  • Hello! I am an AI chatbot trained to assist you with the Wolf BM-Solar Installation And Operating Instructions Manual. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
3061916_0611 Subjecttomodications 6.6701.615
GB
Installation and
operating instructions
Programming module BM-Solar
Wolf GmbH · Postfach 1380 · D-84048 Mainburg · Tel. +49-8751/74-0 · Fax +49-8751/741600 · Internet: www.wolf-heiztechnik.de
2 3061916_0611
Index
Safety instructions / Standards...............................................3
Standards / Regulations ..........................................................4
Installation
• Applicationrange...........................................................5
• Moduleinstallation.........................................................5
• Asaremotecontrol........................................................5
• Wallmountingbase.......................................................5
• Remotecontrolpowersupply........................................6
Overview
• Standarddisplay............................................................7
• Statusdisplay................................................................7
Display level
• Informationdisplay(Infokey).........................................8
• DisplayvaluesSM1.......................................................9
• DisplayvaluesSM2.......................................................9
• Descriptionofdisplayvalues................................. 10-13
Parameter level
• Accesstotheparameterlevel.....................................14
• SM1parameters..........................................................15
• SM2parameters.................................................... 16-17
System ON / OFF ....................................................................18
Specication ...........................................................................18
Troubleshooting .....................................................................19
3061916_0611 3
Thefollowingsymbolsareusedinconjunctionwiththeseimportant
instructions concerning personal safety as well as operational
reliability.
"Safetyinstructions"areinstructionswithwhichyoumustcomply
exactly,topreventinjuryandmateriallosses.
Dangerthrough'live'electricalcomponents.
NBSwitchOFFtheON/OFFswitchbeforeremovingthe
casing.
NevertouchelectricalcomponentsorcontactswhentheON/OFF
switchisintheONposition.Thisbringsariskofelectrocutionthat
maycauseinjuryordeath.
The main supply terminals are 'live' even when the ON / OFF
switchisintheOFFposition.
This indicates technical instructions that you must observe to
preventmateriallossesandboilermalfunctions.
NB
Safety instructions
The appliance and control unit accessories comply with the
followingregulations:
EC Directives
-2006/95/EC LowVoltageDirective
-2004/108/EC EMCDirective
EN Standards
- EN55014-1 Interferenceemissions
-EN55014-2 Resistancetojamming
-EN60529
Standards / Directives
Safety instructions / Standards
4 3061916_0611
Standards / Regulations
-AccordingtoDINEN50110-1,onlyqualiedelectriciansmay
carryouttheinstallationandcommissioningoftheheatingcontrol
unitandconnectedaccessories.
-Observeall regulations specied by your local power supply
utilityandallVDEorlocalregulations.
-DIN VDE 0100 regulations regarding the installation of high
voltagesystemsupto1000V
-DINVDE0105-100operationofelectricalsystems
Installation /
Commissioning
Warnings -Never remove, bypass or disable safety and monitoring
equipment.
-Only operate the system in perfect technical condition.
Immediatelyremove/remedyanyfaultsanddamagethatmay
impactonsafety.
- Alwaysensurethatcoldwaterismixedinwithhotwater,when
theDHWtemperatureissetabove60°C(riskofscalding).
Maintenance / Repair -Regularlychecktheperfectfunctionofallelectricalequipment.
-Onlyqualiedpersonnelmayremovefaultsorrepairdamage.
-OnlyreplacefaultycomponentsorequipmentwithoriginalWolf
spareparts.
AnydamageorlossresultingfromtechnicalmodicationstoWolf
controlunitsisexcludedfromourliability.
NB
Observethefollowinginformationregardingthedisposaloffaulty
systemcomponentsorthesystemattheendofitsservicelife:
Dispose of all components in accordance with applicable
regulations,i.e.separatematerialgroupscorrectly.Theaimshould
bethemaximumpossibleamountofbasicmaterialsrecycledand
thelowestpossibleenvironmentalimpact.
Neverthrowelectricalorelectronicscrapintothehouseholdwaste,
butrecycleitappropriately.
Generally, dispose of materials in the most environmentally
responsible manner according environmental, recycling and
disposalstandards.
Disposal and recycling
3061916_0611 5
Installation
TheBM-Solar programmingmodule canbe integratedinto the
SMsolarmoduleorcanbeusedasremotecontrolinconjunction
withawallmountingbase.
WhenintegratingtheBM-Solarinthesolarmodule,allsettings
aremadeatthesolarmodule.
The electrical connection must only be carried out by a
qualiedelectrician.
- SwitchOFFthepoweratthesolarmodule
- Removethefaciafromthesolarmodule
- ClicktheBM-Solarprogrammingmoduleintothesolar
moduleasshowninthediagram
- SwitchONthepoweratthesolarmodule
Module installation
Remote control Fittedtoawallmountingbase(partno.2744275),theBM-Solar
programmingunitcanbeusedasaremotecontrol(e.g.inthe
livingroom).
Onlyatwo-wireBUSisrequiredfortheuseasremotecontrol.
Wall mounting base
installation
- Removethewallmountingbasefromitspacking.
- Secure the wall mounting base on a ush-mounting box
(Ø55mm)ordirectlyonthewall.
Wallmountingbase
Fixingholes Fixingholes
6 3061916_0611
Installation
Electrical connection
Remote control
Theelectricalconnectionmustonlybecarriedoutbyaqualied
electrician.
Neverroutesensorleadsalongsidemainspowercables.
- SwitchOFFthepoweratthesolarmodule
- Wire the wall mounting base with a two-core cable (minimum
cross-section0.5mm²)inaccordancewiththediagramshown
- ClicktheBM-Solarprogrammingmoduleintothewallmounting
baseasshowninthediagram
- SwitchONthepoweratthesolarmodule
green
eBus
Greenplugof
thesolarmodule
Terminalstrip
Wallmountingbase
3061916_0611 7
Overview
Rotary selector with
pushbutton function
ON / OFF
pushbutton
Status display
Solar circuit pump
Info
pushbutton
▪ Inthetoplineofthestandarddisplay,thecurrentsolar cylinder
temperature is shown; the bottom line shows the current
collector temperature.
▪ Insystemswithtwocylinders,thesolarcylindertemperatureof
cylinder1isshown.
▪ Insystemswithtwocollectorarrays,thecollectortemperature
ofcollectorarray1isshown.
▪ The BUS symbol indicates that a BUS connection exists
betweentheprogrammingmoduleandtheSMsolarmodule.
TheBUSconnectionisfaultyifthissymbolisnotdisplayed.
Thiswouldpreventthesolarmodulefrombeingoperated.
An arrow on the status display signals which output of the
connectedsolarmoduleiscurrentlyactive.
Standard display
Solarcylindertemperature,cylinder1
BUSsymbol
Collectortemperature,collectorarray1
Statusdisplay,outputA4
Statusdisplay,solarcircuitpump1and
outputsA1-A3
Display
In conjunction with
Status display SM1 solar module SM2 solar module
Solarcircuitpump Solarcircuitpump1
A1 - OutputA1*
A2 - OutputA2*
A3 - OutputA3*
-** - OutputA4*
Status display
* Outputassignmentsubjecttoconguration.
** AnactiveoutputA4issignalledbyanarrowpointingdownwards.
8 3061916_0611
Display level
Example:displayvalueA01
Inadditiontothevaluesshownonthestandarddisplay,further
values for the solar thermal system can be scanned at the
BM-Solar.
PressingtheInfo keyleadstothedisplaylevel.Thedisplayvalue
A01(solarcylindertemperature,cylinder1)isshown.
Information display
PressingtheInfokeyagainorturningtherotaryselectorclockwise
enablesalladditionaldisplayvaluestobescannedinsequence.
If the nal display value is reached and the selector further is
turnedfurther,thesystemexitsthedisplaylevelandreturnsto
thestandarddisplay.Thestandarddisplayreturnsautomatically
ifnofurtheractivityisdetectedwithinthenextminute.
Press
Rotary selector with
pushbutton function
Info key
3061916_0611 9
Display Designation
A : 0 1
ActualDHWtemperature,solarcylinder(°C)
A : 0 2
Max.DHWtemperature,solarcylinder(°C)
A : 0 3
Collectortemperature(°C)
A : 0 4
Maximumcollectortemperature(°C)
A : 0 5
Returntemperature(°C)
A : 0 6
Solarcircuitowrate(l/min)
A : 1 0
Hoursrun,solarcircuitpump(h)
A : 1 2
Currentoutput(kW)
A : 1 3
Currentdayyield(kWh)
A : 1 4
Totalyield(Wh)
A : 1 5
Totalyield(kWh)
A : 1 6
Totalyield(MWh)
A : 1 7
Solarheatingstatus
(0=unsuccessful,1=successful)
Display values used with
SM1 solar module
Subject to the solar module used, different display values are available.
Display Designation
A : 0 1
ActualDHWtemperatureinsolarcylinder1(°C)
A : 0 2
Max.DHWtemperature,solarcylinder1(°C)
A : 0 3
Collectortemperature,collectorarray1(°C)
A : 0 4
Maximumcollectortemperature,collectorarray1(°C)
A : 0 5
InputE1*
A : 0 6
InputE2:solarcircuitowrate(l/min)
A : 0 7
InputE3*
A : 0 8
MaximumDHWtemperature,solarcylinder2(°C)
A : 0 9
Maximumcollectortemperature,collectorarray2(°C)
A : 1 0
Hoursrun,solarcircuitpump1(h)
A : 1 1
Hoursrun,solarcircuitpump2(h)
A : 1 2
Currentoutput(kW)
A : 1 3
Currentdayyield(kWh)
A : 1 4
Totalyield(Wh)
A : 1 5
Totalyield(kWh)
A : 1 6
Totalyield(MWh)
A : 1 7
Solarheatingstatus,cylinder1
(0=unsuccessful, 1=successful)
A : 1 8
Solarheatingstatus,cylinder2
(0=unsuccessful, 1=successful)
A : 1 9
MaximumDHWtemperature,solarcylinder3(°C)
A : 2 0
Hoursrun,solarcircuitpump3(h)
A : 2 1
Solarheatingstatus,cylinder3
(0=unsuccessful,1=successful)
*AssignmentofinputsE1andE3subjecttothecongurationselectedattheSM2.
Display values used with
SM2 solar module
Note:DisplayA19toA21onlyeffectivefromsoftwareversion
SM1/SM2228_04.
Display level
10 3061916_0611
SM1: Thecurrenttemperatureofthesolarcylinderatthelevelof
thesolarindirectcoilisdisplayed.
SM2: Thecurrenttemperatureofsolarcylinder1atthelevelof
thesolarindirectcoilisdisplayed.
A : 0 1
SM1: Actual
DHWtemperature
Solarcylinder
SM2: DHW
Actualtemperature
Solarcylinder1
SM1: ThemaximumDHWtemperatureoverthecourseof24hours
isdisplayed.
SM2: The maximum DHW temperature of cylinder 1 over the
courseof24hoursisdisplayed.
Thisvalueisresetevery24hours.
A : 0 2
SM1: Maximum
DHWtemperature
Solarcylinder
SM2: Maximum
DHWtemperature
Solarcylinder1
SM1: Thecurrenttemperaturecapturedattheoutlet(ow)ofthe
collectororcollectorarrayisdisplayed.
SM2: Thecurrenttemperaturecapturedattheoutlet(ow)ofthe
collectororcollectorarray1isdisplayed.
A : 0 3
SM1: Collectortemperature
SM2: Collectortemperature,
collectorarray1
SM1: The maximum collector temperature over the course of
24hoursisdisplayed.
SM2: The maximum collector temperature of collector array 1
overthecourseof24hoursisdisplayed.
Thisvalueisresetevery24hours.
A : 0 4
SM1: Maximumcollector
temperature
SM2: Maximumcollector
temperature
Collectorarray1
SM1: Thecurrenttemperatureofthesolarcircuitreturnisdisplayed.
Thisvalueisrequiredforcalculatingtheyield.
SM2: The current value captured by the sensor connected
to input E1 is displayed. Subject to the conguration
set at the SM2, this may be the return temperature, the
actual DHW temperature of solar cylinder 2, the actual
DHW temperature of solar cylinder 3 or the heating
temperature.
Thisvaluewillonlybedisplayedifatemperaturesensor
hasbeenconnected.
A : 0 5
SM1: Returntemperature
SM2: InputE1
SM1/ Thecurrentowrateinl/min(litresperminuteisdisplayed.
SM2: This display is only shown if value 1 or 2 has been
selectedforparameter08(capturingtheamountofheat).
Thisvalueisrequiredforcalculatingtheyield.
A : 0 6
Solarcircuitowrate
Description of the display values
Display level
3061916_0611 11
SM1: Notinstalled
SM2: The maximum DHW temperature of cylinder 2 over the
courseof24hoursisdisplayed.
Thisvalueisresetevery24hours.
A : 0 8
SM1: Notinstalled
SM2: MaximumDHW
temperature
Solarcylinder2
SM1: Notinstalled
SM2: The maximum collector temperature of collector array 2
overthecourseof24hoursisdisplayed.
Thisvalueisresetevery24hours.
A : 0 9
SM1: Notinstalled
SM2: Maximumcollector
temperature
Collectorarray2
SM1: Theoverallhoursrunbythesolarcircuitpumparedisplayed.
SM2: Theoverallhoursrunbysolarcircuitpump1aredisplayed.
Thisvaluecorrespondstothedisplay value x 10.
Thisvaluecanberesetto0bypressingandholdingdown
therotaryselectorforatleast10seconds.
A : 1 0
SM1: Hoursrun
Solarcircuitpump
SM2: Hoursrun
Solarcircuitpump1
SM1: Notinstalled
SM2: Theoverallhoursrunbysolarcircuitpump2aredisplayed.
Thisvaluecorrespondstothedisplay value x 10.
Thisvaluecanberesetto0bypressingandholdingdown
therotaryselectorforatleast10seconds.
A : 1 1
SM1: Notinstalled
SM2: Hoursrun
Solarcircuitpump2
SM1/ Thecurrentoutputofthesolarcircuitisdisplayed.
SM2:Thisvalueisonlyavailableifareturnsensororaheatmeter
sethasbeenconnectedtotheassociatedSMsolarmodule,
andvalue1or2hasbeenselectedforparameter08.
A : 1 2
Currentoutput
SM1: Notinstalled
SM2: The current value captured by the sensor connected
to input E3 is displayed. Subject to the conguration
set at the SM2, this may be the buffer temperature, the
actualDHWtemperatureofsolarcylinder2,thecollector
temperatureofcollectorarray2orthebypasstemperature.
Thisvaluewillonlybedisplayedifatemperaturesensor
hasbeenconnected.
A : 0 7
SM1: Notinstalled
SM2: InputE3
Display level
12 3061916_0611
SM1/ Theyieldforthecurrentdayisdisplayed.Thisvalue
SM2: isonlyavailableifareturnsensor,aheatmetersetoran
externalheatmeterhasbeenconnectedtotheassociated
SMsolarmodule,andvalue1,2,3or4hasbeenselected
forparameter08.Inaddition,afurther BMprogramming
modulewithaddress0oraradioclockreceiver(accessory)
mustbeinstalledintheoverallsystem.
Thisvaluecanberesetto0bypressingandholdingdownthe
rotaryselectorforatleast10seconds.
A : 1 3
Currentdayyield
SM1/ Thesethreedisplaysshowtheentireyieldachieved
SM2: bythesolarthermalsystem.Thevalueiscomposedofthe
threevaluesthataredisplayed.
Example:A14=350,A15=12,A16=0
Totalyield=350Wh+12kWh+0MWh=12.35kWh
Thesevaluescanberesetto0bypressingandholdingdownthe
rotaryselectorforatleast10seconds.
Thesevaluesareonlyavailableifareturnsensor,aheatmeterset
oranexternalheatmeterhasbeenconnectedtotheassociated
SMsolarmodule,andvalue1,2,3or4hasbeenselectedfor
parameter08.
A : 1 4
TotalyieldinWh
A : 1 6
TotalyieldinMWh
A : 1 5
TotalyieldinkWh
SM1: Thisindicateswhetherasolarheatingprocesshasbeen
completedsuccessfullywithinthelast24hours.
SM2: Thisindicateswhethersolarheatingofcylinder1hasbeen
completedsuccessfullywithinthelast24hours.
This applies if, within 24 hours prior to 14:00 h, the set DHW
temperatureselectedattheheatingappliancewasexceededby
solarheating.
Inthatcase,thesetDHWtemperatureattheheatingappliance
willbesettotheminimumcylindertemperature(cylinderreheating
blocked).
Thisfunctionisonlyavailableifthesolarmoduleisoperatedas
partofaWolfcontrolsystem(forafunctiondescription,seethe
SMsolarmodulemanual).
A : 1 7
SM1: Solarheatingstatus
SM2: Solarheatingstatus
Cylinder1
A : 1 8
SM1: Notinstalled
SM2: Thisindicateswhethersolarheatingofcylinder2hasbeen
completedsuccessfullywithinthelast24hours.
This applies if, within 24 hours prior to 14:00 h, the set
DHWtemperatureselectedattheheatingappliancewasexceeded
bysolarheating.
Inthiscase,thesetDHWtemperatureattheheatingappliance
willbesettotheminimumcylindertemperature(cylinderreheating
blocked).
Thisfunctionisonlyavailableifthesolarmoduleisoperatedas
partofaWolfcontrolsystem(forafunctiondescription,seethe
SMsolarmodulemanual).
SM1: Notinstalled
SM2: Solarheatingstatus
Cylinder2
Display level
3061916_0611 13
A : 1 9
SM1: Notinstalled
SM2: The maximum DHW temperature of cylinder 3 over the
courseof24hoursisdisplayed.
Thisvalueisresetevery24hours.
SM1: Notinstalled
SM2: MaximumDHW
temperature
Solarcylinder3
SM1: Notinstalled
SM2: Theoverallhoursrunbysolarcircuitpump3aredisplayed.
Thisvaluecorrespondstothedisplay value x 10.
Thisvaluecanberesetto0bypressingandholdingdown
therotaryselectorforatleast10seconds.
A : 20
SM1: Notinstalled
SM2: Hoursrun
Solarcircuitpump3
A : 21
SM1: Notinstalled
SM2: Thisindicateswhethersolarheatingofcylinder3hasbeen
completedsuccessfullywithinthelast24hours.
This applies if, within 24 hours prior to 14:00 h, the set
DHWtemperatureselectedattheheatingappliancewasexceeded
bysolarheating.
Inthiscase,thesetDHWtemperatureattheheatingappliance
willbesettotheminimumcylindertemperature(cylinderreheating
blocked).
Thisfunctionisonlyavailableifthesolarmoduleisoperatedas
partofaWolfcontrolsystem(forafunctiondescription,seethe
SMsolarmodulemanual).
SM1: Notinstalled
SM2: Solarheatingstatus
Cylinder3
Display level
14 3061916_0611
Parameter level
Turningtherotaryselectorclockwisescansallfurtheravailable
parametersinsequence.
Changing parameters:
▪ Pressingtherotaryselectoragainenablesthecurrently
displayedparameter.
Thedisplayofthecorrespondingvalueashes.
▪ Turningtherotaryselectorenablesyoutomodifythevalue.
▪ Pressingtherotaryselectoragainconrmsthevalue.The
valuedisplaythenchangesfromashingtostatic.
TheparameterlevelcanbeexitedbypressingtheInfokey.
Theparameterlevelwillalsobeterminatedifnofurtheractivityis
detectedwithinoneminute.
Access to the
parameter level
Atthe parameter level, all values thatcan be modied can be
checkedandchangedifrequired.
Theparameterlevelisactivatedbypressingtherotaryselectoronce.
ParameterP01appears
(startdifferentialsolarcylinder1).
Display(factorysetting):
Rotary selector with
Example:parameterP01
pushbutton function
3061916_0611 15
Subject to the solar module used, different parameters are available.
Parameters used with SM1 solar module:
Parameter
BM
Parameter
BM-Solar
Explanation
Setting range Factory
setting
min. max.
SOL 01 P 01
Startdifferentialsolarcylinder 5K 30K 8K
SOL 02 p 02
Stopdifferentialsolarcylinder 2K 20K 4K
SOL 03 P 03
Collectorcoolingfunction 0(OFF) 1(ON) 0
SOL 04 P 04
Criticalcollectortemperature 90°C 150°C 110°C
SOL 05 P 05
Maximumcollectortemperature 100°C 150°C 130°C
SOL 06 P 06
Maximumcylindertemperature,
solarcylinder
15°C 90°C 60°C
SOL 07 P 07
Assignment,solarcylinder 0 8 0
SOL 08 P 08
Capturingtheamountofheat 0(OFF) 4 0
SOL 09 P 09
P 08=0→P 09 Notadjustable
P 08=1→
Pulsevalue,pulsegenerator
P 08=2→
Constantflowrate
P 08=3or4→
Pulsevalue
externalheatmeter
0l/pulse
0l/min
-2
99.5l/pulse
99.5l/min
1
1l/pulse
1l/min
0
SOL 10 P 10
Glycolselection:
0=Water
1=TyfocorL(Anro)
2=TyfocorLS(AnroLS)
3=Propyleneglycol
4=Ethyleneglycol
0 4 1
SOL 11 p 11
BUSfeed 0 2 2
SOL 27 * p 27 *
Tubecollectorfunction 0(OFF) 2 0
SOL 28 * p 28 *
Frostprotectionfunction 0(OFF) 1(ON) 0
SOL 33 * P 33 *
Hysteresis,solarcylinder 0.5K 5K 1K
SOL 36 * P 36 *
Solarcylinderemergency
shutdown
60°C 95°C 95°C
SOL 39 * P 39 *
Minimumcollectorlimit -25°C 90°C 10°C
SOL 41 * P 41 *
Functioncheck,owrate 0(OFF) 1(ON) 0
SOL 42 * P 42 *
Functioncheck,gravitybrake 0(OFF) 60°C 40°C
SOL 44 * P 44 *
Reversecoolingfunction 0(OFF) 1(ON) 0
SOL 51 * P 51 *
Proportionofglycolinwater
P 10=0→P 51 Notadjustable
P 10 =1:TyfocorL(Anro)
P 10 =2→P 51 Notadjustable
P 10 =3→P 51 Notadjustable
P 10 =4→Ethyleneglycol
----
20 %
----
----
20 %
----
75%
----
----
80 %
----
45%
----
----
45%
SOL 6O p 60
Relaytest 1 5 1
Parameter level
For function descriptions of the individual parameters, see the SM solar module instruction
manual.
*ParametersonlyeffectivefromsoftwareversionSM1/SM2228_04.
16 3061916_0611
Parameter
BM
Parameter
BM-Solar
Explanation
Setting range Factory
setting
min. max.
SOL 01 P 01
Startdifferentialsolarcylinder1 5K 30K 8K
SOL 02 p 02
Stopdifferentialsolarcylinder1 2K 20K 4K
SOL 03 P 03
Collectorcoolingfunction 0(OFF) 1(ON) 0
SOL 04 P 04
Criticalcollectortemperature 90°C 150°C 110°C
SOL 05 P 05
Maximumcollectortemperature 100°C 150°C 130°C
SOL 06 P 06
Maximumtemperature,solar
cylinder1
15°C 90°C 60°C
SOL 07 P 07
Assignment,solarcylinder1 0 8 0
SOL 08 P 08
Capturingtheamountofheat 0(OFF) 4 0
SOL 09 P 09
P 08=0→P 09 Notadjustable
P 08=1→
Pulsevalue,pulsegenerator
P 08=2→
Constantflowrate
P 08=3or4→
Pulsevalue
externalheatmeter
0l/pulse
0l/min
-2
99.5l/pulse
99.5l/min
1
1l/pulse
1l/min
0
SOL 10 P 10
Glycolselection:
0=Water
1=TyfocorL(Anro)
2=TyfocorLS(AnroLS)
3=Propyleneglycol
4=Ethyleneglycol
0 4 1
SOL 11 p 11
BUSfeed 0 2 2
SOL 12 p 12
Conguration 1 14 1
SOL 13 p 13
Speedcontrol,solarcircuitpump 0(OFF) 1(ON) 0
SOL 14 p 14
Startdifferentialsolarcylinder2 5K 30K 8K
SOL 15 p 15
Stopdifferentialsolarcylinder2 2K 20K 4K
SOL 16 p 16
Maximumtemperature,solar
cylinder2
15°C 90°C 60°C
SOL 17 p 17
Assignment,solarcylinder2 0 8 8
SOL 18 p 18
Burnerblockedduring
returntemperatureraising
0s 300s 0s
SOL 19 p 19
Startdifferential,return
temperatureraising
4K 30K 10K
SOL 20 p 20
Stopdifferential,return
temperatureraising
2K 20K 5K
SOL 21 p 21
Prioritysolarcylinder1 0 2 0
SOL 22 p 22
Startdifferential
parallelcylinderoperation
20K 60K 30K
SOL 23 p 23
Differentialtemperature,bypass 8K 50K 15K
SOL 24 p 24
FunctionoutputA4 0(OFF) 3 0
SOL 25 p 25
Starttemperature,thermostat
function
30°C 90°C 50°C
SOL 26 p 26
Stopdifferential,thermostat
function1/2
5K 30K 10K
SOL 27 p 27
Tubecollectorfunction 0(OFF) 2 0
SOL 28 p 28
Frostprotectionfunction 0(OFF) 1(ON) 0
Parameters used with SM2 solar module:
Parameter level
3061916_0611 17
SOL 29 * p 29 *
Startdifferentialsolarcylinder3 5K 30K 8K
SOL 30 * P 30 *
Stopdifferentialsolarcylinder3 2K 20K 4K
SOL 31 * P 31 *
Maximumtemperature,solar
cylinder3
15°C 90°C 60°C
SOL 32 * P 32 *
Assignment,solarcylinder3 0 8 8
SOL 33 * P 33 *
Hysteresis,solarcylinder1 0.5K 5K 1K
SOL 34 * P 34 *
Hysteresis,solarcylinder2 0.5K 5K 1K
SOL 35 * P 35 *
Hysteresis,solarcylinder3 0.5K 5K 1K
SOL 36 * P 36 *
Solarcylinderemergencyshutdown1
60°C 95°C 95°C
SOL 37 * P 37 *
Solarcylinderemergencyshutdown2
60°C 95°C 95°C
SOL 38 * P 38 *
Solarcylinderemergencyshutdown3
60°C 95°C 95°C
SOL 39 * P 39 *
Minimumcollectorlimit -25°C 90°C 10°C
SOL 40 * P 40 *
Minimumbufferlimit 10°C 90°C 10°C
SOL 41 * P 41 *
Functioncheck,owrate 0(OFF) 1(ON) 0
SOL 42 * P 42 *
Functioncheck
Gravitybrake
0(OFF) 60°C 40°C
SOL 43 * P 43 *
Lowerpumprate 28 % 100 % 30 %
SOL 44 * P 44 *
Reversecoolingfunction 0(OFF) 1(ON) 0
SOL 45 * P 45 *
Selectioncylinderthermostat
function
1 3 1
SOL 46 * P 46 *
Prioritysolarcylinder2 0 2 1
SOL 47 * P 47 *
Cylinderoperatingmode 1 3 2
SOL 48 * P 48 *
Cyclicalheatingtime 0min. 60min. 30min.
SOL 49 * P 49 *
Idletime 0min. 60min. 5min.
SOL 50 * P 50 *
Blockingtime,solarcircuit pump
orelectricalvalve
0s 300s 90s
SOL 51 * P 51 *
Proportionofglycolinwater
P 10=0→P 51 Notadjustable
P 10 =1:TyfocorL(Anro)
P 10 =2→P 51 Notadjustable
P 10 =3→P 51 Notadjustable
P 10 =4→Ethyleneglycol
----
20 %
----
----
20 %
----
75%
----
----
80 %
----
45%
----
----
45%
SOL 52 * P 52 *
Cylinder switching with external
cylinderheating
0 1 0
SOL 53 * P 53 *
Samplinginterval 1s 60s 10s
SOL 54 * P 54 *
Internalpumpspeed 5% 20 % 5%
SOL 55 * P 55 *
Upperpumprate 50% 100 % 100 %
SOL 6O p 60
Relaytest 1 5 1
Parameter
BM
Parameter
BM-Solar
Explanation
Setting range Factory
setting
min. max.
For function descriptions of the individual parameters, see the SM solar module instruction
manual.
*ParametersonlyeffectivefromsoftwareversionSM1/SM2228_04.
Parameter level
18 3061916_0611
System ON / OFF
The solar module can be switched ON and OFF with the
ON / OFF pushbutton.
To prevent the system being switched OFF accidentally, the
pushbuttonneedstobehelddownforatleast3secondstoeffect
ashutdown.Abriefactivationofthepushbutton is sufcientto
startthesystemagain.
Whenthesystemisshutdown,thedisplayshowsoff insteadof
thecollectortemperature.
Example:
System ON / OFF
NB
In the shutdown state, no protective functions are enabled
(except anti-seizing pump protection).
Specication Supplyvoltage: eBUS15–24V
Powerconsumption: Max.0.5W
Protection: Withwallmountingbase:IP30
Moduleinstallation:IP30
Ambienttemperature: 0....50°C
Storagetemperature: -20....+60°C
Specication
3061916_0611 19
Troubleshooting
Thestandarddisplaywillreturnwhenthefaulthasbeenremoved.
Thefollowingfaultmessagescanoccuratthesolarmodule:
Fault codes Iffaultsoccur atthe SMsolar module,the correspondingfault
codeandawarningsymbolwillashonthedisplay.
Example:
ashing
Fault
code
Fault Cause Remedy
FC62 Functioncheck,owrate(noow) Toolittleorno
throughput
Checksolarcircuitpump
FC63 Functioncheck,gravitybrake Faultygravitybrake Checkgravitybrake
FC64
applies
onlyto
P08=1
Pulsegeneratorfaulty Pulsegeneratororcable
faulty
Checkpulsegenerator
andcable;replaceif
required
FC71 SM1: TerminalSFS,solarsensor Faultysensororlead Checksensorandlead;
replaceifrequired
Cylinderfaulty
SM2: TerminalSFS1
Solarsensor
Cylinder1faulty
FC72 SM1: TerminalRLF,returnsensor
faulty
Faultysensororlead Checksensorandlead;
replaceifrequired
SM2: TerminalE1,sensoron
inputE1faulty
FC73 SM1: N/A Faultysensororlead Checksensorandlead;
replaceifrequired
SM2: TerminalE3,sensoron
inputE3faulty
FC74 DCFsignalorreception
interference
NoBUSconnection;no
DCFreception
CheckeBUS
connection/DCF
reception
FC79 SM1: TerminalSFK,solarsensor Faultysensororlead Checksensorandlead;
replaceifrequired
Collectorfaulty
SM2: TerminalSFK1,solar
sensor
Collectorarray1faulty
FC81 EEPROMfault Parametervalues
outsidevalidrange
Resettostandard
valuesbybriey
interruptingthepower
supply,andcheck
values
Note:
Faultcodes71,72,79,73,64,62and74areresetautomaticallyassoonastheircausehas
beenremoved.Faultcodes63and81mustbereset(acknowledged)explicitlybyrestartingthe
SM.Alternatively,FC63canberesetviatheBM-Solar(byholdingdowntherotaryselectorforat
least5seconds).