  • Hello! I am an AI chatbot trained to assist you with the Lenovo System x3750 M4 Installation Instructions Manual. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
LenovoSystemx3750M4RackInstallation
Instructions
MachineType:8753
Second(November2015)
©CopyrightLenovo2015.
LIMITEDANDRESTRICTEDRIGHTSNOTICE:IfdataorsoftwareisdeliveredpursuantaGeneralServicesAdministration
“GSAcontract,use,reproduction,ordisclosureissubjecttorestrictionssetforthinContractNo.GS-35F-05925
Contents
Chapter1.Safetyinformation.....1
Chapter2.Rackkitpartsinventory..3
Chapter3.Rackinstallation......5
Identifyingtherackspacefortheserver.....5
Installingtherailsintherack.........5
Openingthefrontslideraillatches.....5
Openingtherearsliderailhooks......6
Installingtherearendofthesliderailsintothe
rackcabinet..............6
Aligningthefrontofthesliderailstotherack
cabinet................7
Installingthefrontendofthesliderailsintothe
rackcabinet..............7
Installingtheserveronthesliderails......8
Slidingtheserverintotherackcabinet.....9
Installingthecablemanagementsupportbar...10
Connectingthecablemanagementsupportbarto
thecablemanagementarmstopbracket....11
Connectingthecablemanagementarmstop
brackettothesliderail...........11
Installingthecablemanagementarm......12
Openingandclosingthecablemanagementarm
stopbracket...............12
Connectingandroutingthecables.......13
Securingthecableswiththehook-and-loop
fasteners.................14
Securingthecablemanagementarmandthe
serverintherackforshipping.........14
Installingthefrontscrews..........15
Chapter4.Removingtheserverfrom
therack................17
Unlatchingandrotatingthefrontoftheserver..17
Liftingtheserveroffthesliderails.......17
Removingthecablemanagementarm.....18
Disconnectingthecablemanagementarmstop
bracketfromthesliderail..........18
Disconnectingthecablemanagementsupportbar
fromthecablemanagementarmstopbracket..19
Removingthecablemanagementsupportbar
fromtheslidesrails.............19
Removingthesliderailsfromthefrontofthe
rack...................20
Removingthesliderailsfromtherearoftherack.20
Chapter5.Changingthecable
managementarmforinstallationon
therightsideoftherack.......23
Installingthecablemanagementarmontheright
sideoftherack..............23
©CopyrightLenovo2015,and2012,2015
i
iiLenovoSystemx3750M4RackInstallationInstructions
Chapter1.Safetyinformation
Thetopicprovidessafetyguidelinesthatyouneedtoreadbeforeyouinstalltheserverinarackcabinet.
Reviewthedocumentationthatcomeswiththerackcabinetforsafetyandcablinginformation.Beforeyou
installtheserverinarackcabinet,reviewthefollowingguidelines:
Notes:
UsetheM6screwsthatcomewithsliderailstoinstalltheserverinarackcabinetifyouplantotransport
therackcabinettoanotherlocationwiththeserverinstalledortherackisinavibration-pronearea.
Youcaninstallthecablemanagementarmoneithersideoftherack.Theseinstructionsareshownwith
thecablemanagementarmmountedontheleftside.Theinstallationinstructionsinthisdocumentcanbe
reversedifyouareinstallingthecablemanagementarmontheothersideoftherack.
Twoormorepeoplearerequiredtoinstalldevices2Uorlargerinarackcabinet.
Seetheserverdocumentationforthemaximumroomairtemperature.
Donotblockanyairvents;usually15cm(6in.)ofspaceprovidesproperairflow.
Donotleaveopenspacesaboveorbelowaninstalledserverinyourrackcabinet.Tohelpprevent
damagetoservercomponents,alwaysinstallablankfillerpaneltocovertheopenspaceandtohelp
ensureproperaircirculation.
Installtheserveronlyinarackcabinetwithperforateddoors.
Planthedeviceinstallationstartingfromthebottomoftherackcabinet.
Installtheheaviestdeviceinthebottomoftherackcabinet.
Donotextendmorethanonedeviceoutoftherackcabinetatthesametime.
Removetherackdoorsandsidepanelstoprovideeasieraccessduringinstallation.
Connecttheservertoaproperlygroundedoutlet.
Donotoverloadthepoweroutletwhenyouinstallmultipledevicesintherackcabinet.
Installtheserverinarackthatmeetsthefollowingrequirements:
Minimumdepthof70mm(2.76in.)betweenthefrontmountingflangeandinsideofthefrontdoor.
Minimumdepthof157mm(6.18in.)betweentherearmountingflangeandinsideofthereardoor.
Minimumdepthof718mm(28.27in.)andmaximumdepthof762mm(30in.)betweenthefrontand
rearmountingflangestosupporttheuseofthecablemanagementarm.
Note:ThemaximumdistancebetweenthefrontandtherearEIArailsoftherackis810mm(31.9in.).
Statement4
Threegraphicillustrationsforsafetypracticeswhenlifting.
©CopyrightLenovo2015,and2012,2015
1
CAUTION:Usesafepracticeswhenlifting.
18kg(39.7lb)32kg(70.5lb)55kg(121.2lb)
Statement26
CAUTION:
Donotplaceanyobjectontopofrack-mounteddevices.
Statement37
DANGER
Whenyoupopulatearackcabinet,adheretothefollowingguidelines:
Alwayslowerthelevelingpadsontherackcabinet.
Alwaysinstallthestabilizerbracketsontherackcabinet.
Alwaysinstalltheheaviestdevicesinthebottomoftherackcabinet.
Donotextendmultipledevicesfromtherackcabinetsimultaneously,unlesstherack-mounting
instructionsdirectyoutodoso.Multipledevicesextendedintotheservicepositioncancause
yourrackcabinettotip.
IfyouarenotusingtheIBM9308rackcabinet,securelyanchortherackcabinettoensure
itsstability.
2LenovoSystemx3750M4RackInstallationInstructions
Chapter2.Rackkitpartsinventory
Thisinformationprovidesthelistofitemsinthesliderailboxkitandcablemanagementarmboxkit.
Theservercomeswithallofthehardwarethatisnecessaryforyoutoinstalltheserverintherackcabinet.
Thefollowingillustrationsdisplaytheitemsthatyouneedtoinstalltheserverintherackcabinet.Ifanyitems
aremissingordamaged,contactyourplaceofpurchase.
Notes:
Youwillneedboththesliderailboxkitandthecablemanagementarmboxkitforthisinstallation.
Thehook-and-loopfastenersarelocatedonthecablemanagementarm.
Thesliderailboxkitincludesthefollowinghardware.Thiskitshipswiththeserver.
Onerightserversupportrail
Oneleftserversupportrail
FourM6hexheadscrews
Thecablemanagementarmboxkitincludesthefollowinghardware.Thiskitshipswiththeserver.
Onecablemanagementsupportbar
Onecablemanagementarmassembly
Onecablemanagementarmstopbracket
©CopyrightLenovo2015,and2012,2015
3
Cable-management
arm assembly
(large capacity)
Cable management
support bar
Cable management arm
stop bracket
Cable Management Arm box contents
4LenovoSystemx3750M4RackInstallationInstructions
Chapter3.Rackinstallation
Thissectionprovidesinstructionsforinstallingtheserversecurelyinarackcabinet.
Identifyingtherackspacefortheserver
Thistopicprovidesinformationonidentifyingthespaceneededtoinstalltheserverintherackcabinet.
Whenyouinstallthe2Userver,besuretochoosetheappropriaterackspacetoinstalltheserverinthe
rackasindicatedbelow:
1.InstallthesliderailsinthebottomUofthe2Uareaintherack.
2.Selectanavailable2Uspaceinyourracktoinstallyourserver.
Front Rear
Upper U
Lower U
Optional screw
to secure system
into the rack
Pins
Installingtherailsintherack
Theinformationinthistopicprovidesinstructionsabouthowtoinstalltherailsintherackcabinet.
Openingthefrontslideraillatches
Thistopicprovidesinformationabouthowtoopenthefrontslideraillatchestoinstallthesliderailsinto
therackcabinet.
Toopenthefrontslideraillatches,completethefollowingsteps:
1.Ifyourfrontsliderailsareshippedwiththefrontlatchesintheopenposition,proceedto“Opening
therearsliderailhooks”onpage6.
2.Ifyourfrontsliderailsareshippedwiththefrontlatchesintheclosedposition,completethefollowing
step:
a.Openthelatchbypushingthebluebuttonin1andpushingthelatchback2.
©CopyrightLenovo2015,and2012,2015
5
2
Openingtherearsliderailhooks
Thistopicprovidesinformationabouthowtoopentherearsliderailhooks.
Toopentherearsliderailhooks,completethefollowingsteps:
1.Selectthefirstsliderailyouwanttoinstall.
2.Pulltherearbracketallthewaybackuntilitclicksintoplace.
Note:EachsliderailismarkedwithLEFTFRONT/REARorRIGHTFRONT/REARonitsends.
Rack Right
Installingtherearendofthesliderailsintotherackcabinet
Thistopicprovidesinformationabouthowtoinstalltherearendofthesliderailsintotherackcabinet.
Toinstalltherearendofthesliderails,completethefollowingsteps:
1.Fromthefrontoftherackcabinet,lineupthetwopinsontherearofthesliderailinthelowerUof
theselected2Uontherearoftherackcabinet.
2.Pushtherailssothatthepinsgointotheholes.
3.Slidetherailsintotherackcabinettolocktherearofthesliderailsintotherackcabinet.
6LenovoSystemx3750M4RackInstallationInstructions
Rack Rear
Square hole rack
Round hole rack
Aligningthefrontofthesliderailstotherackcabinet
Thistopicprovidesinformationabouthowtoalignthefrontofthesliderailstotherackcabinet.
Toalignthefrontofthesliderailstotherackcabinet,completethefollowingsteps:
1.PullthesliderailsforwardandlocatethefrontlatchesintheappropriateUspacesinfrontoftherack
EIArails.
2.MakesurethatthefrontendisbeingrotatedintopositionwiththefrontlatchinfrontoftheEIA
railoftherack.
Rack Front
Installingthefrontendofthesliderailsintotherackcabinet
Thistopicprovidesinformationabouthowtoinstallthefrontendofthesliderailsintotherackcabinet.
Toinstallthefrontendofthesliderails,completethefollowingsteps:
1.Pressthebluebuttontoclosethebracketwiththepins.
2.Movethesliderailupanddowntoensuretherailisfullyengaged.
3.Repeatthestepsinthefollowingsectionstoinstalltheotherrailintotherackcabinet:
“Openingthefrontslideraillatches”onpage5
“Openingtherearsliderailhooks”onpage6
Chapter3.Rackinstallation7
“Installingtherearendofthesliderailsintotherackcabinet”onpage6
Aligningthefrontofthesliderailstotherackcabinet”onpage7
“Installingthefrontendofthesliderailsintotherackcabinet”onpage7
Note:Makesurethateachfrontlatchisfullyengaged.
Rack Fr ont
Installingtheserveronthesliderails
Thistopicprovidesinformationonhowtoinstalltheserveronthesliderails.
Toinstalltheserveronthesliderails,completethefollowingsteps:
1.Pullthesliderailsforward1untilthesliderailsclickintoplace.
2.Carefullylifttheserver.Tiltitintopositionoverthesliderailssothattherearnailheads2ontheserver
lineupwiththeslotsinthesliderails.
3.Lowertheserverdownuntiltherearnailheadsslipintothetworearslots.
4.Slowlylowerthefrontoftheserver3untiltheothernailheadsgointotheotherslotsonthesliderails.
Note:Makesurethefrontlatchcoversthefrontnailheadtoensuretheserverissecuredtothesliderails.
8LenovoSystemx3750M4RackInstallationInstructions
Lift point
Lift point
2
3
Slidingtheserverintotherackcabinet
Thistopicprovidesinformationabouthowtoslidetheserverintotherackcabinet.
Toslidetheserverintotherackcabinet,completethefollowingsteps:
1.Liftthelockinglevers1onthesliderails.
2.Pushtheserver2allthewayintotherackcabinetuntilitclicksintoplace.
Chapter3.Rackinstallation9
Installingthecablemanagementsupportbar
Thistopicprovidesinformationonhowtoinstallthecablemanagementsupportbar.
Notes:
Thecable-managementarmcanbeinstalledoneithersideoftherack.Thisdocumentshowsitbeing
installedontheleftsideoftherack.Toinstallthecable-managementarmontherightsideoftherack,
see“Installingthecablemanagementarmontherightsideoftherack”onpage23.
Theouterrailofthecablemanagementsupportbarmustbeinstalledonthesidethatthecable
managementarmisattachedto.
Toinstallthecablemanagementarmontheleft-rearsideoftherack,completethefollowingsteps:
1.Alignthecablemanagementarmstopbracketparalleltothesliderail.
2.Lowertheendofthecablemanagementsupportbar1tothesamesliderailtowhichyouplantoattach
thecablemanagementarm.
3.Rotatethecablemanagementsupportbartowardstherearoftheserver2.
Rack Rear
2
10LenovoSystemx3750M4RackInstallationInstructions
Connectingthecablemanagementsupportbartothecablemanagement
armstopbracket
Thistopicprovidesinformationonhowtoconnectthecablemanagementsupportbartothecable
managementarmstopbracket.
Toconnectthecablemanagementsupportbartothecablemanagementarmstopbracket,completethe
followingsteps:
1.Alignthecablemanagementarmstopbracketsothatthemetaltabisparalleltothecablemanagement
supportbar.
2.Placethetablocatedontheundersideofthecablemanagementsupportbarintothelowerhole
inthecablemanagementarmstopbracket
1.
3.Rotatethecablemanagementarmstopbracket2untilthemetaltabfacesthebackofthesliderail.
2
Connectingthecablemanagementarmstopbrackettothesliderail
Thistopicprovidesinformationonhowtoconnectthecablemanagementarmstopbrackettothesliderail.
Toidentifytheinsideandoutsidetabs,thecapitallettersIandOareprintedonthecablemanagementarm
tabsandthecablemanagementarmstopbracket.
Toconnectthecablemanagementarmstopbrackettothesliderail,completethefollowingsteps:
1.Installthecablemanagementarmstopbracket(withcapitalletterO)ontheouterslidemember(with
capitalletterO).
2.Makesurethatthecablemanagementsupportbarissecurelyinstalled.
Chapter3.Rackinstallation11
Rack Rear
Stop bracket
Installingthecablemanagementarm
Thistopicprovidesinformationonhowtoinstallthecablemanagementarmtotherackcabinet.
Toinstallthecablemanagementarm,completethefollowingsteps:
1.Placethecablemanagementarmonthecablemanagementsupportbar.
2.Aligntheinnerandoutertabsofthecablemanagementarmwiththeinnerandouterslotsonthe
sliderails.
3.Slidethecablemanagementarmtabsintoboththeinsideandtheoutsideslotsofthesliderail.
4.Pushthetabsuntiltheysnapintoplace.
Rack Rear
Openingandclosingthecablemanagementarmstopbracket
Thistopicprovidesinformationaboutthecablemanagementarmstopbracket.
Tomakeiteasiertorotatethecablemanagementarmonandoffthecablemanagementsupportbar,
completethefollowingsteps:
1.Openthecablemanagementarmstopbracketbypushingthetabslocatedaboveandbelowthe
supportstopbracket.
2.Rotatethecablemanagementarmawayfromtheserverafteropeningthesupportstopbracket.
12LenovoSystemx3750M4RackInstallationInstructions
3.
Rack Rear
Connectingandroutingthecables
Thistopicprovidesinformationonhowtoconnectandroutethecablestotheserver.
Notes:
Thelocationofthecablestrapsmaybeslightlydifferentonyourserver.
Usethecablestrapsprovidedontherearoftheservertoretainthecablesandpreventthemfromsagging.
Toconnectandroutethecablestothesever,completethefollowingsteps:
1.Opentheblueretainingclipsonthecablemanagementarmtoallowthecablestoberoutedinthe
cablemanagementarm.
2.Attachthepowercordsandothercablestotherearoftheserver(includingkeyboard,monitor,and
mousecables,ifrequired).
3.Routethecablesandpowercordsinthecablemanagementarm.
4.Closetheretainingclipsonthecablemanagementarm.
00
00
00
000000
000000
000000
00000000
00000000
00000
00000
00000
0
0
0
Rack Rear
00
Chapter3.Rackinstallation13
Securingthecableswiththehook-and-loopfasteners
Thistopicprovidesinformationaboutsecuringthecableswiththehook-and-loopfasteners.
Cablesmustbebundledwithhook-and-loopfastenersforpropermovementofthecablemanagementarm.
Notes:
1.MakesurethecablesdonotsagbelowtheUspacesotheywillnotgetcaughtonthelowerservers.
2.Allowslackinallcablestoavoidtensioninthecablesasthecablemanagementarmmoves.
3.Pulltheserverinandoutoftheracktwicetomakesurethecablesareroutedcorrectlyandtoensure
thereisnostrainonanycableswhileslidingtheserverinandoutoftherack.
00
00
00
000000
000000
000000
00000000
00000000
00000
00000
00000
0
0
0
Rack Rear
Velcro strap
Securingthecablemanagementarmandtheserverintherackfor
shipping
Thistopicprovidesinformationabouthowtosecurethecablemanagementarmandtheserverinthe
rackforshipping.
Tosecurethecablemanagementarmandtheserverintherackforshipping(iftheshippingtherackwiththe
serverinstalledorifyouareinavibration-pronearea).
1.InserttheM6screwstotherearoftheslides.
2.Useacabletietosecurethefreeendofthecablemanagementarmtotherack,ifneeded.
14LenovoSystemx3750M4RackInstallationInstructions
Rack Rear
Installingthefrontscrews
Thistopicprovidesinformationaboutinstallingthescrewsinthefrontoftheserver.
Toinstallthescrewsinthefrontoftheserver,ifneeded,whenyoumovetherackcabinet,orifyouinstallthe
rackcabinetinavibration-pronearea,completethefollowingsteps:
1.Pressonthereleaselatches1toslidetheserveroutoftherack.
2.InserttheM6screws2inthefrontoftheserver.
000000
000000
000000
000000
000
000
000
000
000
000
000
000
000
000
000
000
000
000
000
Chapter3.Rackinstallation15
16LenovoSystemx3750M4RackInstallationInstructions
/