Fault Codes
Continuous On –Statusnormal
Continuous Off – Checkfor24VACpoweratY1orY2withrespecttoC
1 – Y1call,pressuretransducer1fault. Verify:sensorisconnectedtoP1,andthecorrecttransduceroutputusingappendixB.
2 – Y2call,pressuretransducer2fault. Verify:sensorisconnectedtoP2,andthecorrecttransduceroutputusingappendixB.
3 – Ambienttemperaturesensornotconnectedoropen.
Troubleshooting
Symptom Problem
Unitfailstostart UsinganACvoltmeter,measurethevoltagebetweenY1orY2andCterminals–itshouldread24volts.Measurethelinevoltage
betweenLINE1andLINE2toconrmthatlinevoltageispresent
Thefuseisblownand/orsignsofdamageontheunit Theunithasbeenmiswiredandmaybepermanentlydamaged.
FanONconstantly Iflightsareashingthennoprobeisconnectedorprobemalfunctionhasoccurred.SeeFaultCodesandmeasuretheappropriate
sensor.
CheckwiringofREV.VALVE/heatpumpjumper.
Measuringthethermistor-Disconnecttheambienttemperaturesensoranduseanohmmetertomeasuretheresistancebetween
thewires,itshouldmatchAppendixA.
Measuringthepressuretransducer-Withpowerappliedtothecontrol.UseavoltmetertomeasureDCvoltagebetweenP1&P2
BLKandP1B.W.G(orP2B.W.G),itshouldmatchAppendixB.
Thehighpressureswitchtripsoff SeeUnitfailstostartabove
Checkthesetpointandreduceitifneeded
1.The REV. VALVE terminal accepts the 24 VAC signal from the reversing valve holding coil.
MakeaparallelconnectionfromthereversingvalvetotheREV. VALVE terminal.
Note:Do not apply a voltage higher than 30 VAC to the REV. VALVE terminal.
2.IftheHeat PumpisintheHeatingmodeandthereversingvalveisenergized,thentheHeat Pump Select
jumpermustbeintheDefault(N.O.)position.
3.IftheHeat PumpisintheHeatingmodeandthereversingvalveisnotenergized,thentheHeat Pump
SelectjumpermustbeintheN.C.position.
Connections for Heat Pump Systems
N.O.
N.C.
N.C.
C
Y1
Y2
REV. VALVE
P1&P2 BLK
HEAT
PUMP
N.O.
T AMBIENT
P1&P2 RED
P2
B.W.G.
P1 B.W.G.
Y1
Y2
O/B
T’STAT
24 VAC
COMMON
7313 William Barry Blvd., North Syracuse, NY 13212
(Toll Free) 800-365-5525 (Phone) 315-233-5266 (Fax) 315-233-5276
www.icmcontrols.com
LIAF208-1
ONE-YEAR LIMITED WARRANTY
TheSellerwarrantsitsproductsagainstdefectsinmaterialorworkmanshipforaperiodofone(1)yearfromthedateofmanufacture.
TheliabilityoftheSellerislimited,atitsoption,torepair,replaceorissueanon-casecreditforthepurchasepricesofthegoods
whichareprovidedtobedefective.Thewarrantyandremediessetforthhereindonotapplytoanygoodsorpartsthereofwhich
havebeensubjectedtomisuseincludinganyuseorapplicationinviolationoftheSeller’sinstructions,neglect,tampering,improper
storage,incorrectinstallationorservicingnotperformedbytheSeller.InordertopermittheSellertoproperlyadministerthewarranty,
theBuyershall:1)NotifytheSellerpromptlyofanyclaim,submittingdatecodeinformationoranyotherpertinentdataasrequested
bytheSeller.2)PermittheSellertoinspectandtesttheproductclaimedtobedefective.Itemsclaimedtobedefectiveandare
determinedbySellertobenon-defectivearesubjecttoa$30.00perhourinspectionfee.ThiswarrantyconstitutestheSeller’ssole
liabilityhereunderandisinlieuofanyotherwarrantyexpressed,impliedorstatutory.Unlessotherwisestatedinwriting,Sellermakes
nowarrantythatthegoodsdepictedordescribedhereinaretforanyparticularpurpose.
Mode of Operations
AfterproperlyinstallingtheICM334,thethreephasemotorswitchwillcontrolaconnectedmotor.Usingatemperaturesensorandtwopressuresensors,thedevicewillmonitortheambient
temperatureandpressureinsidethesystem.ThemonitorwillbeenergizedwhenthereisaYcall.
Whentheambienttemperatureisabove50°F(10°C),themotorwillbeenergizedcontinuously.Whentheambienttemperatureisbelow50°F,thepressuresensorisusedtodetermine
whetherthemotoristurnedonoroff.Whenthepressureis15psibelowthesetpressure,accordingtothehighestreadingofthetwopressuresensors,themotorwillbeturnedoff.Whenthe
pressureis15psiabovethesetpressure,accordingtothehighestreadingofthetwopressuresensors,themotorwillbeturnedon.
WhenthereisanewYcalltheloadwillenergizefor10seconds(hardstart).
Appendix A
Temperature vs. Probe Resistance
Appendix B
Pressure (psig) Voltage (Vdc)
0 0.5
50 0.9
100 1.3
150 1.7
200 2.1
250 2.5
300 2.9
350 3.3
400 3.7
450 4.1
500 4.5
Pressure vs. Voltage