RTS-500

Gianni Industries RTS-500, RTS-500N, RTS-600, RTS-600-S Installation guide

  • Hello! I am an AI chatbot trained to assist you with the Gianni Industries RTS-500 Installation guide. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
Infrared Sensor Exit Device
Specifications
Operating Voltage: 12~24VDC
Current Draw: Holding: 60mA/12VDC, Pull in: 50mA/12VDC
Relay Timer: 0.5, 5,10,20 Seconds
Sensor Range: Up to 10 cm (18% gray reflection)
Relay Rating: 3A/125VAC/30VDC
Faceplate material: stainless steel
Operating Temperature: -20~+70°C
Ambient Humidity: 5~95% relative humidity non-condensing
Visual Signals: Bi-colour LED display with audible Indication
1. European size & ANSI size faceplate
Features
Fig.A
Control Device
Request-to-exit
input contact
NC
COM
NO
+
NC
COM
NO
+
12 VDC
Power Supply
Electric Lock
Application & Installation
Relay Timer:
0.5 seconds
5 seconds
10 seconds
20 seconds
The RTS-500/RTS-600 Infrared
Sensor Exit Device and access control
package have many different ways of
connection, and the diagrams below
illustrate two recommended ways of
(Fail-Safe)
Fig.B
2. Infrared sensor adapts to any environment
3. 10 cm proximity range
4. Suitable for any access control units
5. Emergency push button (RTS-500)
6. Safe circuit design in case of power failure or emergency
exit
86mm
86mm
RTS-500 RTS-500N
RTS-600
70mm
114mm
5mm
RTS-600-S
70mm
114mm
35mm
12 VDC
Power Supply
Unit:mm
connection.
In Fig.A, RTS-500/RTS-600
connects to the Request-to-exit input
contact. Relay strike time can be set
as 0.5 seconds.
In Fig.B, RTS-500/RTS-600
controls a fail-safe locking device. If it
controls a fail-secure lock, the contact
is N.O. Relay strike time is door opening
time.
Note: To avoid burning when
RTS-500/RTS-600 controls an electric
lock, please pay attention to the limit
of relay rating:3A/125VAC/VDC.
Contact for
emergency
exit button
Relay active: N.C.
Illustration of safe circuit design
Power off: N.C.
Power on & Stand by: N.O.
Copyright
©
All Rights Reserved.
P-MU-RTS500 Publish: 2014.12.12
Holding: 40mA/24VDC, Pull in: 30mA/24VDC
/