Mode of Operations
Whenusingatemperatureprobe,thecontrolwillmaintaincondensertemperaturebetween7°Fabove
and7°FbelowdialedTemperatureSetpoint.ThedialTemperatureSetpointrangeis70°Fto140°F.
Whenusingapressureprobe,thecontrolwillmaintaincondenserpressurebetween20psigaboveand
20psigbelowdialedPressureSetpoint.ThedialPressureSetpointrangeis35psigto465psig.
Theisnocorrelationbetweendialtemperatureandpressurescalesonthecontrol.
Whenthemotorstartsrunningitwillhard startforthelengthoftimedictatedbythehard startdial
setting.Afterthehard starttimehaselapsed,themotorspeediscontrolledbytheprobereading,
temperatureorpressure.Thegreenlightturnsonwhenthemotorrunsatfullspeed.
Asthesensedtemperature/pressuredecreases,theoutputvoltagedecreases.Theyellowlightturnson
duringmotorvariablespeed.Theoutputvoltagemaydecreasetotheminimumvoltagedictatedbythe
cutout speeddial.Astemperature/pressuredecreasesfurther,theoutputvoltagegoestozerovolts.
Theyellowlightturnsoff.
Thecutoutspeeddialadjuststhemotorvoltagerange.Setthecutout
voltagedialaccordingtothetypeofmotoryouhave.
Sleeve Bearing Motors: Setthecutoutspeeddialtothemiddleof
thesleevebearingrange.Inthisrange,
themotorcanrundownapproximately40-
50%ofthefulllinevoltage,whichallows
sufcientRPMsforcoolingandlubrication.
CAUTION!:
Withsleevebearingmotors,itisimportantnotto
adjustoutsidethesleevebearingrangeorbearingfailuremayresult.
Ball Bearing Motors:SetthecutoutspeeddialtotheMINpositionintheballbearingrange.This
positionoffersthegreatestrangeofspeedcontrol.AttheMINsettingthemotor
canrundowntoapproximately20-30%ofthefulllinevoltage.
Note:Afterstartingattherecommendedsettingsforeithersleeveorballbearingmotors,youcanne
tunethecutoutspeedtoachievethedesiredresults.
Setting the Cutout Speed
DuringtheHard Startmode,fullvoltageisappliedtothemotor
duringstartuptoovercomewindmillingandtolubricatethebearings.
Thepositionofthehardstartdialdeterminesthetimeperiodofthe
hardstartmode.Thedialcanbeadjustedbetween0.2secondsand
approximately4seconds.
Setthehardstartdialaccordingtothetypeofmotoryouhave.If
youhaveaball bearing motor,setthehardstartdialtotheMIN
position.Ifyouhaveasleeve bearing motor,setthehardstartdial
tothemiddleofthesleevebearingrange.
Afteryoubeginattherecommendedsetting,youcannetunethehardstarttimewithinthe
recommendedrangeforthetypeofmotoryouhave.
Itisrecommendedthatyouusetheminimumpossiblehardstarttimetoavoidblowingtoomuchcoldair
overthecondenser.
Thehardstartmodeappliesfullvoltagetothemotorforthesettimeperiod.Afterwards,themotorspeed
isdictatedbythetemperature/pressuresensor.
Setting the Hard Start Speed
Appendix A
°C °F Resistance (KΩ)
0° 32° 32.7
5° 41° 25.4
10° 50° 19.9
15° 59° 15.7
20° 68° 12.5
25° 77° 10.0
30° 86° 8.1
35° 95° 6.5
40° 104° 5.3
45° 113° 4.4
50° 122° 3.6
Temperature vs. Probe Resistance
Appendix B
Pressure (psig) Voltage (Vdc)
0 0.5
50 0.9
100 1.3
150 1.7
200 2.1
250 2.5
300 2.9
350 3.3
400 3.7
450 4.1
500 4.5
Pressure vs. Voltage
ICM330 Typical Installation
Condenser
Sensor
Sensor
ReversingValveforHeat
Pump
T-Stat
Control
Transformer
Terminaltobe
usedfor480VAC
Line1
Line2
LineVoltage Motor1
Motor2
Symptom Problem
Unitfailstostart UsinganACvoltmeter,measurethevoltagebetweenthe24VACterminals.It
shouldreadapproximately24volts.
MeasurethelinevoltagebetweenLINE1andLINE2toconrmthatline
voltageispresent.Checkwiringtothefanmotor.
Iflightsareashingalternativelythennoprobeisconnectedormalfunctioning
probe.
Whenusingatemperatureprobe,disconnectitanduseanohmmeterto
measuretheresistancebetweenthewires.Itshouldmatchthechartin
AppendixA.
Whenusingapressureprobe,withpowerappliedtothecontrolusea
voltmetertomeasurevoltsDCbetweenGNDandVout.Thereadingshould
beaccordingtothechartinAppendixB.
Thefuseisblownand/
orsignsofdamageon
theunit
Theunithasbeenmiswiredandmaybepermanentlydamaged.
Thefancyclesfrom
ONtoOFFwith
littleornospeed
modulation
Reducehard startstettingtominimumneededtoacceleratethefanmotor.
Excessivehard startcauseslargepressuredropsbyrunningtoomuchcold
airoverthecondenser.
Reducecutoutsettingtominimumneededforthemotorinuse.
Shouldthecyclingpersist,relocatethetemperatureprobeupthecondenser
toincreasesensitivitytotemperaturechangeand/oradjustthetemperature
setpoint.
Thehighpressure
switchtripsoff
See“Unitfailstostart”above
Checkthesetpointandreduceitifneeded
Troubleshooting
1.TheHeat Pumpterminalsacceptthe24VACsignalfromthereversingvalveholdingcoil.Makea
parallelconnectionfromthereversingvalvetotheHEAT PUMPterminals.
Note:Do not apply a voltage higher than 30 VAC to the HEAT PUMP terminals.
2.IftheHeat PumpisintheHeatingmodeandthereversingvalve
isenergized,thentheHeat Pump Selectjumpermustbeinthe
Default(N.O.)position.
3.IftheHeat PumpisintheHeatingmodeandthereversingvalveisnot
energized,thentheHeat Pump SelectjumpermustbeintheN.C.position.
Connections for Heat Pump Systems
N.O.
N.C.
LIAF069-1
7313 William Barry Blvd., North Syracuse, NY 13212
(Toll Free) 800-365-5525 (Phone) 315-233-5266 (Fax) 315-233-5276
www.icmcontrols.com
ONE-YEAR LIMITED WARRANTY
TheSellerwarrantsitsproductsagainstdefectsinmaterialorworkmanshipforaperiodofone(1)year
fromthedateofmanufacture.TheliabilityoftheSellerislimited,atitsoption,torepair,replaceorissue
anon-casecreditforthepurchasepricesofthegoodswhichareprovidedtobedefective.Thewarranty
andremediessetforthhereindonotapplytoanygoodsorpartsthereofwhichhavebeensubjected
tomisuseincludinganyuseorapplicationinviolationoftheSeller’sinstructions,neglect,tampering,
improperstorage,incorrectinstallationorservicingnotperformedbytheSeller.Inordertopermitthe
Sellertoproperlyadministerthewarranty,theBuyershall:1)NotifytheSellerpromptlyofanyclaim,
submittingdatecodeinformationoranyotherpertinentdataasrequestedbytheSeller.2)Permitthe
Sellertoinspectandtesttheproductclaimedtobedefective.Itemsclaimedtobedefectiveandare