Linortek ITRIXX NHM IoT Controller and Run­time Meter User manual

Type
User manual
ITRIXXNHMQUICKSETTINGINSTRUCTION
HOWTOTRIGGERTHEMETER
TheNHMmaybeactivatedinanumberofdifferentways:powerinput,digitalinputandanaloginput.
1.Powerinput
InthesimplestsetuptheNHMmaybeactivatedwheneverpowerisappliedtotheunit.Inthiscase,iftheNHMison,itiscounting.A
voltagethresholdisprovidedsotheNHMmaystopcountingaspowerislosttopreventmemorycorruption.Inthisway,youonlyneedto
connecttheNHMtothesamepowersourceoftheequipmentyouwishtocollectrunningdata,nootherwiringrequired.
2.Digitalinput
Youmayalsouseoneoftheinputstoturncountingonandoff.TherearetwodigitalinputsintheNHM.ThedigitalinputsallowNHMto
detectanexternalon/offstateofasensor.Whenyouusethedigitalinputstotriggerthemeter,youwillneedtoenablethedigitalinputs
first.Forinstructionsonhowtoenablethedigitalinputsfromthewebpage,pleasechecktheConfiguringtheDigitalInputsectionon
Page10oftheiTrixxNHMUserManual.
Therearetwomodesofoperationforthedigitalinputs,PULLUP(PU)andISOLATED(ISO).TheNHMissetinISObydefault.Thismodeis
selectedbytheswitchontheNHMmarkedISOandPUforISOLATEDorPULLUPrespectively.
PuttheswitchupforISOanddownforPU.WheninPUmode,theinputsareworkingasadrycontactsothataswitchmaybeused.The
ISOmodeallowsyoutodirectlydrivetheNHM'soptoisolatorwithanexternalvoltagethoughtheinternal1Kresistor.Thisvoltagemaybe
intherangeof5VDCto24VDCsupplyingaminumumof2mAoramaximimof30mAtotheoptoisolatordiode.
Note:Ifusingavoltageabove12VDCforadigitalinput,youMUSTtusetheexternalresistorincludedinthepackaging.Pleaseseethe
wiringinstructionbelow.
ThetwoinputsarelabeledasIN1andIN2ontheNHMcover.EachinputhasaPCterminal,PisforpositiveandCforcommon.
AnoteofCAUTION:TheNHMunitsaregroundisolated.AlwaysconnectsothatpowerloopisonlyconnectedtotheNHMunit.
DoNOTuseexternalgroundconnections.DoingsomaydamagetheNHMorPOEoriginatingdevice.
3.Relayoutput
ThemetercanbeconfiguredtofollowoneoftherelayssuchthatwhentherelayisactivatedtheNHMwillcount.Therearetwo
removeable2positionconnectors(1foreachrelay)andaresimplynumbered"1"and"2"ontheNHM.Theserelaysarenormallyopen.
FormoreinformationonhowtowireyouriTrixxNHM,pleaserefertotheWiringyourITrixxNHMsectionontheiTrixxNHMUserManual.
ACCESSINGYOURITRIXXNHMSOFTWARE
FindingyourIPAddresswithLinortekDiscoverer
TheDiscovererprogramwillautomaticallylocateyourITrixxNHMSERVER.TheDiscovererisaJavaprogram,andrequiresJavaRuntime
tobeinstalledtousethisfeature.Javacanbefoundhere:http://java.com/en/download/index.jsp.
TodownloadtheDiscoverprogram,pleasegoto:https://www.linortek.com/downloads/support¬programming/
UseofChrome&Firefoxbrowsersisrecommended.Pleasenote:IfyouprefertouseInternetExplorer,InternetExplorersavesLinortek
DiscovererasaZipfilebydefault.InordertousetheDiscoverer,youwillneedtoselectSaveasandrenamethefileasLinortek
Discoverer.jarwhenyoudownload.
WhendownloadingtheDiscoverprogram,sometimesyouwillseeapopupwarningmessagedependingonyourbrowsersecurity
settings,askingifyouwanttokeepordiscardthisfile,pleaseclicktheKeepbuttonasthisisaJavaprogram,itwon'tharmyour
computer.
ClickthedeviceyouwanttouseshownontheDiscovererprogramtolaunchtheSERVERwebpagesinyourbrowser.ClicktheLogin
buttononthehomepage.DefaultUsername/passwordis:admin/admin.Youmaychangetheseasyoudesireordisablethisfeaturein
thesettingsmenu.
ConnectingyourITrixxNHMDirectlytoYourPC
YoucanalsoplugyourNHMdirectlytoyourPCinthecasethereisnonetworkconnectionavailable.IfyouplugyourNHMintoyourPC’s
EthernetportitwillusethedefaultIPaddress:169.254.1.1unlessyouhavepreviouslyconfiguredyourNHMtouseastaticIP.Enter
169.254.1.1intoyourwebbrowsertoconnect.Nointernetconnectionrequired.Onceconfigured,youcantheninstallyourNHMwhere
desired.
SERVERCONFIGURATION
LandingPage
AfteryouconnectyourequipmenttotheNHM,downloadtheDiscoverprogramfromourwebsitetoidentifythemeter'sIPaddress.Click
thedeviceshownontheDiscoverprogram,launchthemeterwebpagesinabrowser,youwillbeabletomonitoryourequipmentrun
hoursfromtheNHM'slandingpagewithoutsigningin.
Thelandingpagedisplaysthefollowingsettings:
1.Twometers:EachNetworkHourMeterincludestwoseparatehourmeterswithindependenttriggers.
2.Eachmetercanrecord999999.99hours,decimalhourswith1/100hour.
3.Runningindicator:Spinsifallconditionsaremetandcountinghours.
SettingTimeandDate
WhenfirstconfiguringyourNHMyouwillneedtoverifythetimeanddateonyourhomepage.YourNHMisconfiguredbydefaulttouse
EasternStandardTime(GMT5)andwillapplycorrectionfordaylightsavingstime.Tochangethesesettings,navigatetothe
SettingsTime/Datepage.YoucanthenchangeyourtimezonebyadjustingthevalueinthethirdboxlabeledTimeZone.Ifyou
intendtokeepyourNHMoffyournetworkafterconfiguring,youwillneedtouncheckUseDaylightSavingsTimeandUseNTP
Update.Youwillthenhavetomanuallysetthetimetoaccountfordaylightsavings,andadjustthetimeperiodicallytoaccountfortime
creep.
SettingDataReport
InordertohaveyourNHMsenditsdatatotheHourCollectordesktopapp(introducedinthenextsection),navigatetoSettings
Settings.FortheNHMensureJavaReportisenabled.
ConfiguringtheHourMeter
AfterenablingtheDataReport,younowneedtoconfigurethehourmeter.ToreachtheHourMeterpage,navigatetotheServices
Hours.Onthispagetherearetwoidenticalcolumns;oneforeachhourmeter.
UseMeter–Hourcounterwillnotrununlessthe"UseMeter"ischecked.
Trigger–Thetriggerselectstheconditiontostartandstopthecountermeter.YoucanselectanINPUToraRELAY.Ifthose
conditionsaremetsuchthatthedeviceisON,themeterwillstartrunning.YoumayadditionallyselecttohavetheINPUT
VOLTAGEstartthecounter.Forexample,iftheNetworkHourMeterHourispoweredthecounterruns.
MeterName–Givethemeteranametoidentifywhatisbeingmetered.
Seconds/Tick–Thetickssetthecountingresolution.Thesmallerthenumberthefasterthememoryisusedup.Usuallyset
to2.
UsedEndurance–Becausethenumberofmemorywritesisfinite,theEnduranceindicatorgivesanideaofthememories
condition.Itwillwearout.(Tick*512*100000=memoryenduranceinseconds.)
VoltageThreshold–TheVoltageThresholdconditionmustbesatisfiedalongwiththetriggerconditiontomakethemeter
count.Thisisusefultostopthecountershouldtheunitstarttolosepower.Forexample:bysettingathresholdof20voltsona
24voltsystem,theHourMeterwillassumethatthepowerisdecliningandshutofftopreventacountermemoryerror.
SendEmail–UsingtheEmailcheckboxandtheCount,theunitwillsendanemailwhenthisvalueisexceeded.(Not
compatiblewithSSL/TLSemailserver,thereare3rdpartySMTPdeliveryserverswhichdonotrequireSSLandcanbeused.For
instructionsonhowtousea3rdpartySMTPdeliveryservice,pleaserefertoAppendix1oftheiTrixxNHMUserManual)
EmailCount–Hourmetervaluetosendemailnotification.Thisvaluemaybeenteredin[seconds]or(hours).
RelayControl–ByusingaRelayNumberandaCount,theunitwillactivatearelaywhenthevalueisexceeded.Thisisuseful
forturningonamaintenancelightorbuzzeronamachinethatrequiresalook.
RelayCount–Hourmetervaluetotriggerrelay.Thisvaluemaybeenteredin[seconds]or(hours).
Preset–ThePresetisusedtoZEROthemeterorsetittoanyvalueyoulike.Thisvaluemaybeenteredin[seconds]or
(hours).
PushReportInterval–YoucanchangehowoftentosendthehourreportouttotheHourCollectorApp,it’ssetfor2minute
bydefault.Ifyouwanttochangethefrequency,youcanenterthenumberhere(byminutes).
DATACOLLECTIONAPP
HourMeterCollector
LinortekHourCollectorisaJavaprogram.ItwasdevelopedforusewithanyLinortekIoTMeter,Thisappisfreetodownloadat:
https://www.linortek.com/downloads/supportprogramming/
TheCollectorprogramisazipfilewhenyoudownloadfromourwebsite.Youneedtoextractthefilebeforeusingit.TheCollectorhas
twoparts:.Jarfileandalibfolder.BothofthesefilesMUSThavethesamenameandbeinthesamedirectory.
TheLinortek_HourMeterisanexecutableJarfile,youcanopenitonceyouhaveJavaenabledonyourcomputer.
WhenyouruntheHourMeterCollectorforthefirsttime,itwilgenerateaCSV_FILEfolderwithyourHourMeterLogsdetails.Ifyou
renamethisfileordeleteit,itwilljustcreateanotherfoldernameCSV_FILE.
DataCollectorProApp
TheDataCollectorProappisanupgradedversionoftheHourCollectorapp.Itcannotonlydisplaythehourreadingsandstatus,aswell
asthedigital/analoginputsdataforeachmeter,butalsoallowsyoutoselectmanually/automaticallycollecting/exportingthedata.The
DatacollectorProAppcanbedownloadedhere:https://www.linortek.com/downloads/supportprogramming/.
Formoreinformationonhowtousethedatacollectionapps,pleaserefertotheiTrixxNHMUserManual.
RESTFULAPI
HerearetheavailableAPIsthatyoucanexportthedatafromthedevicedirectly(Note:ThisAPIcommandsareforsoftwareREV.
427andabove)
Meter1:your_IP_address/api/hourmeter/1/getcount
Meter2:your_IP_address/api/hourmeter/2/getcount
Forpullingthehoursout,therearetwoXMLcommandsbuiltin:
your_IP_address/hours.xml
your_IP_address/hourdetail.xml
Forotherwaystointegratethehourreadingstoyoursystem,pleaserefertotheiTrixxNHMUserManual,oremailourtechnical
supportteamat[email protected]forassistance.
ThankyouforpurchasingtheLinortekITrixxNHM.TheNHMisanIoTcontrollerandruntimemeter.TheNHMisequippedwithtwo
digitalinputs(524VDC),tworelayoutputscapableoftrackingruntimehoursofuptotwodifferentpiecesofequipment.Forthe
completesettinginstructions,pleaserefertotheiTrixxNHMUserManual,whichcanbedownloadedhere:
https://www.linortek.com/downloads/documentations/
PRODUCTCHECKLIST–Eachproductkitboxcontainsthefollowing:
____OneiTrixxNHMSERVER
____One12VDCPowerSupply
____OneCAT5PatchCord
____OneDINrailmountclip
____One2.2kOhmResistorKit
____iTrixxNHMQuickSettingInstruction
1
HOWTOTRIGGERTHEMETER
TheNHMmaybeactivatedinanumberofdifferentways:powerinput,digitalinputandanaloginput.
1.Powerinput
InthesimplestsetuptheNHMmaybeactivatedwheneverpowerisappliedtotheunit.Inthiscase,iftheNHMison,itiscounting.A
voltagethresholdisprovidedsotheNHMmaystopcountingaspowerislosttopreventmemorycorruption.Inthisway,youonlyneedto
connecttheNHMtothesamepowersourceoftheequipmentyouwishtocollectrunningdata,nootherwiringrequired.
2.Digitalinput
Youmayalsouseoneoftheinputstoturncountingonandoff.TherearetwodigitalinputsintheNHM.ThedigitalinputsallowNHMto
detectanexternalon/offstateofasensor.Whenyouusethedigitalinputstotriggerthemeter,youwillneedtoenablethedigitalinputs
first.Forinstructionsonhowtoenablethedigitalinputsfromthewebpage,pleasechecktheConfiguringtheDigitalInputsectionon
Page10oftheiTrixxNHMUserManual.
Therearetwomodesofoperationforthedigitalinputs,PULLUP(PU)andISOLATED(ISO).TheNHMissetinISObydefault.Thismodeis
selectedbytheswitchontheNHMmarkedISOandPUforISOLATEDorPULLUPrespectively.
PuttheswitchupforISOanddownforPU.WheninPUmode,theinputsareworkingasadrycontactsothataswitchmaybeused.The
ISOmodeallowsyoutodirectlydrivetheNHM'soptoisolatorwithanexternalvoltagethoughtheinternal1Kresistor.Thisvoltagemaybe
intherangeof5VDCto24VDCsupplyingaminumumof2mAoramaximimof30mAtotheoptoisolatordiode.
Note:Ifusingavoltageabove12VDCforadigitalinput,youMUSTtusetheexternalresistorincludedinthepackaging.Pleaseseethe
wiringinstructionbelow.
ThetwoinputsarelabeledasIN1andIN2ontheNHMcover.EachinputhasaPCterminal,PisforpositiveandCforcommon.
AnoteofCAUTION:TheNHMunitsaregroundisolated.AlwaysconnectsothatpowerloopisonlyconnectedtotheNHMunit.
DoNOTuseexternalgroundconnections.DoingsomaydamagetheNHMorPOEoriginatingdevice.
3.Relayoutput
ThemetercanbeconfiguredtofollowoneoftherelayssuchthatwhentherelayisactivatedtheNHMwillcount.Therearetwo
removeable2positionconnectors(1foreachrelay)andaresimplynumbered"1"and"2"ontheNHM.Theserelaysarenormallyopen.
FormoreinformationonhowtowireyouriTrixxNHM,pleaserefertotheWiringyourITrixxNHMsectionontheiTrixxNHMUserManual.
ACCESSINGYOURITRIXXNHMSOFTWARE
FindingyourIPAddresswithLinortekDiscoverer
TheDiscovererprogramwillautomaticallylocateyourITrixxNHMSERVER.TheDiscovererisaJavaprogram,andrequiresJavaRuntime
tobeinstalledtousethisfeature.Javacanbefoundhere:http://java.com/en/download/index.jsp.
TodownloadtheDiscoverprogram,pleasegoto:https://www.linortek.com/downloads/support¬programming/
UseofChrome&Firefoxbrowsersisrecommended.Pleasenote:IfyouprefertouseInternetExplorer,InternetExplorersavesLinortek
DiscovererasaZipfilebydefault.InordertousetheDiscoverer,youwillneedtoselectSaveasandrenamethefileasLinortek
Discoverer.jarwhenyoudownload.
WhendownloadingtheDiscoverprogram,sometimesyouwillseeapopupwarningmessagedependingonyourbrowsersecurity
settings,askingifyouwanttokeepordiscardthisfile,pleaseclicktheKeepbuttonasthisisaJavaprogram,itwon'tharmyour
computer.
ClickthedeviceyouwanttouseshownontheDiscovererprogramtolaunchtheSERVERwebpagesinyourbrowser.ClicktheLogin
buttononthehomepage.DefaultUsername/passwordis:admin/admin.Youmaychangetheseasyoudesireordisablethisfeaturein
thesettingsmenu.
ConnectingyourITrixxNHMDirectlytoYourPC
YoucanalsoplugyourNHMdirectlytoyourPCinthecasethereisnonetworkconnectionavailable.IfyouplugyourNHMintoyourPC’s
EthernetportitwillusethedefaultIPaddress:169.254.1.1unlessyouhavepreviouslyconfiguredyourNHMtouseastaticIP.Enter
169.254.1.1intoyourwebbrowsertoconnect.Nointernetconnectionrequired.Onceconfigured,youcantheninstallyourNHMwhere
desired.
SERVERCONFIGURATION
LandingPage
AfteryouconnectyourequipmenttotheNHM,downloadtheDiscoverprogramfromourwebsitetoidentifythemeter'sIPaddress.Click
thedeviceshownontheDiscoverprogram,launchthemeterwebpagesinabrowser,youwillbeabletomonitoryourequipmentrun
hoursfromtheNHM'slandingpagewithoutsigningin.
Thelandingpagedisplaysthefollowingsettings:
1.Twometers:EachNetworkHourMeterincludestwoseparatehourmeterswithindependenttriggers.
2.Eachmetercanrecord999999.99hours,decimalhourswith1/100hour.
3.Runningindicator:Spinsifallconditionsaremetandcountinghours.
SettingTimeandDate
WhenfirstconfiguringyourNHMyouwillneedtoverifythetimeanddateonyourhomepage.YourNHMisconfiguredbydefaulttouse
EasternStandardTime(GMT5)andwillapplycorrectionfordaylightsavingstime.Tochangethesesettings,navigatetothe
SettingsTime/Datepage.YoucanthenchangeyourtimezonebyadjustingthevalueinthethirdboxlabeledTimeZone.Ifyou
intendtokeepyourNHMoffyournetworkafterconfiguring,youwillneedtouncheckUseDaylightSavingsTimeandUseNTP
Update.Youwillthenhavetomanuallysetthetimetoaccountfordaylightsavings,andadjustthetimeperiodicallytoaccountfortime
creep.
SettingDataReport
InordertohaveyourNHMsenditsdatatotheHourCollectordesktopapp(introducedinthenextsection),navigatetoSettings
Settings.FortheNHMensureJavaReportisenabled.
ConfiguringtheHourMeter
AfterenablingtheDataReport,younowneedtoconfigurethehourmeter.ToreachtheHourMeterpage,navigatetotheServices
Hours.Onthispagetherearetwoidenticalcolumns;oneforeachhourmeter.
UseMeter–Hourcounterwillnotrununlessthe"UseMeter"ischecked.
Trigger–Thetriggerselectstheconditiontostartandstopthecountermeter.YoucanselectanINPUToraRELAY.Ifthose
conditionsaremetsuchthatthedeviceisON,themeterwillstartrunning.YoumayadditionallyselecttohavetheINPUT
VOLTAGEstartthecounter.Forexample,iftheNetworkHourMeterHourispoweredthecounterruns.
MeterName–Givethemeteranametoidentifywhatisbeingmetered.
Seconds/Tick–Thetickssetthecountingresolution.Thesmallerthenumberthefasterthememoryisusedup.Usuallyset
to2.
UsedEndurance–Becausethenumberofmemorywritesisfinite,theEnduranceindicatorgivesanideaofthememories
condition.Itwillwearout.(Tick*512*100000=memoryenduranceinseconds.)
VoltageThreshold–TheVoltageThresholdconditionmustbesatisfiedalongwiththetriggerconditiontomakethemeter
count.Thisisusefultostopthecountershouldtheunitstarttolosepower.Forexample:bysettingathresholdof20voltsona
24voltsystem,theHourMeterwillassumethatthepowerisdecliningandshutofftopreventacountermemoryerror.
SendEmail–UsingtheEmailcheckboxandtheCount,theunitwillsendanemailwhenthisvalueisexceeded.(Not
compatiblewithSSL/TLSemailserver,thereare3rdpartySMTPdeliveryserverswhichdonotrequireSSLandcanbeused.For
instructionsonhowtousea3rdpartySMTPdeliveryservice,pleaserefertoAppendix1oftheiTrixxNHMUserManual)
EmailCount–Hourmetervaluetosendemailnotification.Thisvaluemaybeenteredin[seconds]or(hours).
RelayControl–ByusingaRelayNumberandaCount,theunitwillactivatearelaywhenthevalueisexceeded.Thisisuseful
forturningonamaintenancelightorbuzzeronamachinethatrequiresalook.
RelayCount–Hourmetervaluetotriggerrelay.Thisvaluemaybeenteredin[seconds]or(hours).
Preset–ThePresetisusedtoZEROthemeterorsetittoanyvalueyoulike.Thisvaluemaybeenteredin[seconds]or
(hours).
PushReportInterval–YoucanchangehowoftentosendthehourreportouttotheHourCollectorApp,it’ssetfor2minute
bydefault.Ifyouwanttochangethefrequency,youcanenterthenumberhere(byminutes).
DATACOLLECTIONAPP
HourMeterCollector
LinortekHourCollectorisaJavaprogram.ItwasdevelopedforusewithanyLinortekIoTMeter,Thisappisfreetodownloadat:
https://www.linortek.com/downloads/supportprogramming/
TheCollectorprogramisazipfilewhenyoudownloadfromourwebsite.Youneedtoextractthefilebeforeusingit.TheCollectorhas
twoparts:.Jarfileandalibfolder.BothofthesefilesMUSThavethesamenameandbeinthesamedirectory.
TheLinortek_HourMeterisanexecutableJarfile,youcanopenitonceyouhaveJavaenabledonyourcomputer.
WhenyouruntheHourMeterCollectorforthefirsttime,itwilgenerateaCSV_FILEfolderwithyourHourMeterLogsdetails.Ifyou
renamethisfileordeleteit,itwilljustcreateanotherfoldernameCSV_FILE.
DataCollectorProApp
TheDataCollectorProappisanupgradedversionoftheHourCollectorapp.Itcannotonlydisplaythehourreadingsandstatus,aswell
asthedigital/analoginputsdataforeachmeter,butalsoallowsyoutoselectmanually/automaticallycollecting/exportingthedata.The
DatacollectorProAppcanbedownloadedhere:https://www.linortek.com/downloads/supportprogramming/.
Formoreinformationonhowtousethedatacollectionapps,pleaserefertotheiTrixxNHMUserManual.
RESTFULAPI
HerearetheavailableAPIsthatyoucanexportthedatafromthedevicedirectly(Note:ThisAPIcommandsareforsoftwareREV.
427andabove)
Meter1:your_IP_address/api/hourmeter/1/getcount
Meter2:your_IP_address/api/hourmeter/2/getcount
Forpullingthehoursout,therearetwoXMLcommandsbuiltin:
your_IP_address/hours.xml
your_IP_address/hourdetail.xml
Forotherwaystointegratethehourreadingstoyoursystem,pleaserefertotheiTrixxNHMUserManual,oremailourtechnical
supportteamat[email protected]forassistance.
2
HOWTOTRIGGERTHEMETER
TheNHMmaybeactivatedinanumberofdifferentways:powerinput,digitalinputandanaloginput.
1.Powerinput
InthesimplestsetuptheNHMmaybeactivatedwheneverpowerisappliedtotheunit.Inthiscase,iftheNHMison,itiscounting.A
voltagethresholdisprovidedsotheNHMmaystopcountingaspowerislosttopreventmemorycorruption.Inthisway,youonlyneedto
connecttheNHMtothesamepowersourceoftheequipmentyouwishtocollectrunningdata,nootherwiringrequired.
2.Digitalinput
Youmayalsouseoneoftheinputstoturncountingonandoff.TherearetwodigitalinputsintheNHM.ThedigitalinputsallowNHMto
detectanexternalon/offstateofasensor.Whenyouusethedigitalinputstotriggerthemeter,youwillneedtoenablethedigitalinputs
first.Forinstructionsonhowtoenablethedigitalinputsfromthewebpage,pleasechecktheConfiguringtheDigitalInputsectionon
Page10oftheiTrixxNHMUserManual.
Therearetwomodesofoperationforthedigitalinputs,PULLUP(PU)andISOLATED(ISO).TheNHMissetinISObydefault.Thismodeis
selectedbytheswitchontheNHMmarkedISOandPUforISOLATEDorPULLUPrespectively.
PuttheswitchupforISOanddownforPU.WheninPUmode,theinputsareworkingasadrycontactsothataswitchmaybeused.The
ISOmodeallowsyoutodirectlydrivetheNHM'soptoisolatorwithanexternalvoltagethoughtheinternal1Kresistor.Thisvoltagemaybe
intherangeof5VDCto24VDCsupplyingaminumumof2mAoramaximimof30mAtotheoptoisolatordiode.
Note:Ifusingavoltageabove12VDCforadigitalinput,youMUSTtusetheexternalresistorincludedinthepackaging.Pleaseseethe
wiringinstructionbelow.
ThetwoinputsarelabeledasIN1andIN2ontheNHMcover.EachinputhasaPCterminal,PisforpositiveandCforcommon.
AnoteofCAUTION:TheNHMunitsaregroundisolated.AlwaysconnectsothatpowerloopisonlyconnectedtotheNHMunit.
DoNOTuseexternalgroundconnections.DoingsomaydamagetheNHMorPOEoriginatingdevice.
3.Relayoutput
ThemetercanbeconfiguredtofollowoneoftherelayssuchthatwhentherelayisactivatedtheNHMwillcount.Therearetwo
removeable2positionconnectors(1foreachrelay)andaresimplynumbered"1"and"2"ontheNHM.Theserelaysarenormallyopen.
FormoreinformationonhowtowireyouriTrixxNHM,pleaserefertotheWiringyourITrixxNHMsectionontheiTrixxNHMUserManual.
ACCESSINGYOURITRIXXNHMSOFTWARE
FindingyourIPAddresswithLinortekDiscoverer
TheDiscovererprogramwillautomaticallylocateyourITrixxNHMSERVER.TheDiscovererisaJavaprogram,andrequiresJavaRuntime
tobeinstalledtousethisfeature.Javacanbefoundhere:http://java.com/en/download/index.jsp.
TodownloadtheDiscoverprogram,pleasegoto:https://www.linortek.com/downloads/support¬programming/
UseofChrome&Firefoxbrowsersisrecommended.Pleasenote:IfyouprefertouseInternetExplorer,InternetExplorersavesLinortek
DiscovererasaZipfilebydefault.InordertousetheDiscoverer,youwillneedtoselectSaveasandrenamethefileasLinortek
Discoverer.jarwhenyoudownload.
WhendownloadingtheDiscoverprogram,sometimesyouwillseeapopupwarningmessagedependingonyourbrowsersecurity
settings,askingifyouwanttokeepordiscardthisfile,pleaseclicktheKeepbuttonasthisisaJavaprogram,itwon'tharmyour
computer.
ClickthedeviceyouwanttouseshownontheDiscovererprogramtolaunchtheSERVERwebpagesinyourbrowser.ClicktheLogin
buttononthehomepage.DefaultUsername/passwordis:admin/admin.Youmaychangetheseasyoudesireordisablethisfeaturein
thesettingsmenu.
ConnectingyourITrixxNHMDirectlytoYourPC
YoucanalsoplugyourNHMdirectlytoyourPCinthecasethereisnonetworkconnectionavailable.IfyouplugyourNHMintoyourPC’s
EthernetportitwillusethedefaultIPaddress:169.254.1.1unlessyouhavepreviouslyconfiguredyourNHMtouseastaticIP.Enter
169.254.1.1intoyourwebbrowsertoconnect.Nointernetconnectionrequired.Onceconfigured,youcantheninstallyourNHMwhere
desired.
SERVERCONFIGURATION
LandingPage
AfteryouconnectyourequipmenttotheNHM,downloadtheDiscoverprogramfromourwebsitetoidentifythemeter'sIPaddress.Click
thedeviceshownontheDiscoverprogram,launchthemeterwebpagesinabrowser,youwillbeabletomonitoryourequipmentrun
hoursfromtheNHM'slandingpagewithoutsigningin.
Thelandingpagedisplaysthefollowingsettings:
1.Twometers:EachNetworkHourMeterincludestwoseparatehourmeterswithindependenttriggers.
2.Eachmetercanrecord999999.99hours,decimalhourswith1/100hour.
3.Runningindicator:Spinsifallconditionsaremetandcountinghours.
SettingTimeandDate
WhenfirstconfiguringyourNHMyouwillneedtoverifythetimeanddateonyourhomepage.YourNHMisconfiguredbydefaulttouse
EasternStandardTime(GMT5)andwillapplycorrectionfordaylightsavingstime.Tochangethesesettings,navigatetothe
SettingsTime/Datepage.YoucanthenchangeyourtimezonebyadjustingthevalueinthethirdboxlabeledTimeZone.Ifyou
intendtokeepyourNHMoffyournetworkafterconfiguring,youwillneedtouncheckUseDaylightSavingsTimeandUseNTP
Update.Youwillthenhavetomanuallysetthetimetoaccountfordaylightsavings,andadjustthetimeperiodicallytoaccountfortime
creep.
SettingDataReport
InordertohaveyourNHMsenditsdatatotheHourCollectordesktopapp(introducedinthenextsection),navigatetoSettings
Settings.FortheNHMensureJavaReportisenabled.
ConfiguringtheHourMeter
AfterenablingtheDataReport,younowneedtoconfigurethehourmeter.ToreachtheHourMeterpage,navigatetotheServices
Hours.Onthispagetherearetwoidenticalcolumns;oneforeachhourmeter.
UseMeter–Hourcounterwillnotrununlessthe"UseMeter"ischecked.
Trigger–Thetriggerselectstheconditiontostartandstopthecountermeter.YoucanselectanINPUToraRELAY.Ifthose
conditionsaremetsuchthatthedeviceisON,themeterwillstartrunning.YoumayadditionallyselecttohavetheINPUT
VOLTAGEstartthecounter.Forexample,iftheNetworkHourMeterHourispoweredthecounterruns.
MeterName–Givethemeteranametoidentifywhatisbeingmetered.
Seconds/Tick–Thetickssetthecountingresolution.Thesmallerthenumberthefasterthememoryisusedup.Usuallyset
to2.
UsedEndurance–Becausethenumberofmemorywritesisfinite,theEnduranceindicatorgivesanideaofthememories
condition.Itwillwearout.(Tick*512*100000=memoryenduranceinseconds.)
VoltageThreshold–TheVoltageThresholdconditionmustbesatisfiedalongwiththetriggerconditiontomakethemeter
count.Thisisusefultostopthecountershouldtheunitstarttolosepower.Forexample:bysettingathresholdof20voltsona
24voltsystem,theHourMeterwillassumethatthepowerisdecliningandshutofftopreventacountermemoryerror.
SendEmail–UsingtheEmailcheckboxandtheCount,theunitwillsendanemailwhenthisvalueisexceeded.(Not
compatiblewithSSL/TLSemailserver,thereare3rdpartySMTPdeliveryserverswhichdonotrequireSSLandcanbeused.For
instructionsonhowtousea3rdpartySMTPdeliveryservice,pleaserefertoAppendix1oftheiTrixxNHMUserManual)
EmailCount–Hourmetervaluetosendemailnotification.Thisvaluemaybeenteredin[seconds]or(hours).
RelayControl–ByusingaRelayNumberandaCount,theunitwillactivatearelaywhenthevalueisexceeded.Thisisuseful
forturningonamaintenancelightorbuzzeronamachinethatrequiresalook.
RelayCount–Hourmetervaluetotriggerrelay.Thisvaluemaybeenteredin[seconds]or(hours).
Preset–ThePresetisusedtoZEROthemeterorsetittoanyvalueyoulike.Thisvaluemaybeenteredin[seconds]or
(hours).
PushReportInterval–YoucanchangehowoftentosendthehourreportouttotheHourCollectorApp,it’ssetfor2minute
bydefault.Ifyouwanttochangethefrequency,youcanenterthenumberhere(byminutes).
DATACOLLECTIONAPP
HourMeterCollector
LinortekHourCollectorisaJavaprogram.ItwasdevelopedforusewithanyLinortekIoTMeter,Thisappisfreetodownloadat:
https://www.linortek.com/downloads/supportprogramming/
TheCollectorprogramisazipfilewhenyoudownloadfromourwebsite.Youneedtoextractthefilebeforeusingit.TheCollectorhas
twoparts:.Jarfileandalibfolder.BothofthesefilesMUSThavethesamenameandbeinthesamedirectory.
TheLinortek_HourMeterisanexecutableJarfile,youcanopenitonceyouhaveJavaenabledonyourcomputer.
WhenyouruntheHourMeterCollectorforthefirsttime,itwilgenerateaCSV_FILEfolderwithyourHourMeterLogsdetails.Ifyou
renamethisfileordeleteit,itwilljustcreateanotherfoldernameCSV_FILE.
DataCollectorProApp
TheDataCollectorProappisanupgradedversionoftheHourCollectorapp.Itcannotonlydisplaythehourreadingsandstatus,aswell
asthedigital/analoginputsdataforeachmeter,butalsoallowsyoutoselectmanually/automaticallycollecting/exportingthedata.The
DatacollectorProAppcanbedownloadedhere:https://www.linortek.com/downloads/supportprogramming/.
Formoreinformationonhowtousethedatacollectionapps,pleaserefertotheiTrixxNHMUserManual.
RESTFULAPI
HerearetheavailableAPIsthatyoucanexportthedatafromthedevicedirectly(Note:ThisAPIcommandsareforsoftwareREV.
427andabove)
Meter1:your_IP_address/api/hourmeter/1/getcount
Meter2:your_IP_address/api/hourmeter/2/getcount
Forpullingthehoursout,therearetwoXMLcommandsbuiltin:
your_IP_address/hours.xml
your_IP_address/hourdetail.xml
Forotherwaystointegratethehourreadingstoyoursystem,pleaserefertotheiTrixxNHMUserManual,oremailourtechnical
supportteamat[email protected]forassistance.
3
Forcompleteproductdocumentation,currentsoftware,webpagesandvariousutilities,visit
https://www.linortek.com/downloads/.Theproductmanual,aswellassoftwareupdates,areavailablefordownload.
HOWTOTRIGGERTHEMETER
TheNHMmaybeactivatedinanumberofdifferentways:powerinput,digitalinputandanaloginput.
1.Powerinput
InthesimplestsetuptheNHMmaybeactivatedwheneverpowerisappliedtotheunit.Inthiscase,iftheNHMison,itiscounting.A
voltagethresholdisprovidedsotheNHMmaystopcountingaspowerislosttopreventmemorycorruption.Inthisway,youonlyneedto
connecttheNHMtothesamepowersourceoftheequipmentyouwishtocollectrunningdata,nootherwiringrequired.
2.Digitalinput
Youmayalsouseoneoftheinputstoturncountingonandoff.TherearetwodigitalinputsintheNHM.ThedigitalinputsallowNHMto
detectanexternalon/offstateofasensor.Whenyouusethedigitalinputstotriggerthemeter,youwillneedtoenablethedigitalinputs
first.Forinstructionsonhowtoenablethedigitalinputsfromthewebpage,pleasechecktheConfiguringtheDigitalInputsectionon
Page10oftheiTrixxNHMUserManual.
Therearetwomodesofoperationforthedigitalinputs,PULLUP(PU)andISOLATED(ISO).TheNHMissetinISObydefault.Thismodeis
selectedbytheswitchontheNHMmarkedISOandPUforISOLATEDorPULLUPrespectively.
PuttheswitchupforISOanddownforPU.WheninPUmode,theinputsareworkingasadrycontactsothataswitchmaybeused.The
ISOmodeallowsyoutodirectlydrivetheNHM'soptoisolatorwithanexternalvoltagethoughtheinternal1Kresistor.Thisvoltagemaybe
intherangeof5VDCto24VDCsupplyingaminumumof2mAoramaximimof30mAtotheoptoisolatordiode.
Note:Ifusingavoltageabove12VDCforadigitalinput,youMUSTtusetheexternalresistorincludedinthepackaging.Pleaseseethe
wiringinstructionbelow.
ThetwoinputsarelabeledasIN1andIN2ontheNHMcover.EachinputhasaPCterminal,PisforpositiveandCforcommon.
AnoteofCAUTION:TheNHMunitsaregroundisolated.AlwaysconnectsothatpowerloopisonlyconnectedtotheNHMunit.
DoNOTuseexternalgroundconnections.DoingsomaydamagetheNHMorPOEoriginatingdevice.
3.Relayoutput
ThemetercanbeconfiguredtofollowoneoftherelayssuchthatwhentherelayisactivatedtheNHMwillcount.Therearetwo
removeable2positionconnectors(1foreachrelay)andaresimplynumbered"1"and"2"ontheNHM.Theserelaysarenormallyopen.
FormoreinformationonhowtowireyouriTrixxNHM,pleaserefertotheWiringyourITrixxNHMsectionontheiTrixxNHMUserManual.
ACCESSINGYOURITRIXXNHMSOFTWARE
FindingyourIPAddresswithLinortekDiscoverer
TheDiscovererprogramwillautomaticallylocateyourITrixxNHMSERVER.TheDiscovererisaJavaprogram,andrequiresJavaRuntime
tobeinstalledtousethisfeature.Javacanbefoundhere:http://java.com/en/download/index.jsp.
TodownloadtheDiscoverprogram,pleasegoto:https://www.linortek.com/downloads/support¬programming/
UseofChrome&Firefoxbrowsersisrecommended.Pleasenote:IfyouprefertouseInternetExplorer,InternetExplorersavesLinortek
DiscovererasaZipfilebydefault.InordertousetheDiscoverer,youwillneedtoselectSaveasandrenamethefileasLinortek
Discoverer.jarwhenyoudownload.
WhendownloadingtheDiscoverprogram,sometimesyouwillseeapopupwarningmessagedependingonyourbrowsersecurity
settings,askingifyouwanttokeepordiscardthisfile,pleaseclicktheKeepbuttonasthisisaJavaprogram,itwon'tharmyour
computer.
ClickthedeviceyouwanttouseshownontheDiscovererprogramtolaunchtheSERVERwebpagesinyourbrowser.ClicktheLogin
buttononthehomepage.DefaultUsername/passwordis:admin/admin.Youmaychangetheseasyoudesireordisablethisfeaturein
thesettingsmenu.
ConnectingyourITrixxNHMDirectlytoYourPC
YoucanalsoplugyourNHMdirectlytoyourPCinthecasethereisnonetworkconnectionavailable.IfyouplugyourNHMintoyourPC’s
EthernetportitwillusethedefaultIPaddress:169.254.1.1unlessyouhavepreviouslyconfiguredyourNHMtouseastaticIP.Enter
169.254.1.1intoyourwebbrowsertoconnect.Nointernetconnectionrequired.Onceconfigured,youcantheninstallyourNHMwhere
desired.
SERVERCONFIGURATION
LandingPage
AfteryouconnectyourequipmenttotheNHM,downloadtheDiscoverprogramfromourwebsitetoidentifythemeter'sIPaddress.Click
thedeviceshownontheDiscoverprogram,launchthemeterwebpagesinabrowser,youwillbeabletomonitoryourequipmentrun
hoursfromtheNHM'slandingpagewithoutsigningin.
Thelandingpagedisplaysthefollowingsettings:
1.Twometers:EachNetworkHourMeterincludestwoseparatehourmeterswithindependenttriggers.
2.Eachmetercanrecord999999.99hours,decimalhourswith1/100hour.
3.Runningindicator:Spinsifallconditionsaremetandcountinghours.
SettingTimeandDate
WhenfirstconfiguringyourNHMyouwillneedtoverifythetimeanddateonyourhomepage.YourNHMisconfiguredbydefaulttouse
EasternStandardTime(GMT5)andwillapplycorrectionfordaylightsavingstime.Tochangethesesettings,navigatetothe
SettingsTime/Datepage.YoucanthenchangeyourtimezonebyadjustingthevalueinthethirdboxlabeledTimeZone.Ifyou
intendtokeepyourNHMoffyournetworkafterconfiguring,youwillneedtouncheckUseDaylightSavingsTimeandUseNTP
Update.Youwillthenhavetomanuallysetthetimetoaccountfordaylightsavings,andadjustthetimeperiodicallytoaccountfortime
creep.
SettingDataReport
InordertohaveyourNHMsenditsdatatotheHourCollectordesktopapp(introducedinthenextsection),navigatetoSettings
Settings.FortheNHMensureJavaReportisenabled.
ConfiguringtheHourMeter
AfterenablingtheDataReport,younowneedtoconfigurethehourmeter.ToreachtheHourMeterpage,navigatetotheServices
Hours.Onthispagetherearetwoidenticalcolumns;oneforeachhourmeter.
UseMeter–Hourcounterwillnotrununlessthe"UseMeter"ischecked.
Trigger–Thetriggerselectstheconditiontostartandstopthecountermeter.YoucanselectanINPUToraRELAY.Ifthose
conditionsaremetsuchthatthedeviceisON,themeterwillstartrunning.YoumayadditionallyselecttohavetheINPUT
VOLTAGEstartthecounter.Forexample,iftheNetworkHourMeterHourispoweredthecounterruns.
MeterName–Givethemeteranametoidentifywhatisbeingmetered.
Seconds/Tick–Thetickssetthecountingresolution.Thesmallerthenumberthefasterthememoryisusedup.Usuallyset
to2.
UsedEndurance–Becausethenumberofmemorywritesisfinite,theEnduranceindicatorgivesanideaofthememories
condition.Itwillwearout.(Tick*512*100000=memoryenduranceinseconds.)
VoltageThreshold–TheVoltageThresholdconditionmustbesatisfiedalongwiththetriggerconditiontomakethemeter
count.Thisisusefultostopthecountershouldtheunitstarttolosepower.Forexample:bysettingathresholdof20voltsona
24voltsystem,theHourMeterwillassumethatthepowerisdecliningandshutofftopreventacountermemoryerror.
SendEmail–UsingtheEmailcheckboxandtheCount,theunitwillsendanemailwhenthisvalueisexceeded.(Not
compatiblewithSSL/TLSemailserver,thereare3rdpartySMTPdeliveryserverswhichdonotrequireSSLandcanbeused.For
instructionsonhowtousea3rdpartySMTPdeliveryservice,pleaserefertoAppendix1oftheiTrixxNHMUserManual)
EmailCount–Hourmetervaluetosendemailnotification.Thisvaluemaybeenteredin[seconds]or(hours).
RelayControl–ByusingaRelayNumberandaCount,theunitwillactivatearelaywhenthevalueisexceeded.Thisisuseful
forturningonamaintenancelightorbuzzeronamachinethatrequiresalook.
RelayCount–Hourmetervaluetotriggerrelay.Thisvaluemaybeenteredin[seconds]or(hours).
Preset–ThePresetisusedtoZEROthemeterorsetittoanyvalueyoulike.Thisvaluemaybeenteredin[seconds]or
(hours).
PushReportInterval–YoucanchangehowoftentosendthehourreportouttotheHourCollectorApp,it’ssetfor2minute
bydefault.Ifyouwanttochangethefrequency,youcanenterthenumberhere(byminutes).
DATACOLLECTIONAPP
HourMeterCollector
LinortekHourCollectorisaJavaprogram.ItwasdevelopedforusewithanyLinortekIoTMeter,Thisappisfreetodownloadat:
https://www.linortek.com/downloads/supportprogramming/
TheCollectorprogramisazipfilewhenyoudownloadfromourwebsite.Youneedtoextractthefilebeforeusingit.TheCollectorhas
twoparts:.Jarfileandalibfolder.BothofthesefilesMUSThavethesamenameandbeinthesamedirectory.
TheLinortek_HourMeterisanexecutableJarfile,youcanopenitonceyouhaveJavaenabledonyourcomputer.
WhenyouruntheHourMeterCollectorforthefirsttime,itwilgenerateaCSV_FILEfolderwithyourHourMeterLogsdetails.Ifyou
renamethisfileordeleteit,itwilljustcreateanotherfoldernameCSV_FILE.
DataCollectorProApp
TheDataCollectorProappisanupgradedversionoftheHourCollectorapp.Itcannotonlydisplaythehourreadingsandstatus,aswell
asthedigital/analoginputsdataforeachmeter,butalsoallowsyoutoselectmanually/automaticallycollecting/exportingthedata.The
DatacollectorProAppcanbedownloadedhere:https://www.linortek.com/downloads/supportprogramming/.
Formoreinformationonhowtousethedatacollectionapps,pleaserefertotheiTrixxNHMUserManual.
RESTFULAPI
HerearetheavailableAPIsthatyoucanexportthedatafromthedevicedirectly(Note:ThisAPIcommandsareforsoftwareREV.
427andabove)
Meter1:your_IP_address/api/hourmeter/1/getcount
Meter2:your_IP_address/api/hourmeter/2/getcount
Forpullingthehoursout,therearetwoXMLcommandsbuiltin:
your_IP_address/hours.xml
your_IP_address/hourdetail.xml
Forotherwaystointegratethehourreadingstoyoursystem,pleaserefertotheiTrixxNHMUserManual,oremailourtechnical
supportteamat[email protected]forassistance.
LinorTechnology,Inc.
Informationsubjecttochangewithoutnotice.
www.linortek.com
0150800018
0422D
PrintedinU.S.A.
FURTHERNOTICEFORLIMITATIONOFUSE
WhenwiringalinevoltagedeviceyouMUSTeitherbeaqualifiedelectricianorusetheservicesofaqualifiedelectrician.Additionally,localcodesmustbefollowed
includingbutnotlimitedtowiregaugesizeandsuitablehousing.
Linortekcannotassumeanyresponsibilityforharmtotheuserorthirdpartiesforimproperlyusingourproduct.Thisliabilityremainswiththeuser.Linortekcannot
assumeanyresponsibilityfordamagetothedeviceforimproperlyusingourSERVERproduct.
SeeproductmanualonourwebsiteforfullDisclaimerandUserAgreement.