WARNINGS AND CAUTIONS:
• Tobeinstalledand/orusedinaccordancewithappropriateelectricalcodesandregulations.
• Ifyouareunsureaboutanypartoftheseinstructions,consultaqualiedelectrician.
• Controllingaloadinexcessofthespeciedratingswilldamagetheunitandposeriskofre,electricshock,personalinjuryordeath.
Checkyourloadratingstodeterminesuitabilityforyourapplication.
• Donotinstallthisunittocontrolareceptacle.
WARNINGS AND CAUTIONS:
• TheOSSMT-GDOccupancySensorisintendedtoreplaceastandardsingle-poleDecorawallswitch.
• Donottouchthesurfaceofthelens.Cleanoutersurfacewithadampclothonly.
• Disconnectpoweratcircuitbreakerorfusewhenservicing,installingorremovingxture.
• Usethisdeviceonlywithcopperorcoppercladwire.WithaluminumwireuseonlydevicesmarkedCO/ALRorCU/AL.
SinglePole(OneLocation)orMulti-Location
Multi-Technology Designer Wall Switch Occupancy Sensor
California Title 24 2005 Compliant
Cat. No. OSSMT-GD
Incandescent/Tungsten:800W@120VBallast:1200VA@120VBallast:2700VA@277VMotor:1/4hp@120V
Operating Temperature Range:0°Cto50°C
Relative Humidity:20%to90%non-condensing
No Minimum Load Required
Compatiblewithincandescentlamps,low-voltagelightingwithelectronicandmagnetictransformers,electronicandmagneticuorescentballasts,andfans.
INSTALLATION INSTRUCTIONS
TOOLS NEEDED TO INSTALL YOUR SENSOR
Slotted/PhillipsScrewdriver ElectricalTape
Pliers Cutters
SmallSlottedScrewdriver
• Leviton’sDecora
®
styledesign
• Sensorcanbegangedtogetherwithotherunitsinamultiple-switch
wallplate.
• Self-AdaptiveTechnologyadjuststooccupancypatternsofusein
autoadaptmode.
• TheAdaptingTime-outwalk-throughfeaturepreventslightsfrom
remainingONforanextendedperiodafteronlyamomentary
occupancy.
• Switchesasingleloadcircuit.
• OnePush-ButtonwhichprovidesmanualON/OFFswitchingat
anytime.
• Adjustablehorizontaleldofview.
• IntegratedphotocellpreventslightsfromturningONwhenroomis
adequatelyilluminatedbynaturallight.
• TrueZero-Crossrelayprovidesmaximumcontactlifeand
compatibilitywithelectronicballasts.
• Dualdetectiontechnology,bothPassiveInfraredandUltrasonic.
CanbeconguredasUltrasonicOnlybydisablingPassive
Infrared.
Leviton'sDesignerMulti-TechnologyWallSwitchOccupancySensor,
Cat.No.OSSMT-GD,isdesignedtodetectmotionusingthepassive
infrared(PIR)sensorfromsources(suchasapersonenteringa
room)withinitseld-of-view(monitoredspace)andautomatically
switchlightsON.TheOccupancySensorsensesmotionwithinits
maximumcoverageareaof2400sq.ft(223m
2
).Theultrasonic(US)
sensorsworkwiththePIRtokeepthelightsONwhenoccupied.The
controlledlightswillremainONuntilnomotionisdetectedandthe
scheduledtime-delayhasexpired,atwhichpointthelightswillbe
turnedOFF.Inadaptingtime-outmodethesensoradaptsitstime
delaysettingstotheoccupancypatternsofaroom.
TheCat.No.OSSMT-GDisanOccupancySensorthatisdesignedto
controlasinglelightingcontrolcircuitandprovidetheenergysavings
ofanoccupancysensor.Thisdevicedoesnotcontainaneutral
conductor.Itisintendedforuseinretrotapplicationswhereaneutral
isnotavailableinthewallbox.
TheOSSMT-GDisasinglerelaydevice,whichcanbeAutoONor
ManualON.ThedevicecontainsaphotocellthatprovidesanAmbient
LightHoldOfffunction.ThedeviceiscongurableforeitherUltrasonic
withPIRorUltrasonicOnlymodesofoperation.
Cat. No. OSSMT-GD is ETL listed, cETL listed and conforms to
California Title 24 requirements.
ThePIROccupancySensorusesasmallsemiconductorheatdetector
thatresidesbehindamulti-zoneopticallens.ThisFresnellens
establishesdozensofzonesofdetection.TheSensorissensitivetothe
heatemittedbythehumanbody.InordertoinitiallytriggertheSensor,
thesourceofheatmustmovefromonezoneofdetectiontoanother.
Thedeviceismosteffectiveinsensingmotionacrossitseld-of-view
anditislesseffectivesensingmotiontowardsorawayfromitseld-of-
view).Keepthisinmindwhenselectingtheinstallationlocation(refer
to Field-of-View diagrams).
TheUSOccupancySensorusesanon-audible,highfrequency(40kHz)
tosenseDopplershiftscausedbymotioninthespace.TheUSismore
sensitivetosmallmotionanddoesnotrelyonlineofsightfordetection.
Ifbothsensorshavenotdetectedanymotionforthesettimeoutperiod,
therelayanditscorrespondingloadwillbeturnedOFF.
Notethatoccupancysensorsrespondtorapidchangesintemperature,
socareshouldbetakennottomountthedevicenearaclimatecontrol
source(i.e.radiators,airexchanges,andairconditioners).Hotorcold
draftswilllooklikebodymotiontothedeviceandwilltriggeritiftheunit
ismountedtooclose.It is recommended to mount the Occupancy
Sensor at least 6 feet away from a climate control source.
Inaddition,itisalsorecommendedNOTtomounttheOccupancySensor
directlyunderalargelightsource.Largewattagebulbs(greaterthan
100Wincandescent)giveoffalotofheatandswitchingthebulbcauses
atemperaturechangethatcanbedetectedbythedevice.Mountthe
OccupancySensoratleast6ft.awayfromlargebulbs.Ifitisnecessary
tomountthedevicecloser,lowerthewattageofthebulbdirectly
overhead.
WARNING:TO AVOID FIRE, SHOCK, OR DEATH; TURN
OFF POWER atcircuitbreakerorfuseandtestthatpoweris
offbeforewiring!
Step 1
/./&&
/./&&
/./&&
/./&&
/./&&
/./&&
/./&&/./&&
/./&&
/./&&
/./&&
/./&&
• Pulloffpre-cutinsulationfromsensorleads.
• Makesurethattheendsofthewiresfromthewallboxarestraight
(cut if necessary).
• Removeinsulationfromeachwireinthewallboxasshown.
Preparing and connecting wires:
9/16"
(1.4 cm)
Strip Gage
(measure bare
wire here)
Cut
(if necessary)
Step 3
INSTALLING YOUR SENSOR
NOTE:UsecheckboxeswhenStepsarecompleted.
Installing your Sensor – Single-Pole Application:
Step 4
Identifying your wiring application
(most common):
Step 2
WIRING SENSOR:
Connect wires per WIRING DIAGRAM as follows:Screwwireconnector
onclockwisemakingsuretherearenobareconductorsbelowthewire
connectors.Secureeachconnectorwithelectricaltape.
• GreenorbarecopperwireinwallboxtoGreenlead.
• LineHotwallboxwiretoBlacklead.
• LoadwallboxwiretoBluelead.
NOTE: Allow 1 minute for warm-up after connecting and energizing.
WIRING SENSOR 1:
Connect wires per WIRING DIAGRAM as follows:
• GreenorbarecopperwireinwallboxtoSensor1Greenlead.
• LineHot(common)wallboxwireidentied(tagged)whenremovingold
switchandFirsttravelerfromSensor2toSensor1Blacklead.
• SecondTravelerwallboxwirefromSensor2toSensor1Bluelead.
WIRING SENSOR 2:
Connect wires per WIRING DIAGRAM as follows:
• GreenorbarecopperwireinwallboxtoSensor2Greenlead.
• Loadwallboxwireidentied(tagged)whenremovingoldswitchand
SecondTravelerfromSensor1toSensor2Bluelead.
• FirstTravelerLineHotfromSensor1toSensor2Blacklead.
NOTE: Allow 1 minute for warm-up after connecting and energizing.
Step 5
NOTE:
TheCat.No.OSSMT-GDrequiresagroundwiretooperateproperly.
Ifthereisnogroundwire,ensureelectricalboxisgroundedandattach
groundwiretoboxwithascrew.Ifthegroundwireisoatingthisdevice
willnotwork.
NOTE:TheCat.No.OSSMT-GDrequiresagroundwiretooperate
properly.Ifthereisnogroundwire,ensureelectricalboxisgroundedand
attachgroundwiretoboxwithascrew.Ifthegroundwireisoatingthis
devicewillnotwork.
NOTE:Sensor1
must
beinstalledinawallboxthathasbothaLINEHot
andaGroundconnection.Sensor2
must
beinstalledinawallboxthat
hasbothaLoadandaGroundconnection.
Ifyouareunsureaboutanypartoftheseinstructions,consultaqualied
electrician.
NOTE:EithersensorcanturnthelightsON.Bothsensorsmusttimeout
toOFForbothmanualbuttonsmustbepressedforthelightstogoOFF
DESCRIPTION
DI-0XX-OSSMT-00A
FEATURES
1
2
3
4
3
2
1
3-Way
1. LineorLoad(Seeimportant*
instruction)
2. Ground
3. FirstTraveler–notecolor
4. SecondTraveler–notecolor
Single-Pole
1.Line(Hot)
2.Ground
3.Load
IMPORTANT:For3-Wayapplications,notethatoneofthescrew
terminalsfromtheoldswitchbeingremovedwillusuallybeadifferent
color(Black)orlabeledCommon.Tagthatwirewithelectricaltapeand
identifyasthecommon(LineorLoad)inbothswitchwallboxes.
Sensor
Green
Blue
Black
1
2
3
Black (Hot)
Neutral (White)
Load
Sensor
Black
Black
White
Blue
Green
Ground
Line
120VAC, 60Hz
Installing your Sensor – 3-Way Wiring Application:
Black (Hot)
Neutral (White)
Load
Sensor 2 Sensor 1
Black
Black
Black
White
Blue Blue
Green
Ground
Green
Ground
Line
120VAC, 60Hz
NOTE:Dresswireswithabendasshownindiagramtorelievestress
whenmountingdevice.
Positionallwirestoprovideroominoutletwallboxfordevice.
• Partiallysecuredeviceusinglongmountingscrewsprovided.
• Restorepoweratcircuitbreakerorfuse.
NOTE: Allow 1 minute for warm-up after energizing.
NOTE:AllmodelsoftheOSSMT-GDarefactorypresettowork
withoutanyadjustments.Ifnecessary,adjusttheBlindersandPIR
RangeControltostopanyunwantedactivationofthelights(refer
to FEATURES section).
• ForadditionalTimeControlSettings(refer to the SETTINGS section).
NOTE:ToavoidPERMANENTDAMAGEtotheunit,becareful
NOTTOOVERTURNthecontrolknobsorleverswhensettingthe
Sensor.Thecontrolscanbeaccessedbyremovingthewallplate
(ifapplicable)andcontrolpanelcover(refer to Control Panel
Diagram).Useasmallstraightbladescrewdrivertoadjustknobs
andblinderlevers.
NOTE: DO NOT pressinonblinderleversoruseexcessiveforce
(refer to Control Panel Diagram).
• AttachtheControlPanelcoverwhenthedesiredsettingsare
complete.
If lights do not turn ON, refer to the TROUBLESHOOTING section.
Testing your Sensor prior to completely
mounting in wall box:
Step 6
NOTE: To access control settings, remove the control panel cover.
If necessary, remove the warning label that covers the adjustment
dials (refer to Control Panel Diagram).
Factory Settings:Thesensorisshippedfromthefactorytoworkin
almostallsituations,withoutanyaddedadjustments.Thefactorysettings
are:Blindersopen,10minutesxedTime-Out,LightsalwaysturnON
regardlessofexistinglightlevels,Mediumpassiveinfrared(PIR)range,
andHighUltrasonicrange.ThePIRandultrasonictechnologiesareboth
active.
Blinders:Theblindersaretwoindependentshuttersthatcannarrow
theeld-of-viewfromamaximumof180°downto32°.Theblindersare
operatedbymovingtheblinderleverstowardsorawayfromthecenterof
theSensor.Theblinderleverscanbefoundabovethecontroldialsinthe
controlpanel(refer to Control Panel Diagram).
Time-Outs:TheSensorhasthreetypesofTime-Outs:Fixed,Adapting,
andWalkthrough.
• FixedTime-Out:ThevalueofthisTime-Outisuserselected
throughtheuseoftheTimeControlSetting(refertoControlPanel
DiagramandTime-OutSettings).
FEATURES
Mounting
screws
(2 places)
Wall surface
Sensor
Sensor 1
Green
Blue
Black
4
3
2
1
Sensor 2
Green
Blue
Black
4
3
2
1
• Adapting Time-Out:Whenactivated,thevalueofthisTime-Out
(30minutes)ischangedbytheSensorbasedonroomoccupancy
andlightingconditions.
• Walk-through Time-Out:ThevalueofthisTime-Outispresetto
2.5minutesandonlyexistsintheAdaptingTime-Outmode.
Fixed Time Delay:ThexedTime-Outvalueisselectedbyrotatingthe
TimeControldial.Therearefour(4)valuesfromwhichtochoose.Each
markaroundthedialcorrespondstoadifferentvalueasindicatedbelow
(refer to Control Panel Diagram).
NOTE:Alltimedurationsareapproximatewithin±10seconds.
Adapting Time Delay:TheSensorhasbuiltinadaptingintelligencethat
changestheAdaptingTime-Outdurationinresponsetotheoccupancy
conditionsoftheroomitisinstalledin.IftheSensordetects“large,”
infrequentmotionitwillINCREASEtheAdaptingTime-Outduration.If
theSensordetects“large,”frequentmotion(asinseveralpersonsina
roomduringameeting),itwillDECREASEthetime-outdurationonlyifit
wasNEVERincreased(thisisbecausethebuiltinintelligencewillalways
proceedinthedirectionof“increasing”adaptingTime-Outonceithas
increaseditforanyoftheoccupancyconditionssensed).TheAdapting
Time-Outdurationwillrangefrom10to30minutesintimeplustheWalk-
ThroughTimeDelay.
Walk-Through Time Delay:Thewalk-throughfeaturewhichisonly
activeintheAdaptingTime-Outmode,isusefulwhenaroomis
momentarilyoccupied.Withthisfeature,theSensorwillturnthelights
OFFshortlyafterthepersonleavestheroom.Thewalk-throughfeature
worksinthefollowingmanner:Whenapersonenterstheroom,thelights
willturnON.Ifthepersonleavestheroombeforethewalk-throughtime-
outof2.5minutes,theSensorwillturnthelightsOFFafter2.5minutes.If
thepersonstaysintheroomforlongerthan2.5minutes,theSensorwill
insteadusethestoredAdaptingTime-OutDelaysetting.
IftheSensordetectsmotionwithin30secondsafterthelightsturnOFF,
itwillturnthelightsONandincreasethetime-outvalueby1.5timesthe
existingvalue.
TheAdaptingTime-Outmayberesettothebasevalueof30minutesby
rotatingtheTimeControltoanewtimeselectionvalueandthenbackto
theAdaptingTime-Outvalue(refer to Control Panel Diagram).
Ambient Light Override:TheAmbientLightOverrideisusedtokeep
thelightsOFFifthereisalreadyenoughnaturallightintheroom.
Forproperoperation,theAmbientLightOverrideadjustmentmustbe
performedwhenthereisenoughnaturallight(refer to the SETTINGS
section).Iftheadjustmentismadewhenthereislessnaturallight,the
lightsmaynotturnONeventhoughtheyareneededandwillrequire
manualactivationofthepush-buttonstoturnthelightsON.
NOTE:Theambientlightlevelinthecenterofaroomwillbedifferent
thanthelevelatthewallwheretheswitchislocated.
Ambient Light Dial:Theambientlightsettingisadjustedwiththe
AmbientLightDial(refer to Control Panel Diagram).TurningtheLight
Dialfullycounter-clockwise(CCW),setstheSensortomanualONmode
(seefollowingsection).IfthelightcontrolisinthefullyCWposition,the
lightswillturnONwhenevermotionisdetected,eveninfulldaylight.
IntermediatesettingswillcausethelightstoturnONonlywhenthe
ambientlightisbelowthelevelselectedbythelightcontrol.
NOTE:WhenthesettingisattheminimumCCWlevel,thelightswill
stayOFFwhentheroomisdim.Whenthesettingisatthemaximum
levelclockwise(CW),thelightswillturnONwhentheroomisbright.
Manual ON Mode:WhenthelightcontrolisinthefullyCCWposition
thelightswillneverautomaticallyturnON.Inthismodethelightsneed
tobemanuallyturnedONbythepush-button,andwillturnOFFwiththe
absenceofmotion.
PIR RANGE:TodecreasePIRdetectionrangeandsensitivity,rotatethe
knobCCW(refer to Control Panel Diagram).Thedetectionrangecan
beadjustedfrom100%downto30%.
ULTRASOUND (US) SENSITIVIY AND PIR DISABLE:USsensitivity
canbeadjustedtoHIGH-MEDIUM-LOWbyholdingtheONbuttonfor
15seconds.TheLEDwillashtorepresenttheUltrasonicsensitivity
andPIRstatus.TappingtheONbuttonduringthedesiredLEDash
indicationwillsettheUltrasonicsensitivityandPIRstatus.Usethe
followingchart:
TIME
1
2
A
3
RANGE
BLINDERS
LIGHT
4
7
10
4
7
10
Slash Mark
Blinder adjustment levers
Control Panel Cover
PUSH BUTTON(S)
Cat.No.OSSMT-GDxhasasinglepush-buttonswitchthattogglesthe
relayanditscorrespondingload,ONandOFF(refer to figure).Ifthe
relayisOFF,therelaywillturnONwhenthepush-buttonispressed,
andremainONinthepresenceofmotion.Intheabsenceofmotion,the
SensorUnitwillTime-OutandturntherelayOFF.
NOTES:
• TheMotionIndicatorLEDwillblinkeverysecondwhilemotion
isdetected.AredblinkrepresentsPIRdetection,agreenblink
representsUltrasonicdetection.
• WhentheTime-OutexpiresandtherelayturnsOFFa30second
vacancyconrmationexisttoturntherelaybackON.Afterthistime
thedevicewillbeplacedintoalowerdetectionthresholdmode.
• InManual-ONmode,thebuttonmustbepressedtoturnthelightsON.
Intheabsenceofmotion,theunitwillTime-OutandturnthelightsOFF.
• IfManual-Onmodeisdesired,keeptheLightknobinthefully
counter-clockwise(CCW)position.
NOTE:ToavoidPERMANENTDAMAGEtotheunit,becarefulNOT
TOOVERTURNoruseexcessiveforcewhensettingthecontrol
knobsorleversofCatNo.OSSMT-GD.Useasmallstraightblade
screwdrivertoadjusttheknobsandyourngertoadjusttheblinder
levers.
1. RemoveDecora
®
wallplateandControlPanelCoverfromSensor.
2. RotatetheTimedialtoselectthedesiredxedTime-Outvalue.
3. IftheSensorisinstalledwithin6feetofanairduct,rotatetheRange
Control1/4turncounter-clock-wise(CCW).
4. Set the Ambient Light Level - AMBIENT LIGHT:Cat.No.OSSMT-
GDhasanadjustmenttodetermineatwhatminimumambientlight
leveltheunitwilloperate.Theadjustmentshouldbemadewhenthe
ambientlightisatthelevelwherenoarticiallightisneeded.Follow
thesestepstomakeamoreaccurateadjustmentofthelightcontrol.
ThisfeaturewillnotworkinManual-Onmode.
A. WiththelightsON,rotatetheTimeControlfullyCCWtotheset
theTime-Outtothethirty(30)secondtestmode(refer to Control
Panel Diagram).
B. RotatetheLightControlfullyCCW.
C. ManuallyturnOFFthelights.
D. RotatetheLightControlclockwise(CW)SLOWLY,untilthelights
turnON.Thisisthesettingforthecurrentleveloflightintheroom.
Adjustthelightcontrolback(CCW)alittlesothelightswillnotturn
onwiththecurrentroomlightinglevel.Leavetheroomandwait
forthe30-secondtimeoutand30-secondvacancyconrmation
toexpire.Performawalkthroughtoseeifthelightsturnonwith
thenewambientlightleveladjustment.Repeatthisadjustmentas
neededtokeepthelightsfromturningonunderconditionswhen
enoughlightispresent.
 NOTE:WhenthelightcontrolisinthefullyCCWpositionthelights
willneverautomaticallyturnON.ThisistheManual-Onmode,
wherethelightsneedtobemanuallyturnedONbythepush-
button,andwillturnOFFwiththeabsenceofmotion.
  IfthelightcontrolisinthefullyCWposition,thelightswillturnON
whenevermotionisdetected,eveninfulldaylight.
  IntermediatesettingswillcausethelightstoturnONonlywhenthe
ambientlightisbelowthelevelselectedbythelightcontrol.
 NOTE:Theambientlightinaroomwillchangewiththetimeofday
andtheseasonoftheyear.
5. Time-Out Settings:
A. AdjusttheTimedial.TheSensorAmberLEDwillashtwiceeach
timetheTimedialispointedatanewTime-Outvalue.TheTime-
Outvaluesfornon-adaptingmodeare:
NOTE:Toreturntoadaptingmode,rotatetheTimedialtofullCW
position(Asetting).BesuretheTimedialisrotateduntilanAmber
LEDashisissuedtobesureanewsettingwasselected.
(/)SlashMark
1
2
3
A
30secondxedtime-outforperformingawalktest
10minutesxedtime-out
20minutesxedtime-out
30minutesxedtime-out
AutoAdapting
Value of TimeFace Marking
SETTINGS
OPERATION
LIMITED 5 YEAR WARRANTY AND EXCLUSIONS
LevitonwarrantstotheoriginalconsumerpurchaserandnotforthebenetofanyoneelsethatthisproductatthetimeofitssalebyLevitonisfreeofdefectsinmaterialsandworkmanshipundernormalandproperuseforveyearsfromthepurchasedate.Leviton’sonlyobligationistocorrectsuchdefectsbyrepairorreplacement,atitsoption,ifwithinsuchveyearperiodtheproductisreturnedprepaid,
withproofofpurchasedate,andadescriptionoftheproblemtoLeviton Manufacturing Co., Inc., Att: Quality Assurance Department, 59-25 Little Neck Parkway, Little Neck, New York 11362-2591.Thiswarrantyexcludesandthereisdisclaimedliabilityforlaborforremovalofthisproductorreinstallation.Thiswarrantyisvoidifthisproductisinstalledimproperlyorinanimproperenvironment,
overloaded,misused,opened,abused,oralteredinanymanner,orisnotusedundernormaloperatingconditionsornotinaccordancewithanylabelsorinstructions.There are no other or implied warranties of any kind, including merchantability and fitness for a particular purpose,butifanyimpliedwarrantyisrequiredbytheapplicablejurisdiction,thedurationofanysuchimpliedwarranty,
includingmerchantabilityandtnessforaparticularpurpose,islimitedtoveyears.Leviton is not liable for incidental, indirect, special, or consequential damages, including without limitation, damage to, or loss of use of, any equipment, lost sales or profits or delay or failure to perform this warranty obligation.Theremediesprovidedhereinaretheexclusiveremediesunderthiswarranty,
whetherbasedoncontract,tortorotherwise.
1. IfthereisnoresponsefromtheunitandtheLEDneverblinksor
thepushbuttondoesnotactivatethelights1-1/2minutesafter
powerisapplied,thenuninstalldeviceandverifywiring(Step 4).
2. IfthelightsconstantlystayON,evenwhentheroomisunoccupied:
A.ChecktheTimesetting.Seehowthistimecomparestohow
longthelightsstayON.
B.TryloweringthePIRRangeControl.Rotatetheknob
counterclockwiseabout30°.
C.Iftheproblempersists,tryreducingagain.
 NOTE:DonotreducesomuchthattheSensorUnitcannotsee
normaloccupancy.
D.TryloweringtheUltrasonicSensitivity.
E.BesuretousetheBlinderstoblockanyunwantedhallway
trafc.
F. Checkforreectedheat/motionastheSensorUnitmaybe
seeingmotionthroughawindow.
G.CheckforadjacentHVACand/orheaterducts.
TROUBLESHOOTING
Lens
Blinders
Control panel
cover
Push button
LED window
US sensor ports
Thisequipmenthasbeentestedandfoundtocomplywiththelimits
foraClassAdigitaldevice,pursuanttopart15oftheFCCRules.
Theselimitsaredesignedtoprovidereasonableprotectionagainst
harmfulinterferencewhentheequipmentisoperatedinacommercial
environment.Thisequipmentgenerates,usesandcanradiateradio
frequencyenergyand,ifnotinstalledandusedinaccordancewith
theinstructionmanual,maycauseharmfulinterferencetoradio
communications.Operationofthisequipmentinaresidentialarea
islikelytocauseharmfulinterferenceinwhichcasetheuserwillbe
requiredtocorrecttheinterferenceattheirownexpense.
FCC COMPLIANCE STATEMENT
• Fortechnicalassistancecontactusat1-800-824-3005
• Visitourwebsiteatwww.leviton.com
PRODUCT INFORMATION
• Securedevicebyrmlytighteningmountingscrews.
• InstallDecora
®
stylewallplate(soldseparately).
Small Motion=DualTechnologycoverage.Thisalsorepresentsthe
maximumultrasonicrangecoverage.
Wall surface
Device mounting screw
(2 places)
Wallplate
Wallplate
mounting
screw
(2 places)
20 ft (6.1 m)
small motion
30 ft (9.1 m)
20 ft (6.1 m)
small motion
40 ft
(12.2 m)
Field - of - View (Horizontal)
Side (Vertical) Field - of - View
DI-0XX-OSSMT-00A
2008©LevitonMfg.Co.,Inc.
Control Panel Diagram
US Sensitivity and PIR Disable
3 amber flashes High ultrasonic sensitivity, PIR enabled
2 amber flashes Medium ultrasonic sensitivity, PIR enabled
1 amber flash Low ultrasonic sensitivity, PIR enabled
3 green flashes High ultrasonic sensitivity, PIR disabled
2 green flashes Medium ultrasonic sensitivity, PIR disabled
1 green flash Low ultrasonic sensitivity, PIR disabled
NOTE:Theprogramtimesoutin30secondsfromthelastbutton
press.ThefactorysettingfortheUSsensitivityisHIGHwithPIRand
Ultrasonictechnologiesenabled.
7. ReplacetheControlPanelCoverandDecora
®
wallplate.
6. Ifdesired,adjusttheblinderstoblockanyunwantedmotion.