Litetronics PRC Series LED Light Panel Retrofit User manual

Type
User manual
WHAT COMES IN THE BOX
2 Mounting rails
2 Side rails
1 LED Light Panel Retrofit
4 Self tapping screws
Installation Instructions
2 Safety cables
1 Quick Connect
1 Luminaire label
LED Light Panel Retrofit (C-Series)
Installation Instructions
PRC-Series | 2’ x 2’, 2’ x 4’ & 1’ x 4
TOOLS NEEDED
Screwdriver or power drill
SAFETY INSTRUCTIONS AND WARNINGS
WARNINGS
Risk of fire or electric shock. LED Light Panel Retrofit kit installation requires knowledge of luminaires electrical system. If not
qualified, do not attempt installation. Contact a qualified electrician. Luminaire wiring and electrical parts may be damaged
when drilling for installation of retrofit kit. Check for enclosed wiring and components. Do not make or alter any open holes in
the enclosure of wiring or electrical components during kit installation.
Install this kit only in luminaires that have the construction features and dimensions shown in the photographs and/or drawings
and where the input rating of the retrofit kit does not exceed the input rating of the luminaire. Only those open holdes indicated
in the photographs and/or drawings may be made or altered as a result of kit installation. Do not leave any other open holes in
an enclosure of wiring or electrical components.
To prevent wiring damage or abrasion, do not expose wiring to edges of sheet metal or other sharp objects.
This LED Light Panel Retrofit kit shall only be installed into a UL/C-UL listed Fluorescent Recessed, Type IC or Non-IC,
listed luminaire with a steel enclosure.
Risk of fire or electric shock. The electrical rating of these products are120-277 Vac, the installer must determine whether they
have 120-277 V at the luminaire before installation.
Risk of fire or electric shock. Install this kit only in the luminaires that have the construction features and dimensions shown in
the photographs and/or drawings.
Risk of fire or electric shock. Luminaire wiring and electrical parts may be damaged when drilling for installation of LED retrofit
kit. Check for enclosed wiring and components.
DISCONNECT SAFETY INSTRUCTIONS:
This is a current rated device. Use in applications involving amperage beyond its rating can be dangerous and cause electrical
fires. See note on this page for allowable current and voltage levels and do not exceed those levels.
Never remove wires from product as contact with electricity can cause serious injury or death. Shut off power at the circuit
breaker or remove fuse when installing this product.
Improperly installed electrical wiring can be dangerous and cause electrical fires. This product must be used
in accordance with the current rating and wire sizes listed.
COPPER to COPPER ONLY. Do not use on Aluminum. Temperature rating: 105° C (221° F) maximum. Flame Rated UL94V-0.
Installation Instruction
General Wiring Diagram
WARNING
To reduce the risk of death, personal injury or property damage from fire, electric shock, falling parts, cuts/abrasions,
and other hazards read all warnings and instructions included with and on the fixture box and all fixture labels.
Before installing, servicing, or performing routine maintenance upon this equipment, follow these general precautions.
Commercial installation, service and maintenance of luminaires should be performed by a qualified licensed electrician.
For the installation: If you are unsure about the installation or maintenance of the luminaires, consult a qualified
licensed electrician and check your local electrical code.
To prevent wiring damage or abrasion, do not expose wiring to edges of sheet metal or other sharp objects.
Do not make or alter any open holes in an enclosure of wiring or electrical components during kit installation.
WARNING
Turn off electrical power at fuse or circuit breaker box before wiring fixture to the power supply.
Turn off the power when you perform any maintenance.
Verify that supply voltage is correct by comparing it with the luminaire label information.
All wiring connections should be capped with UL approved wire connectors.
CAUTION
Avoid direct eye exposure to the light source while it is on.
Account for small parts and destroy packing material, as these may be hazardous to children.
NOTICE:
NOTICE:
Risk of burn. Disconnect power and allow fixture to cool befor changing bulb or handing fixture.
Green ground screw provided in proper location.Do not relocate.
Minimum 90° supply conductors.
NOTICE: Specifications and dimensions subject to change without notice.
NOTICE: Suitable for Dry or Damp location, Type IC
120-277v
Black(Line)
White(Neutral)
Green(Grd)
Purple(Dim+)
Grey(Dim-)
Blue(-)
Red(+)
Dimming wire
to 0-10v IEC
compliant control
Lead wire to
LED load
If you have an interest in this product,please feel free to contact the email:[email protected]
If you have an interest in the other product,please visit the web www.designlights.org/qpl.
Search by Keyword : ever-tie
A
B
C
D
A: End Plates 2pcs
B: Side Plates 2pcs
C:Door Assembly body 1pcs
D:Self-tapping screws 4pcs
INSTALLATION PROCEDURE
READ ALL INSTRUCTIONS BEFORE BEGINNING INSTALLATION
Preparation
1. Turn off power at the electrical panel.
2. Remove the lens/diffuser, tubes and ballast from the existing troffer.
3. Locate the wattage and CCT slide switch, which can be found on the outside of the driver, and adjust
to the desired settings.
Wattage settings:
2’ x 4’ fixture: 23W (2,875 lumens) | 30W (3,750 lumens) | 36W (4,500 lumens)
2’ x 2’ fixture: 18W (2,250 lumens) | 22W (2,750 lumens) | 25W (3,125 lumens)
1’ x 4’ fixture: 18W (2,250 lumens) | 22W (2,750 lumens) | 25W (3,125 lumens)
CCT settings:
3500K | 4000K | 5000K
Rail installation
4. Insert the mounting rails on the opposite sides of the troffer. Slide them between the troffer and t-grid.
See Figure 1.
5. Next, insert the side rails on the remaining opposite sides of the troffer, between the troffer and t-grid,
and insert the end tabs into the slots on the mounting rails. See Figure 2.
6. Secure the mounting rails to the troffer using the included self-drilling screws. See Figure 1.
Panel installation
7. Locate the two panel hinges on the side edge of the panel. Insert the hinges into the keyhole on the
mounting rails. This will allow the panel to hang freely. See Figure 3.
8. Attach the two seismic safety cables from the panel to the mounting rail clip. See figure 4.
9. Connect power wires AC-L (Black) and AC-N (White) into the open side of the quick-connect.
10. Connect the ground wire.
11. Connect Purple (Dim+) and Pink (Dim-) to *0-10V dimmer (if required) with help of wire nuts (not included).
*Follow dimmer control manufacturer instructions
12. Apply the luminaire label to the inside of the troffer.
13. Locate the locking latches (2) on the panel and rotate them to the open or install position.
14. Swing the panel up so it’s even with the ceiling. Then rotate the locking latches (2) so that they engage
the mounting rail tabs. Panel should be flush to ceiling. See Figure 5.
15. Your installation is complete. Once all retrofit kits have been installed you can restore power.
INSTALLATION PROCEDURE
Installation Instruction
If you have an interest in this product,please feel free to contact the email:[email protected]
If you have an interest in the other product,please visit the web www.designlights.org/qpl.
Search by Keyword : ever-tie
Installation
keyhole
Hinges
Safety cable
The existing fluorescent luminaries housing shall be larger than dimensions described in below table:
NOTICE:
Figure 1
2' x 2'
Figure 3
Figure 4 Figure 5
Figure 4A
Figure 2A
2' x 4'
Housing Designation Overall inner Dimensions
610 mm by 608 mm by 78 mm high
1220 mm by 608 mm by 78 mm high
Figure 2
.
Prior to installation, disconnect all incoming power to fixture. Remove existing hardware (lens/lens frame, parabolic
louver, reflectors/ballast covers, brackets, lamps/lamp holders).Leave supply and grounding leads.(Fig.1)
NOTE: Follow all federal and local regulations when disposing of lamps and removed components.
Install LED panel end brackets to each end of the existing fixture by gently lifting it and placing LED panel end
If you are not pleased with the gap between the fixture and T-grid, you may install LED panel side brackets between
Secure the LED panel brackets to the existing fixture using the provided #8x1/2” self-drilling screws. (Fig.3)
Locate the door assembly body onto the keyholes of end brackets, and then slide the door assembly body
Hook the safety cables into the holes positioned the end brackets.
Use the provided wire caps to connect the wire leads of the troffer kits to the main power leads.
Secure the door assembly body by lock the latches riveted on each end of the assembled door frame. (Fig.6)
brackets between the fixture and T-grid.
the fixture and T-grid, there are two tabs to allow for placing the side brackets into the slot of end brackets. (Fig.2)
horizontally to the end of slots. (Fig.4)
(Black-Live, White-Neutral, Green-Grounding) (Fig.5)
Locking Latch
Figure 5A
Figure 6
Installation Instruction
If you have an interest in this product,please feel free to contact the email:[email protected]
If you have an interest in the other product,please visit the web www.designlights.org/qpl.
Search by Keyword : ever-tie
Installation
keyhole
Hinges
Safety cable
The existing fluorescent luminaries housing shall be larger than dimensions described in below table:
NOTICE:
Figure 1
2' x 2'
Figure 3
Figure 4 Figure 5
Figure 4A
Figure 2A
2' x 4'
Housing Designation Overall inner Dimensions
610 mm by 608 mm by 78 mm high
1220 mm by 608 mm by 78 mm high
Figure 2
.
Prior to installation, disconnect all incoming power to fixture. Remove existing hardware (lens/lens frame, parabolic
louver, reflectors/ballast covers, brackets, lamps/lamp holders).Leave supply and grounding leads.(Fig.1)
NOTE: Follow all federal and local regulations when disposing of lamps and removed components.
Install LED panel end brackets to each end of the existing fixture by gently lifting it and placing LED panel end
If you are not pleased with the gap between the fixture and T-grid, you may install LED panel side brackets between
Secure the LED panel brackets to the existing fixture using the provided #8x1/2” self-drilling screws. (Fig.3)
Locate the door assembly body onto the keyholes of end brackets, and then slide the door assembly body
Hook the safety cables into the holes positioned the end brackets.
Use the provided wire caps to connect the wire leads of the troffer kits to the main power leads.
Secure the door assembly body by lock the latches riveted on each end of the assembled door frame. (Fig.6)
brackets between the fixture and T-grid.
the fixture and T-grid, there are two tabs to allow for placing the side brackets into the slot of end brackets. (Fig.2)
horizontally to the end of slots. (Fig.4)
(Black-Live, White-Neutral, Green-Grounding) (Fig.5)
Locking Latch
Figure 5A
Figure 6
Installation Instruction
If you have an interest in this product,please feel free to contact the email:[email protected]
If you have an interest in the other product,please visit the web www.designlights.org/qpl.
Search by Keyword : ever-tie
Installation
keyhole
Hinges
Safety cable
The existing fluorescent luminaries housing shall be larger than dimensions described in below table:
NOTICE:
Figure 1
2' x 2'
Figure 3
Figure 4 Figure 5
Figure 4A
Figure 2A
2' x 4'
Housing Designation Overall inner Dimensions
610 mm by 608 mm by 78 mm high
1220 mm by 608 mm by 78 mm high
Figure 2
.
Prior to installation, disconnect all incoming power to fixture. Remove existing hardware (lens/lens frame, parabolic
louver, reflectors/ballast covers, brackets, lamps/lamp holders).Leave supply and grounding leads.(Fig.1)
NOTE: Follow all federal and local regulations when disposing of lamps and removed components.
Install LED panel end brackets to each end of the existing fixture by gently lifting it and placing LED panel end
If you are not pleased with the gap between the fixture and T-grid, you may install LED panel side brackets between
Secure the LED panel brackets to the existing fixture using the provided #8x1/2” self-drilling screws. (Fig.3)
Locate the door assembly body onto the keyholes of end brackets, and then slide the door assembly body
Hook the safety cables into the holes positioned the end brackets.
Use the provided wire caps to connect the wire leads of the troffer kits to the main power leads.
Secure the door assembly body by lock the latches riveted on each end of the assembled door frame. (Fig.6)
brackets between the fixture and T-grid.
the fixture and T-grid, there are two tabs to allow for placing the side brackets into the slot of end brackets. (Fig.2)
horizontally to the end of slots. (Fig.4)
(Black-Live, White-Neutral, Green-Grounding) (Fig.5)
Locking Latch
Figure 5A
Figure 6
FIGURE 1
Mounting rails Side rails
FIGURE 3
FIGURE 2
FIGURE 4
FIGURE 5
The information and product specifications contained in these instructions
are based upon data believed to be accurate at the time of printing. This
information is subject to change without notice and without incurring liability.
If you have questions regarding specific product details, please contact us at
800-860-3392 or via email at customerservice@litetronics.com.
To check for an updated version of these instructions,
please visit www.litetronics.com.
WWW.LITETRONICS.COM
CustomerService@Litetronics.com or 1-800-860-3392
6969 W. 73rd Street
Bedford Park, IL 60638
Thank you for choosing
9/29/22 - V1.2
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

Litetronics PRC Series LED Light Panel Retrofit User manual

Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI