Leviton OSSMD-MDI Installation guide

Type
Installation guide

This manual is also suitable for

Leviton OSSMD-MDI is a multi-technology designer wall switch occupancy sensor with dual relays, compatible with a wide range of lighting types and loads, including incandescent, fluorescent, electronic ballasts, and motors. It features both passive infrared (PIR) and ultrasonic (US) detection technology, providing reliable motion detection and coverage up to 2400 sq. ft. The device includes convenient push-buttons for manual ON/OFF control, adjustable field of view, and integrated photocell for ambient light hold-off.

Leviton OSSMD-MDI is a multi-technology designer wall switch occupancy sensor with dual relays, compatible with a wide range of lighting types and loads, including incandescent, fluorescent, electronic ballasts, and motors. It features both passive infrared (PIR) and ultrasonic (US) detection technology, providing reliable motion detection and coverage up to 2400 sq. ft. The device includes convenient push-buttons for manual ON/OFF control, adjustable field of view, and integrated photocell for ambient light hold-off.

WARNINGS AND CAUTIONS:
• Tobeinstalledand/orusedinaccordancewithappropriateelectricalcodesandregulations.
• Ifyouareunsureaboutanypartoftheseinstructions,consultaqualiedelectrician.
• Controllingaloadinexcessofthespeciedratingswilldamagetheunitandposeriskofre,electricshock,personalinjuryordeath.
Checkyourloadratingstodeterminesuitabilityforyourapplication.
• Donotinstallthisunittocontrolareceptacle.
WARNINGS AND CAUTIONS:
• Donottouchthesurfaceofthelens.Cleanoutersurfacewithadampclothonly.
• Disconnectpoweratcircuitbreakerorfusewhenservicing,installingorremovingxture.
• Usethisdeviceonlywithcopperorcoppercladwire.WithaluminumwireuseonlydevicesmarkedCO/ALRorCU/AL.
• NeutralconnectionrequiredwhenusedincircuitswithGFCIs.UseCatNo.'sOSSMD-MDorOSSMD-FTonly.
TwoCircuit(OneLocation)orMulti-Location
Multi-Technology Designer Wall Switch Occupancy Sensor with Dual Relays
California Title 24 2005 Compliant
Cat. No. OSSMD-MD, OSSMD-FT, OSSMD-GD
Incandescent/Tungsten:800W@120VPrimary/SecondaryBallast:1200VA@120VPrimary-800VA@120VSecondary
Ballast:2700VA@277VPrimary-1200VA@277VSecondaryMotor:1/4hp@120VPrimary/Secondary
Operating Temperature Range:0°Cto50°C
Relative Humidity:20%to90%non-condensing
No Minimum Load Required
Compatiblewithincandescentlamps,low-voltagelightingwithelectronicandmagnetictransformers,electronicandmagneticuorescentballasts,andfans.
INSTALLATION INSTRUCTIONS
TOOLS NEEDED TO INSTALL YOUR SENSOR
Slotted/PhillipsScrewdriver ElectricalTape
Pliers Cutters
SmallSlottedScrewdriver
• Leviton’sDecora
®
styledesign
• Sensorcanbegangedtogetherwithotherunitsinamultiple-switch
wallplate.
• Self-AdaptiveTechnologyadjuststooccupancypatternsofuseinauto
adaptmode.
• TheAdaptingTime-outwalk-throughfeaturepreventslightsfrom
remainingONforanextendedperiodafteronlyamomentary
occupancy.
• Switchestwoseparateloadcircuits.
• Two(MDandGDmodels)convenientPush-Buttonsprovidemanual
ON/OFFswitchingatanytime.
• Adjustablehorizontaleldofview.
• IntegratedphotocellpreventslightsfromturningONwhenroomis
adequatelyilluminatedbynaturallight.
• TrueZero-Crossforprimaryrelayprovidesmaximumcontactlifeand
compatibilitywithelectronicballasts.
• Dualdetectiontechnology,bothPassiveInfraredandUltrasonic.Can
beconguredasUltrasonicOnlyandPIROnly.
Leviton'sDesignerMulti-TechnologyWallSwitchOccupancySensor,
Cat.No.OSSMD,isdesignedtodetectmotionusingthepassiveinfrared
(PIR)sensorfromsources(suchasapersonenteringaroom)withinits
eld-of-view(monitoredspace)andautomaticallyswitchlightsON.The
OccupancySensorsensesmotionwithinitsmaximumcoverageareaof
2400sq.ft(223m
2
).TheUltrasonic(US)sensorsworkwiththePIRto
keepthelightsONwhenoccupied.ThecontrolledlightswillremainON
untilnomotionisdetectedandthescheduledtime-delayhasexpired,at
whichpointthelightswillbeturnedOFF.Inadaptingtime-outmodethe
sensoradaptsitstimedelaysettingstotheoccupancypatternsofaroom.
TheOSSMD-MDisanOccupancySensorthatisdesignedtocontroltwo
separatelightingcontrolcircuitsfromasingleunit.Thisallowstheuserto
replacetwoswitcheswithasingleunitthatwillprovidetheconvenience
andenergysavingsofanoccupancysensor.Itisadualrelaydevice,
relayonecanbeAutoONorManualONandrelaytwoisManualON
only.ThedevicecontainsaphotocellthatprovidesanAmbientLightHold
Offfunctionforrelaynumberone.BothrelaysoperateasAutoOFF.The
devicecanbeconguredforUltrasonicwithPIR,UltrasonicOnly,andPIR
Onlymodesofoperation.
TheOSSMD-GDhasallthefunctionalityoftheOSSMD-MDwithouta
neutralconductor.Itisintendedforuseinretrotapplicationswherea
neutralisnotavailableinthewallbox.
TheOSSMD-FTmodelisintendedforapplicationssuchasacommercial
bathroomwhereaconvenienceexhaustfanmustbecontrolled.The
tworelaysturnONintandembutremainONfordifferentdurations.
ThedevicecanbeconguredtobeeitherintheAutoONorManual
ONmodes.TheAutoONmodeutilizesthesensortechnologytoturn
ONwhilethesinglepushbuttononthefrontofthedeviceprovidesthe
ManualONactivation.AxedtimedelayOFFof10minutes,whichstarts
whentherstrelayturnsoff,willapplytothesecondrelayinbothofthese
modesofoperation.ItcanbeconguredforeitherUltrasonicwithPIR,
UltrasonicOnly,orPIROnlymodesofoperation.Thisdevicerequiresa
neutralconductor.
Cat. No. OSSMD is ETL listed, cETL listed and conforms to California
Title 24 requirements.
ThePIROccupancySensorusesasmallsemiconductorheatdetector
thatresidesbehindamulti-zoneopticallens.ThisFresnellens
establishesdozensofzonesofdetection.TheSensorissensitivetothe
heatemittedbythehumanbody.InordertoinitiallytriggertheSensor,
thesourceofheatmustmovefromonezoneofdetectiontoanother.The
deviceismosteffectiveinsensingmotionacrossitseld-of-viewanditis
lesseffectivesensingmotiontowardsorawayfromitseld-of-view.Keep
thisinmindwhenselectingtheinstallationlocation(refer to Field-of-View
diagrams).
TheUSOccupancySensorusesanon-audible,highfrequency(40kHz)
tosenseDopplershiftscausedbymotioninthespace.TheUSismore
sensitivetosmallmotionanddoesnotrelyonlineofsightfordetection.If
bothsensorshavenotdetectedanymotionforthesettimeoutperiod,the
relaysandtheircorrespondingloadswillbeturnedOFF.
Notethatoccupancysensorsrespondtorapidchangesintemperature,so
careshouldbetakennottomountthedevicenearaclimatecontrolsource
(i.e.radiators,airexchanges,andairconditioners).Hotorcolddraftswill
looklikebodymotiontothedeviceandwilltriggeritiftheunitismountedtoo
close.It is recommended to mount the Occupancy Sensor at least 6 feet
away from a climate control source.
Inaddition,itisalsorecommendedNOTtomounttheOccupancySensor
directlyunderalargelightsource.Largewattagebulbs(greaterthan
100Wincandescent)giveoffalotofheatandswitchingthebulbcausesa
temperaturechangethatcanbedetectedbythedevice.
MounttheOccupancySensoratleast6ft.awayfromlargebulbs.Ifitis
necessarytomountthedevicecloser,lowerthewattageofthebulbdirectly
overhead.
WARNING:TO AVOID FIRE, SHOCK, OR DEATH; TURN
OFF POWER atcircuitbreakerorfuseandtestthatpoweris
offbeforewiring!
Step 1
ONOFF
ONOFF
ONOFF
ONOFF
ONOFF
ONOFF
ONOFFONOFF
ONOFF
ONOFF
ONOFF
ONOFF
• Pulloffpre-cutinsulationfromsensorleads.
• Makesurethattheendsofthewiresfromthewallboxarestraight
(cut if necessary).
• Removeinsulationfromeachwireinthewallboxasshown.
Preparing and connecting wires:
9/16"
(1.4 cm)
Strip Gage
(measure bare
wire here)
Cut
(if necessary)
Step 3
INSTALLING YOUR SENSOR
NOTE:UsecheckboxeswhenStepsarecompleted.
4
1
3
2
5
1.Line(Hot)
2.Neutral
3.Ground
4.Load
5.SecondaryLoad
Installing your Sensor - Single Location
Application:
Step 4
Identifying your wiring application
(most common):
Step 2
Hot (Black)
Phase 1
Neutral (White)
Primary
Load
Secondary
Load
Sensor
Black
Blue
Red
Red
Green
Ground
Line
120/277VAC
60Hz
Hot (Black)
Phase 1
Neutral (White)
Primary
Load
Secondary
Load
Sensor
Black
Blue
Red
Red (To Phase 2)
Green
Ground
Line
120/277VAC
60Hz
OSSMD-GD Wiring Methods
NOTE:TheoccupancysensorCat.No.OSSMD-GDdoesnotrequirea
neutralconnectioninordertooperate.Itmusthaveagroundconnection.
Usethegroundwireintheelectricalboxforgroundconnection.Ifthereis
nogroundwire,ensureelectricalboxisgroundedandattachgroundwire
toboxbyanapprovedconnectionmethod.
OSSMD-MD Wiring Methods
NOTE:TheoccupancysensorCat.No.OSSMD-MDrequiresaneutral
connectiontooperate.Usethegroundwireintheelectricalboxfor
groundconnection.Ifthereisnogroundwire,ensureelectricalboxis
groundedandattachgroundwiretoboxwithascrew.
Hot (Black)
Phase 1
Neutral (White)
Primary
Load
Secondary
Load
Sensor
Black
Blue
Red
Red
Green
Ground
Line
120/277VAC
60Hz
White
Hot (Black)
Phase 1
Neutral (White)
Primary
Load
Secondary
Load
Sensor
Black
Blue
Red
Red (To Phase 2)
Green
Ground
Line
120/277VAC
60Hz
White
Hot (Black)
Phase 1
Neutral (White)
Primary
Load
Fan/
Secondary
Load
Sensor
Black
Blue
Red
Red
Green
Ground
Line
120/277VAC
60Hz
White
Hot (Black)
Phase 1
Neutral (White)
Primary
Load
Fan/
Secondary
Load
Sensor
Black
Blue
Red
Red (To Phase 2)
Green
Ground
Line
120/277VAC
60Hz
White
OSSMD-FT Wiring Methods
NOTE:TheoccupancysensorCat.No.OSSMD-FTrequiresaneutral
connectiontooperate.Usethegroundwireintheelectricalboxfor
groundconnection.Ifthereisnogroundwire,ensureelectricalboxis
groundedandattachgroundwiretoboxwithascrew.
Installing your Sensor - Multi-Location Wiring
Application:
Step 5
WARNING:Ifyouareunsureaboutanypartoftheseinstructions,
consultaqualiedelectrician.
NOTE:EithersensorcanturnthelightsON.Bothsensorsmust
time-outtoOFF,orbothmanualbuttonsmustbepressedforthe
lightstoturnOFF.
NOTE:Allow1minuteforwarm-upafterconnectingandenergizing.
NOTE:BothoccupancysensorsCat.No.OSSMD-MDandOSSMD-FT
requireaneutralconnectioninordertooperate.Usethegroundwirein
theelectricalboxforgroundconnection.Ifthereisnogroundwire,ensure
electricalboxisgroundedandattachgroundwiretoboxwithascrew.
NOTE:
Thesedevicesarenottrue3wayproducts.
WARNING:Ifyouareunsureaboutanypartoftheseinstructions,
consultaqualiedelectrician.
NOTE:Allow1minuteforwarm-upafterconnectingandenergizing.
Hot (Black)
Phase 1
Neutral (White)
Primary
Load
Secondary
Load
Sensor 1 Sensor 2
Black
Black
Blue
Red
Blue
Red
Red
Red
Green
Ground
Green
Ground
Line
120/277VAC
60Hz
White
White
Hot (Black)
Phase 1
To Phase 2
Neutral (White)
Primary
Load
Secondary
Load
Sensor 1 Sensor 2
Black
Black
Blue
Red
Blue
Red
Red
Red
Green
Ground
Green
Ground
Line
120/277VAC
60Hz
White
White
DESCRIPTION
DI-000-OSSMD-00C
FEATURES
NOTE:Toaccesscontrolsettings,removethecontrolpanelcover.If
necessary,removethewarninglabelthatcoverstheadjustmentdials
(refer to Control Panel Diagram).
Factory Settings: Thesensorisshippedfromthefactorytowork
inalmostallsituations,withoutanyaddedadjustments.Thefactory
settingsare:Blindersopen,10minutesxedTime-Out,Lightsalways
turnONregardlessofexistinglightlevels,Mediumpassiveinfrared
(PIR)range,andMediumUltrasonicrange.ThePIRandUltrasonic
technologiesarebothactive.
Blinders:Theblindersaretwoindependentshuttersthatcannarrow
theeld-of-viewfromamaximumof180°downto60°.Theblinders
areoperatedbymovingtheblinderleverstowardsorawayfrom
thecenteroftheSensor.Theblinderleverscanbefoundabovethe
controldialsinthecontrolpanel(refer to Control Panel Diagram).
Time-Outs:TheSensorhasthreetypesofTime-Outs:Fixed,
Adapting,andWalkthrough.
• Fixed Time-Out:ThevalueofthisTime-Outisuserselected
throughtheuseoftheTimeControlSettings(refer to Control
Panel Diagram and Time-Out Settings).
• Adapting Time-Out:Whenactivated,thevalueofthisTime-Out
(30minutes)ischangedbytheSensorbasedonroomoccupancy
andlightingconditions.
• Walk-through Time-Out:ThevalueofthisTime-Outispresetto
2.5minutesandonlyexistsintheAdaptingTime-Outmode.
Vacancy Confirmation: Afterlightsshutoffthereisa30second
vacancyconrmationtoon.
Fixed Time Delay:ThexedTime-Outvalueisselectedbyrotating
theTimeControldial.Therearefour(4)valuesfromwhichtochoose.
Eachmarkaroundthedialcorrespondstoadifferentvalueas
indicatedbelow(refer to Control Panel Diagram).
NOTE: Alltimedurationsareapproximatewithin±10seconds.
Adapting Time Delay:TheSensorhasbuiltinadaptingintelligence
thatmodiestheAdaptingTime-Outdurationinresponsetothe
occupancyconditionsoftheroomitisinstalledin.IftheSensor
detects“large,infrequentmotionitwillINCREASEtheAdapting
Time-Outduration.IftheSensordetects“large,frequentmotion(as
inseveralpersonsinaroomduringameeting),itwillDECREASEthe
time-outdurationonlyifitwasNEVERincreased(thisisbecausethe
built-inintelligencewillalwaysproceedinthedirectionof“increasing”
adaptingTime-Outonceithasincreaseditforanyoftheoccupancy
conditionssensed).TheAdaptingTime-Outdurationwillrangefrom10to
30minutesintimeplustheWalk-ThroughTimeDelay.
Walk-Through Time Delay:Thewalk-throughfeature,whichis
onlyactiveintheAdaptingTime-Outmode,isusefulwhenaroomis
momentarilyoccupied.Withthisfeature,theSensorwillturnthelights
OFFshortlyafterthepersonleavestheroom.Thewalk-throughfeature
worksinthefollowingmanner:Whenapersonenterstheroom,thelights
willturnON.Ifthepersonleavestheroombeforethewalk-throughtime-
outof2.5minutes,theSensorwillturnthelightsOFFafter2.5minutes.If
thepersonstaysintheroomforlongerthan2.5minutes,theSensorwill
insteadusethestoredAdaptingTimeDelay.
Iftheroomisoccupiedforlongerthan2.5minutes,theSensorwillenter
theOccupiedModewiththetime-outdurationspeciedbytheAdapting
Time-Outsetting.
IftheSensordetectsmotionwithin30secondsafterthelightsturnOFF,
itwillturnthelightsONandincreasethetime-outvalueby1.5timesthe
existingvalue.
TheAdaptingTime-Outmayberesettothebasevalueof30minutesby
rotatingtheTimeControltoanewtimeselectionvalueandthenbackto
theAdaptingTime-Outvalue(refer to Control Panel Diagram).
Ambient Light Override:TheAmbientLightOverrideisusedtokeep
thelightsOFFifthereisalreadyenoughnaturallightintheroom.
Forproperoperation,theAmbientLightOverrideadjustmentmustbe
performedwhenthereisenoughnaturallight(refer to the SETTINGS
section).Iftheadjustmentismadewhenthereislessnaturallight,the
lightsmaynotturnONeventhoughtheyareneededandwillrequire
manualactivationofthepush-buttonstoturnthelightsON.
NOTE: Theambientlightlevelinthecenterofaroomwillbedifferent
thanthelevelatthewallwheretheswitchislocated.
Ambient Light Dial:Theambientlightsettingisadjustedwiththe
AmbientLightDial(refer to Control Panel Diagram).TurningtheLight
Dialfullycounter-clockwise(CCW),setstheSensortomanualONmode
(see following section).IfthelightcontrolisinthefullyCWposition,
thelightswillturnONwhenevermotionisdetected,eveninfulldaylight.
IntermediatesettingswillcausethelightstoturnONonlywhenthe
ambientlightisbelowthelevelselectedbythelightcontrol.
NOTE:WhenthesettingisattheminimumCCWlevel,thelightswillstay
OFFwhentheroomisdim.Whenthesettingisatthemaximumlevel
clockwise(CW),thelightswillturnONwhentheroomisbright.
Manual ON Mode:WhenthelightcontrolisinthefullyCCWposition
thelightswillneverautomaticallyturnON.Inthismodethelightsneed
tobemanuallyturnedONbythepush-button,andwillturnOFFwiththe
absenceofmotion.
PIR RANGE: TodecreasePIRdetectionrangeandsensitivity,rotatethe
knobCCW(refer to Control Panel Diagram).Thedetectionrangecan
beadjustedfrom100%downto30%.
ULTRASOUND (US) SENSITIVITY AND PIR DISABLE:USsensitivity
canbeadjustedtoHIGH-MEDUIM-LOWbyholdingtheONbuttonfor
15seconds.TheLEDwillashtorepresenttheUltrasonicsensitivity
andPIRstatus.TappingthePrimaryorSecondaryONbuttonduringthe
desiredLEDashindicationwillsetthesensitivityandPIRstatus.Use
thefollowingchart:
NOTE:Todisable/enableUltrasonicTechnology:
1. Turnthe"light"adjustmentknobCCW.
2.Holdthebuttondownfor6-7seconds.
3.Relasebutton.RedLedblinking=PIRonly.GreenLEDblinking=US
active.
NOTE:Theprogramtimesoutin30secondsfromthelastbuttonpress.
ThefactorysettingfortheUSsensitivityisHIGHwithPIRandUltrasonic
technologiesenabled.
Wall surface
Sensor
Mounting
screws
(2 places)
Testing your Sensor prior to completely
mounting in wall box:
Step 6
NOTE:Dresswireswithabendasshownindiagramtorelievestress
whenmountingdevice.
• Positionallwirestoprovideroominoutletwallboxfordevice.
• Partiallysecuredeviceusinglongmountingscrewsprovided.
• Restorepoweratcircuitbreakerorfuse.
NOTE:Allow1minuteforwarm-upafterenergizing.
NOTE:AllmodelsoftheOSSMDarefactorypresettoworkwithout
anyadjustments.Ifnecessary,adjusttheBlindersandPIRRange
Controltostopanyunwantedactivationofthelights(refer to
FEATURES section).
• ForadditionalTimeControlSettings(refer to the SETTINGS
section).
NOTE:ToavoidPERMANENTDAMAGEtotheunit,becareful
NOTTOOVERTURNthecontrolknobsorleverswhensettingthe
Sensor.Thecontrolscanbeaccessedbyremovingthewallplate
(ifapplicable)andcontrolpanelcover(refer to Control Panel
Diagram).Useasmallstraightbladescrewdrivertoadjustknobs
andblinderlevers.
NOTE:DONOTpressinonblinderleversoruseexcessiveforce
(refer to Control Panel Diagram).
• AttachtheControlPanelcoverwhenthedesiredsettingsare
complete.
If lights do not turn ON, refer to the TROUBLESHOOTING section.
TIME
1
2
A
3
RANGE
BLINDERS
LIGHT
4
7
10
4
7
10
S
la
s
h Mark
Blinder adjustment levers
Control Panel Cover
PUSH BUTTON(S)
Cat.No.OSSMD-FThasasinglepush-buttonswitchthattoggles
relaysandtheircorrespondingloads,ONandOFF.Iftherelaysare
OFF,therelayswillturnONwhenthepush-buttonispressed,and
remainONinthepresenceofmotion.Intheabsenceofmotion,the
SensorUnitwillTime-OutandturnrelayoneOFF.Relaytwowill
remainONforthexed10minuteadditionaldelay.Whenthatperiod
timesout,relaytwowillturnOFF.
IftherelaysandtheircorrespondingloadsareON,relayonewill
turnOFFwhenthebuttonispressed.Relaytwowillremainonfor
10minutesaftertheTime-Outexpires.Afterthesetwoevents,the
relayswillturnONwiththenextdetectedmotion.
Cat.No.OSSMD-MDandOSSMD-GDhavetwopush-button
switchesthattoggletherelaysandtheircorrespondingloads,ONand
OFF.Buttononecontrolsrelayoneandbuttontwocontrolsrelaytwo.
IftherelaysareOFF,therelayswillturnONwhentheirpush-buttonis
pressed,andremainONinthepresenceofmotion.Intheabsenceof
motion,theSensorUnitwillTime-OutandturnbothoftherelaysOFF.
IftherelaysandtheircorrespondingloadsareON,therelayswillturn
OFFwhentheircorrespondingbuttonsarepressed.Therelayswillstay
OFFregardlessofmotiondetected,untiltheTime-Outexpires.Afterthe
Time-Outexpires,therelayswillturnONwiththenextdetectedmotion.
NOTES:
• TheMotionIndicatorLEDwillblinkevery1secondwhilemotionis
detected.
• WhentheTime-OutexpiresandtherelaysturnOFFa30second
vacancyconrmationexiststoturntherelay(s)backON.Afterthis
timethedevicewillbeplacedintoalowerdetectionthresholdmode.
• InManual-ONmode,thebuttonmustbepressedtoturnthelights
ON.Intheabsenceofmotion,theunitwillTime-Outandturnthe
lightsOFF.
• IfManual-Onmodeisdesired,keeptheLightknobinthefully
counter-clockwise(CCW)position.
NOTE:ToavoidPERMANENTDAMAGEtotheunit,becarefulNOT
TOOVERTURNoruseexcessiveforcewhensettingthecontrolknobs
orleversofCatNo.OSSMD.Useasmallstraightbladescrewdriverto
adjusttheknobsandyourngertoadjusttheblinderlevers.
1. RemoveDecora
®
wallplateandControlPanelCoverfromSensor.
2. RotatetheTimedialtoselectthedesiredxedTime-Outvalue.
3. IftheSensorisinstalledwithin6feetofanairduct,rotatetheRange
Control1/4turncounter-clock-wise(CCW).
4. Set the Ambient Light Level - AMBIENT LIGHT:Cat.No.OSSMD
hasanadjustmenttodetermineatwhatminimumambientlight
leveltheunitwilloperate.Theadjustmentshouldbemadewhenthe
ambientlightisatthelevelwherenoarticiallightisneeded.Follow
thesestepstomakeamoreaccurateadjustmentofthelightcontrol.
ThisfeaturewillnotworkinManual-Onmode.
A. WiththelightsON,rotatetheTimeControlfullyCCWtothesetthe
Time-Outtothethirty(30)secondtestmode(refertoControlPanel
Diagram).
B. RotatetheLightControlfullyCCW.
C. ManuallyturnOFFthelights.
D. RotatetheLightControlclockwise(CW)SLOWLY,untilthelights
turnON.Thisisthesettingforthecurrentleveloflightintheroom.
  NOTE:WhenthelightcontrolisinthefullyCCWpositionthelights
willneverautomaticallyturnON.ThisistheManual-Onmode,
wherethelightsneedtobemanuallyturnedONbythepush-
button,andwillturnOFFwiththeabsenceofmotion.
  IfthelightcontrolisinthefullyCWposition,thelightswillturnON
whenevermotionisdetected,eveninfulldaylight.
  IntermediatesettingswillcausethelightstoturnONonlywhenthe
ambientlightisbelowthelevelselectedbythelightcontrol.
  NOTE:Theambientlightinaroomwillchangewiththetimeofday
andtheseasonoftheyear.
5. Time-Out Settings:
A. AdjusttheTimedial.TheSensorAmberLEDwillashtwiceeach
timetheTimedialispointedatanewTime-Outvalue.TheTime-
Outvaluesfornon-adaptingmodeare:
NOTE:Toreturntoadaptingmode,rotatetheTimedialtofullCW
position(Asetting).BesuretheTimedialisrotateduntilanAmber
LEDashisissuedtobesureanewsettingwasselected.
6. Ifdesired,adjusttheblinderstoblockanyunwantedmotion.
(/)SlashMark
1
2
3
A
30secondxedtime-outforperformingawalktest
10minutesxedtime-out
20minutesxedtime-out
30minutesxedtime-out
AutoAdapting
Value of TimeFace Marking
FEATURES
SETTINGS OPERATION
LIMITED 5 YEAR WARRANTY AND EXCLUSIONS
LevitonwarrantstotheoriginalconsumerpurchaserandnotforthebenetofanyoneelsethatthisproductatthetimeofitssalebyLevitonisfreeofdefectsinmaterialsandworkmanshipundernormalandproperuseforveyearsfromthepurchasedate.Leviton’sonlyobligationistocorrectsuchdefectsbyrepairorreplacement,atitsoption,ifwithinsuchveyearperiodtheproductisreturnedprepaid,with
proofofpurchasedate,andadescriptionoftheproblemtoLeviton Manufacturing Co., Inc., Att: Quality Assurance Department, 201 North Service Road, Melville, N.Y. 11747, U.S.A.Thiswarrantyexcludesandthereisdisclaimedliabilityforlaborforremovalofthisproductorreinstallation.Thiswarrantyisvoidifthisproductisinstalledimproperlyorinanimproperenvironment,overloaded,misused,
opened,abused,oralteredinanymanner,orisnotusedundernormaloperatingconditionsornotinaccordancewithanylabelsorinstructions.There are no other or implied warranties of any kind, including merchantability and fitness for a particular purpose,butifanyimpliedwarrantyisrequiredbytheapplicablejurisdiction,thedurationofanysuchimpliedwarranty,includingmerchantabilityand
tnessforaparticularpurpose,islimitedtoveyears.Leviton is not liable for incidental, indirect, special, or consequential damages, including without limitation, damage to, or loss of use of, any equipment, lost sales or profits or delay or failure to perform this warranty obligation.Theremediesprovidedhereinaretheexclusiveremediesunderthiswarranty,whetherbasedoncontract,
tortorotherwise.
1. IfthereisnoresponsefromtheunitandtheLEDneverblinksor
thepushbuttondoesnotactivatethelights1-1/2minutesafter
powerisapplied,thenuninstalldeviceandverifywiring(Step 4).
2. IfthelightsconstantlystayON,evenwhentheroomisunoccupied:
A.ChecktheTimesetting.Seehowthistimecomparestohow
longthelightsstayON.
B.TryloweringthePIRRangeControl.Rotatetheknob
counterclockwiseabout30°.
C.Iftheproblempersists,tryreducingagain.
  NOTE:DonotreducesomuchthattheSensorUnitcannotsee
normaloccupancy.
D.TryloweringtheUltrasonicSensitivity.
E.BesuretousetheBlinderstoblockanyunwantedhallway
trafc.
F. Checkforreectedheat/motionastheSensorUnitmaybe
seeingmotionthroughawindow.
G.CheckforadjacentHVACand/orheaterducts.
H.IfyourOSSMDdoesnotseemtobefunctioningandhasa
ashingamberLED,theremaybeazero-crossfailure.Please
callfortechnicalassistance.
TROUBLESHOOTING
Lens
Blinders
Control panel
cover
Push buttons
LED window
US sensor ports
Thisequipmenthasbeentestedandfoundtocomplywiththelimits
foraClassAdigitaldevice,pursuanttopart15oftheFCCRules.
Theselimitsaredesignedtoprovidereasonableprotectionagainst
harmfulinterferencewhentheequipmentisoperatedinacommercial
environment.Thisequipmentgenerates,usesandcanradiateradio
frequencyenergyand,ifnotinstalledandusedinaccordancewith
theinstructionmanual,maycauseharmfulinterferencetoradio
communications.Operationofthisequipmentinaresidentialarea
islikelytocauseharmfulinterferenceinwhichcasetheuserwillbe
requiredtocorrecttheinterferenceattheirownexpense.
FCC COMPLIANCE STATEMENT
• Fortechnicalassistancecontactusat1-800-824-3005
• Visitourwebsiteatwww.leviton.com
PRODUCT INFORMATION
• Securedevicebyrmlytighteningmountingscrews.
• InstallDecora
®
stylewallplate(soldseparately).
Wall surface
Device mounting screw
(2 places)
Wallplate
Wallplate
mounting
screw
(2 places)
20 ft (6.1 m)
small motion
30 ft (9.1 m)
20 ft (6.1 m)
small motion
40 ft
(12.2 m)
Field - of - View (Horizontal)
40 ft.
(12.2 m)
4 ft.
(1.2 m)
Sensor
Side (Vertical) Field - of - View
DI-000-OSSMD-00C©2010LevitonMfg.Co.,Inc.
Control Panel Diagram
US Sensitivity and PIR Disable
3 amber flashes High ultrasonic sensitivity, PIR enabled
2 amber flashes Medium ultrasonic sensitivity, PIR enabled
1 amber flash Low ultrasonic sensitivity, PIR enabled
3 green flashes High ultrasonic sensitivity, PIR disabled
2 green flashes Medium ultrasonic sensitivity, PIR disabled
1 green flash Low ultrasonic sensitivity, PIR disabled
7. ReplacetheControlPanelCoverandDecora
®
wallplate.
  • Page 1 1
  • Page 2 2

Leviton OSSMD-MDI Installation guide

Type
Installation guide
This manual is also suitable for

Leviton OSSMD-MDI is a multi-technology designer wall switch occupancy sensor with dual relays, compatible with a wide range of lighting types and loads, including incandescent, fluorescent, electronic ballasts, and motors. It features both passive infrared (PIR) and ultrasonic (US) detection technology, providing reliable motion detection and coverage up to 2400 sq. ft. The device includes convenient push-buttons for manual ON/OFF control, adjustable field of view, and integrated photocell for ambient light hold-off.