuresensoronthedischargelinetransducertting.
3.InstalltheambienttemperaturesensorattheT AMBIENTterminals
andallowittomeasureoutdoorairtemperature.
4.Whenusingthetemperatureprobeinsteadofatransducer,install
thetemperatureprobeseveralbendsintothecondenser.Itcanbe
attachedtothe
U-bendorplacedbetweenthensintheupper1/3ofthecondenser.
Note:The response of the system can be ne-tuned by repositioning
the probe. Place the probe on the condenser where it is 100°F
when pressures are correct for best response.
Installing and Connecting the Sensors
With Pressure Transducers
2
RED
BLACK
PRESSURE TRANSDUCER
RED
BLACK
PRESSURE TRANSDUCER
1
BLUE
WHITE
GREEN
BLUE
WHITE
GREEN
N.C.
C
Y1
Y2
REV. VALVE
P1&P2 BLK
HEAT
PUMP
N.O.
T AMBIENT
P1&P2 RED
P2 B.W.G.
P1 B.W.G.
AMBIENT
TEMP
SENSOR
With Temperature Sensors
N.C.
C
Y1
Y2
REV. VALVE
P1&P2 BLK
HEAT
PUMP
N.O.
T AMBIENT
P1&P2 RED
P2 B.W.G.
P1 B.W.G.
TEMP
SENSOR
2
AMBIENT
TEMP
SENSOR
TEMP
SENSOR
1
Connections
1.Removepowerfromsystem.
2.Connect3-phaseinputwirestoLine1,Line2,Line3terminals.
3.Connectmotor(load)wirestoLoad1,Load2,andLoad3terminals.
4.Make24VACconnection,probeandHPconnections.
5.Verifywiringiscorrect.
6.Powerupsystemandcheckoperations.
L1
L2
L3
Motor
Fault Codes
Continuous On –Statusnormal
Continuous Off – Checkfor24VACpoweratY1orY2withrespecttoC
1 – Y1call,pressuretransducer1fault. Verify:sensorisconnectedtoP1,andthecorrecttransduceroutputusingappendixB.
2 – Y2call,pressuretransducer2fault. Verify:sensorisconnectedtoP2,andthecorrecttransduceroutputusingappendixB.
3 – Ambienttemperaturesensornotconnectedoropen.
Troubleshooting
Symptom Problem
Unitfailstostart UsinganACvoltmeter,measurethevoltagebetweenY1orY2andCterminals–itshouldread24volts.Measurethelinevoltage
betweenLINE1andLINE2toconrmthatlinevoltageispresent
Thefuseisblownand/orsignsofdamageontheunit Theunithasbeenmiswiredandmaybepermanentlydamaged.
FanONconstantly Iflightsareashingthennoprobeisconnectedorprobemalfunctionhasoccurred.SeeFaultCodesandmeasuretheappropriate
sensor.
CheckwiringofREV.VALVE/heatpumpjumper.
Measuringthethermistor-Disconnecttheambienttemperaturesensoranduseanohmmetertomeasuretheresistancebetween
thewires,itshouldmatchAppendixA.
Measuringthepressuretransducer-Withpowerappliedtothecontrol.UseavoltmetertomeasureDCvoltagebetweenP1&P2
BLKandP1B.W.G(orP2B.W.G),itshouldmatchAppendixB.
Thehighpressureswitchtripsoff SeeUnitfailstostartabove
Checkthesetpointandreduceitifneeded
1.The REV. VALVE terminal accepts the 24 VAC signal from the reversing valve holding coil.
MakeaparallelconnectionfromthereversingvalvetotheREV. VALVE terminal.
 Note:Do not apply a voltage higher than 30 VAC to the REV. VALVE terminal.
2.IftheHeat PumpisintheHeatingmodeandthereversingvalveisenergized,thentheHeat Pump Select
jumpermustbeintheDefault(N.O.)position.
3.IftheHeat PumpisintheHeatingmodeandthereversingvalveisnotenergized,thentheHeat Pump
SelectjumpermustbeintheN.C.position.
Connections for Heat Pump Systems
N.O.
N.C.
N.C.
C
Y1
Y2
REV. VALVE
P1&P2 BLK
HEAT
PUMP
N.O.
T AMBIENT
P1&P2 RED
P2
B.W.G.
P1 B.W.G.
Y1
Y2
O/B
T’STAT
24 VAC
COMMON
7313 William Barry Blvd., North Syracuse, NY 13212
(Toll Free) 800-365-5525 (Phone) 315-233-5266 (Fax) 315-233-5276
www.icmcontrols.com
LIAF208-1
ONE-YEAR LIMITED WARRANTY
TheSellerwarrantsitsproductsagainstdefectsinmaterialorworkmanshipforaperiodofone(1)yearfromthedateofmanufacture.
TheliabilityoftheSellerislimited,atitsoption,torepair,replaceorissueanon-casecreditforthepurchasepricesofthegoods
whichareprovidedtobedefective.Thewarrantyandremediessetforthhereindonotapplytoanygoodsorpartsthereofwhich
havebeensubjectedtomisuseincludinganyuseorapplicationinviolationoftheSeller’sinstructions,neglect,tampering,improper
storage,incorrectinstallationorservicingnotperformedbytheSeller.InordertopermittheSellertoproperlyadministerthewarranty,
theBuyershall:1)NotifytheSellerpromptlyofanyclaim,submittingdatecodeinformationoranyotherpertinentdataasrequested
bytheSeller.2)PermittheSellertoinspectandtesttheproductclaimedtobedefective.Itemsclaimedtobedefectiveandare
determinedbySellertobenon-defectivearesubjecttoa$30.00perhourinspectionfee.ThiswarrantyconstitutestheSeller’ssole
liabilityhereunderandisinlieuofanyotherwarrantyexpressed,impliedorstatutory.Unlessotherwisestatedinwriting,Sellermakes
nowarrantythatthegoodsdepictedordescribedhereinaretforanyparticularpurpose.
Mode of Operations
AfterproperlyinstallingtheICM334,thethreephasemotorswitchwillcontrolaconnectedmotor.Usingatemperaturesensorandtwopressuresensors,thedevicewillmonitortheambient
temperatureandpressureinsidethesystem.ThemonitorwillbeenergizedwhenthereisaYcall.
Whentheambienttemperatureisabove50°F(10°C),themotorwillbeenergizedcontinuously.Whentheambienttemperatureisbelow50°F,thepressuresensorisusedtodetermine
whetherthemotoristurnedonoroff.Whenthepressureis15psibelowthesetpressure,accordingtothehighestreadingofthetwopressuresensors,themotorwillbeturnedoff.Whenthe
pressureis15psiabovethesetpressure,accordingtothehighestreadingofthetwopressuresensors,themotorwillbeturnedon.
WhenthereisanewYcalltheloadwillenergizefor10seconds(hardstart).
Appendix A
Temperature vs. Probe Resistance
Appendix B
Pressure (psig) Voltage (Vdc)
0 0.5
50 0.9
100 1.3
150 1.7
200 2.1
250 2.5
300 2.9
350 3.3
400 3.7
450 4.1
500 4.5
Pressure vs. Voltage
Appendix
/