  • Hello! I am an AI chatbot trained to assist you with the ICM Controls ICM333 Application/Install Guide. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
ICM333
Head Pressure Control with
Optional Heat Pump Override
Regulates head pressure via
temperature or pressure input
Installation, Operation & Application Guide
For more information on our complete range of American-made
products – plus wiring diagrams, troubleshooting tips and more,
visit us at www.icmcontrols.com
Caution!
Installation of the ICM333 shall be performed by trained technicians only. Adhere to all local and national electric codes. Disconnect all power to the system before making any connections.
• Line voltage:120,208,240,277,480and600VAC
• Control voltage:18-30VAC
• Frequency:50-60Hz
• Operating temperature:-40ºFto+176ºF(-40°Cto+75°C)
• Probes: –Temperature:Thermistor,10Kohmat77°F(25°C)
 –Pressure:ICM380(orderedseparately)
• Heat pump override:24VACN.C.orN.O.
• Weight:12ounces(341grams)
Specifications
Note: TheICM333shouldbeappliedtomotorsandequipmentthathavebeendesignatedbytheir
respectivemanufacturersascapableofbeingspeedcontrolled.
• Mounting:
– Surfacemountusing(2)#8screws
– TheICM333shouldbesurfacemountedtoacleanmetalorotherthermallyconductivesurface
formaximumheatdissipation
– ItisrecommendedthattheICM333bemountedawayfromthecondenserexhaustairinorderto
maintainloweroperatingtemperatures
LIAF010-1
7313 William Barry Blvd., North Syracuse, NY 13212
(Toll Free) 800-365-5525 (Phone) 315-233-5266 (Fax) 315-233-5276
www.icmcontrols.com
ONE-YEAR LIMITED WARRANTY
TheSellerwarrantsitsproductsagainstdefectsinmaterialorworkmanshipforaperiodofone(1)
yearfromthedateofmanufacture.TheliabilityoftheSellerislimited,atitsoption,torepair,replace
orissueanon-casecreditforthepurchasepricesofthegoodswhichareprovidedtobedefective.
Thewarrantyandremediessetforthhereindonotapplytoanygoodsorpartsthereofwhichhave
beensubjectedtomisuseincludinganyuseorapplicationinviolationoftheSeller’sinstructions,
neglect,tampering,improperstorage,incorrectinstallationorservicingnotperformedbytheSeller.
InordertopermittheSellertoproperlyadministerthewarranty,theBuyershall:1)NotifytheSeller
promptlyofanyclaim,submittingdatecodeinformationoranyotherpertinentdataasrequestedby
theSeller.2)PermittheSellertoinspectandtesttheproductclaimedtobedefective.Itemsclaimed
tobedefectiveandaredeterminedbySellertobenon-defectivearesubjecttoa$30.00perhour
inspectionfee.ThiswarrantyconstitutestheSeller’ssoleliabilityhereunderandisinlieuofanyother
warrantyexpressed,impliedorstatutory.Unlessotherwisestatedinwriting,Sellermakesnowarranty
thatthegoodsdepictedordescribedhereinaretforanyparticularpurpose.
Example
1.Onlyoneprobetypecanbeusedatatime,temperatureorpressure.Uptotwo
probesofakindcanbeusedinwhichcasethecontrolwillrespondtotheprobe
thatsensesthehighesttemperatureorpressure.
2.AtypicalinstallationisshowninAppendix.Thetemperatureprobecanbe
attachedtotheU-bend.Usetheprovidedthermo-tapetosecuretheprobetothe
placeofattachment.
3.Whenusingapressureprobe,installitonthedischargelinetransducertting.
4.TemperatureandPressureprobesareconnectedtoICM333asshownin
respectivewiringdiagramsbelow.
Installing and Connecting the Probe
BLUE
WHITE
GREEN
RED
BLACK
PRESSURE TRANSDUCER
2
BLUE
WHITE
GREEN
RED
BLACK
PRESSURE TRANSDUCER
1
TEMPERATURE
PROBE
1
TEMPERATURE
PROBE
2
Connections for ICM333 at 120/208/240/277 VAC
1.Removepowerfromsystem.
2.FieldinstallawirefromLine 1wiretoLine 1terminal.
3.CutLine 2wire;afxmotorsidetoMotor 2terminal
andlinesidetoLine 2terminal.
4.Make24VACandtemperatureprobeconnections.
5.Verifywiringiscorrect.
6.Powerupsystemandcheckoperation.
Typical
condenser fan
PSC
Fan
Motor
Run
Capacitor
120/208/240/277
VAC
PSC
Fan
Motor
Run
Capacitor
Field
Installed
Wire
Line
1
120/277
VAC
Line
2
Motor
2
120/208/240/277
VAC
Connections for Heat Pump System at 120/208/240/277 VAC
1.Removepowerfromsystem.
2.FieldinstallawirefromLine 1wiretoLine 1terminal.
3.CutLine 2wire;afxthecommonfromthedefrost
board’sfanrelaytotheMotor 2terminalandtheLine
fromthecontactortotheLine 2terminal.
4.Make24VAC,probeandHPconnections.
5.Verifywiringiscorrect.
6.Powerupsystemandcheckoperation.
Field
Installed
Wire
PSC
Fan
Motor
Run
Capacitor
Fan
Relay
COM NC
Defrost Board
120/208/240/277
VAC
Line
1
120/240/277
VAC
Line
2
Motor
2
Connections for Heat Pump System at 480/600 VAC
1.Removepowerfromsystem.
2.FieldinstallawirefromLine 1wiretoLine 1terminal.
3.CutLine 2wire;afxthecommonfromthedefrost
board’sfanrelaytotheMotor 2terminalandtheLine
fromthecontactortotheLine 2terminal.
4.Make24VAC,probeandHPconnections.
5.Verifywiringiscorrect.
6.Powerupsystemandcheckoperation.
Connections for ICM333 at 480/600 VAC
1.Removepowerfromsystem.
2.FieldinstallawirefromLine 1wiretoLine 1terminal.
3.CutLine 2wire;afxmotorsidetoMotor 2terminal
andlinesidetoLine 2terminal.
4.Make24VACandtemperatureprobeconnections.
5.Verifywiringiscorrect.
6.Powerupsystemandcheckoperation.
Typical
condenser fan
PSC
Fan
Motor
Run
Capacitor
Line
1
Line
2
Motor
2
Field
Installed
Wire
PSC
Fan
Motor
Run
Capacitor
Line
1
Line
2
Motor
2
Field
Installed
Wire
PSC
Fan
Motor
Run
Capacitor
Fan
Relay
COM NC
Defrost Board
DuringtheHard Startmode,fullvoltageisappliedtothemotorduringstartuptoovercomewindmillingandtolubricatethebearings.
Thepositionofthehardstartdialdeterminesthetimeperiodofthehardstartmode.Thedialcanbeadjustedbetween0.2secondsandapproximately4seconds.
Setthehardstartdialaccordingtothetypeofmotoryouhave.Ifyouhaveaball bearing motor,setthehardstartdialtotheMINposition.Ifyouhaveasleeve bearing motor,setthe
hardstartdialtothemiddleofthesleevebearingrange.
Afteryoubeginattherecommendedsetting,youcannetunethehardstarttimewithintherecommendedrangeforthetypeofmotoryouhave.
Itisrecommendedthatyouusetheminimumpossiblehardstarttimetoavoidblowingtoomuchcoldairoverthecondenser.
Thehardstartmodeappliesfullvoltagetothemotorforthesettimeperiod.Afterwards,themotorspeedisdictatedbythetemperaturesensor(s).
Setting the Hard Start Speed
Thecutoutspeeddialadjuststhemotorvoltagerange.Setthecutoutvoltagedialaccordingtothetypeofmotoryouhave.
Sleeve Bearing Motors: Setthecutoutspeeddialtothemiddleofthesleevebearingrange.Inthisrange,themotorcanrundownapproximately40-50%of
thefulllinevoltage,whichallowssufcientRPMsforcoolingandlubrication.
CAUTION!:
Withsleevebearingmotors,itisimportantnottoadjustoutsidethesleevebearingrangeorbearingfailuremayresult.
Ball Bearing Motors:SetthecutoutspeeddialtotheMINpositionintheballbearingrange.Thispositionoffersthegreatestrangeofspeedcontrol.Atthe
MINsettingthemotorcanrundowntoapproximately20-30%ofthefulllinevoltage.
Note:Afterstartingattherecommendedsettingsforeithersleeveorballbearingmotors,youcannetunethecutoutspeedtoachievethedesiredresults.
Setting the Cutout Speed
Mode of Operations
Whenusingtemperatureprobes,thecontrolwillmaintaincondensertemperaturebetween7°Faboveand7°FbelowdialedTemperatureSetpoint.ThedialTemperatureSetpointrangeis70°Fto140°F
Whenusingpressureprobes,thecontrolwillmaintaincondenserpressurebetween20psigaboveand20psigbelowdialedPressureSetpoint.ThedialPressureSetpointrangeis35psigto465psig.
Theisnocorrelationbetweendialtemperatureandpressurescalesonthecontrol
Whenthemotorstartsrunningitwillhardstartforthelengthoftimedictatedbythehardstartdialsetting.Afterthehardstarttimehaselapsed,themotorspeediscontrolledbytheprobereading,temperatureor
pressure.Thegreenlightturnsonwhenthemotorrunsatfullspeed.
Asthesensedtemperature/pressuredecreases,theoutputvoltagedecreases.Theyellowlightturnsonduringmotorvariablespeed.Theoutputvoltagemaydecreasetothedeterminedcutoutspeeddictatedby
thecutoutspeeddial.Uponreachingthecutoutspeedsetting,theoutputvoltagegoestozerovolts.Theyellowlightturnsoff.
Appendix BAppendix A
°C °F Resistance (KΩ)
0° 32° 32.7
5° 41° 25.4
10° 50° 19.9
15° 59° 15.7
20° 68° 12.5
25° 77° 10.0
30° 86° 8.1
35° 95° 6.5
40° 104° 5.3
45° 113° 4.4
50° 122° 3.6
Pressure
(psig)
Voltage
(Vdc)
0 0.5
50 0.9
100 1.3
150 1.7
200 2.1
250 2.5
300 2.9
350 3.3
400 3.7
450 4.1
500 4.5
Temperature vs. Probe Resistance Pressure vs. Voltage
1.TheHeat Pumpterminalsacceptthe24VACsignalfromthereversingvalveholdingcoil.Makeaparallel
connectionfromthereversingvalvetotheHPterminals.
 Note:Do not apply a voltage higher than 30 VAC to the HP terminals.
2.IftheHeat PumpisintheHeatingmodeandthereversingvalveisenergized,then
theHeat Pump SelectjumpermustbeintheDefault(N.O.)position.
3.IftheHeat PumpisintheHeatingmodeandthereversingvalveisnotenergized,
thentheHeat Pump SelectjumpermustbeintheN.C.position.
N.O.
N.C.
Connections for Heat Pump Systems
Troubleshooting
Symptom Problem
Unitfailstostart UsinganACvoltmeter,measurethevoltagebetweenthe24VACterminals.Itshouldreadapproximately24volts.MeasurethelinevoltagebetweenLINE1andLINE2to
conrmthatlinevoltageispresent.
Iflightsareashingalternativelythennoprobeisconnectedormalfunctionprobe.
Whenusingatemperatureprobe,disconnectitanduseanohmmetertomeasuretheresistancebetweenthewires.ItshouldmatchthechartinAppendixA.
Whenusingapressureprobe,withpowerappliedtothecontroluseavoltmetertomeasurevoltsDCbetweenCOMMandP1orP2,wherethewireisconnected.Thereading
shouldbeaccordingtothechartinAppendixB.
Thefuseisblownand/orsignsof
damageontheunit
Theunithasbeenmiswiredandmaybepermanentlydamaged.
ThefancyclesfromONtoOFF
withlittleornospeedmodulation
Reducehard startstettingtominimumneededtoacceleratethefan.Excessivehardstartcauseslargepressuredropsbyrunningtoomuchcoldairoverthecondenser.
Shouldthecyclingpersist,relocatethetemperatureprobeupthecondensertoincreasesensitivitytotemperaturechangeand/oradjustthetemperaturesetpoint.
Thehighpressureswitchtripsoff SeeUnitfailstostartabove
Checkthesetpointandreduceitifneeded
1.For non-heat pump applications,theheatpumpselectjumpermustbeintheDefault(N.O.)position,andtheHPterminalsmustbeleftunconnected.
2.SettheCutoutSpeedandtheHardStartTimetotheappropriatepositionsforthetypeofmotoryouhave(seebelow).
Connections for Air Conditioning Only
ICM333 Typical Installation
Condenser
Sensor
Sensor
Sensor
ICM333
canmonitor
twocondensers
Motor
1
Motor
2
ReversingValvefor
HeatPump
T-Stat
Control
Transformer
Line2
LineVoltage
Terminalto
beusedfor
480/600VAC
Line1
/