Danfoss EPU 2350/2354 Operating instructions

Type
Operating instructions
BC-HM VI.72.J3.02 © Danfoss 9/97 1
Instruction
EPU 2350 and EPU 2354
Contents
System examples...........................2 - 6
Wiring diagrams.............................7 - 8
Wiring ................................................... 9
Temperature sensor connections ... 10
Master/slave units.............................10
Frost protection ................................11
Time control ......................................11
Controller settings .....................12 - 15
User settings .......................................
12
- a) Program time switch
- b) Temperature setting
- c) Function swtich
- d) Indications
Installer settings...........................
13 - 16
- f) Reduced temperature
- g) Integration time
- h) Proportional band
- i) Temperature difference
- j) Return temperature limiter
- k) Mini switches
Controller and sensor test ............... 16
Manual valve control ........................16
Mounting .....................................17 - 20
- Wall mounting
- Board or panel mounting
- DIN-rail mounting
- Several controls side by side
- Dismounting
- Time switch mounting
- Time switch replacement
087R9472
087R9472
2 VI.72.J3.02 © Danfoss 9/97 BC-HM
System example 1
System description
Hot-water-service system with primary
flow heat exchanger control and
secondary hot-water-service circulation.
Function
Valve controls primary flow to keep tap
temperature S1 constant.
At return temperature sensor control S4
reference temperature S1 is limited to
set value.
At time control tap temperature S1 can
be reduced and circulation pump P1 is
stopped.
Note
Circulation pump P1 is to be stopped
only if temperature sensor S1 is
mounted right in the heat exchanger (if
not, there might be risk of breaking the
control loop, which again will result in
heat loss)
WiringWiring
WiringWiring
Wiring
See wiring diagram, example 1 for EPU
2350 - 230 V or example 3 for EPU 2354
- 24 V.
SettingsSettings
SettingsSettings
Settings
Tap temperature can be set on button b)
BC-HM VI.72.J3.02 © Danfoss 9/97 3
System example 2System example 2
System example 2System example 2
System example 2
System descriptionSystem description
System descriptionSystem description
System description
Hot-water-service system with primary
temperature heat exchanger control and
secondary hot-water-service circulation.
FunctionFunction
FunctionFunction
Function
Mixing valve controls primary flow to
keep tap temperature S1 constant.
At return temperature sensor control S4
reference temperature S1 is limited to
set value.
At time control tap temperature S1 can
be reduced and circulation pump P1 is
stopped.
Note
Circulation pump P1 is to be stopped
only if temperature sensor S1 is
mounted right in the heat exchanger (if
not, there might be risk of breaking the
control loop, which again will result in
heat loss)
WiringWiring
WiringWiring
Wiring
See wiring diagram example 1 for EPU
2350 - 230 V or example 3 for EPU 2354
- 24 V.
SettingsSettings
SettingsSettings
Settings
Tap temperature can be set on button b)
4 VI.72.J3.02 © Danfoss 9/97 BC-HM
System example 3
System description
Hot-water-service system with
secondary temperature cylinder control
and secondary hot-water-service
circulation.
Function
Hot-water cylinder temperature is
maintained at system temperature level.
Mixing valve mixes cold and hot water to
keep tap temperature constant.
At time control tap temperature S1 can
be reduced and circulation pump P1 is
stopped.
BC-HM VI.72.J3.02 © Danfoss 9/97 5
System example 4
System description
Hot-water-service system with primary
temperature cylinder control and
secondary hot-water-service circulation.
Function
Cylinder heating coil is connected direct
to district heating system. The valve
controls primary flow in dependence of
hot-water cylinder temperature S1.
Return temperature sensor S4 keeps
return temperature from exceeding a set
limit.
At time control tap temperature S1 can
be reduced and circulation pump P1 is
stopped.
Wiring
See wiring diagram, example 1 for EPU
2350 - 230 V or example 3 for EPU 2354
- 24 V.
Settings
Cylinder temperature can be set on
button b). Return temperature limitation
is to be set as low as possible
considering heating time.
6 VI.72.J3.02 © Danfoss 9/97 BC-HM
System example 5System example 5
System example 5System example 5
System example 5
System descriptionSystem description
System descriptionSystem description
System description
Hot-water-service system with primary
flow heat exchanger control, charging
circuit cylinder control with one or two
sensors and secondary side hot-water-
service circulation.
FunctionFunction
FunctionFunction
Function
Heat exchanger is connected direct to
district heating system and primary
control valve controls charging circuit
temperature (S1). Hot-water cylinder has
one (S2) or two (S2 and S2*) sensors.
Pump (P2) in charge circuit is cut-in
when cylinder temperature S2 (top
sensor) is lower than cut-in temperature
and stopped when reaching cut-out
temperature S2* (bottom sensor).
At return temperature sensor control S4
reference temperature S1 is limited to
set value.
At time control tap temperature S1 can
be lowered and circulation pump P1 is
stopped.
Note
Circulation pump P1 is to be stopped only
if temperature sensor S1 is mounted
right in the heat exchanger (if not, there
might be risk of breaking the control
loop, which again will result in heat loss)
WiringWiring
WiringWiring
Wiring
See wiring diagram, example 2 for
EPU 2350 - 230 V or example 4 for
EPU 2354 - 24 V.
SettingsSettings
SettingsSettings
Settings
- Charge temperature S1 is set on
temperature button.
- Cut-in temperature S2 = S1 (setting
DI L 4) − ∆ T potentiometer j.)
Cut-out temperature S2* = S1
(setting DIL 4)
Note:
At hot-water service flow through heat
exchanger, mini-switch 5 must be set in
position ON (control) to maintain charge
temperature in circulation pipe during
pump P2 standby.
BC-HM VI.72.J3.02 © Danfoss 9/97 7
Wiring diagramsWiring diagrams
Wiring diagramsWiring diagrams
Wiring diagrams
Wiring diagram 2) for EPU 2350 (230 V)
Wiring diagram 1) for EPU 2350 (230 V)
8 VI.72.J3.02 © Danfoss 9/97 BC-HM
Wiring diagrams
Wiring diagram 3) for EPU 2354 (24 V)
Wiring diagram 4) for EPU 2354 (24 V)
BC-HM VI.72.J3.02 © Danfoss 9/97 9
Wiring
Terminal strips
Terminal strips with screw fastening wire
the controller.
Each terminal can wire up to 3 × 1.5
mm
2
or the like. The terminals are
encoded, so units with supply voltage
cannot be wired in the safety voltage part.
Wiring EPU 2350 - 230 V a.c.
Connections with supply voltage - (terminals 13 - 24)
Terminal Load
Zero (N) - 230 V a.c. 13
Phase (L) - 230 V a.c. 14
16 (close) 8 (2) A 250 V a.c.
Reversible gear motor 230 V a.c. - AMB, AMV
17 (open) 8 (2) A 250 V a.c.
Relay outlet 230 V a.c.- NC (R1) 21 - 22 8 (2) A 250 V a.c.
Relay outlet 230 V a.c. - NC (R2) 23 - 24 8 (2) A 250 V a.c.
Wiring EPU 2354 - 24 V a.c.
Connections with supply voltage - (terminals 13 - 24)
Terminal Load
Zero (N) - 24 V a.c. 13
Phase (L) - 24 V a.c. 14
16 (close) 8 (2) A 24 V a.c.
Reversible gear motor 24 V a.c.- AMB, AMV
17 (open) 8 (2) A 24 V a.c.
Relay outlet 24 V a.c.- NC (R1) 21 - 22 8 (2) A 24 V a.c.
Relay outlet 24 V a.c.- NC (R2) 23 - 24 8 (2) A 24 V a.c.
10 VI.72.J3.02 © Danfoss 9/97 BC-HM
Temperature sensor connection, etc. - safety voltage (terminals 1 - 12)Temperature sensor connection, etc. - safety voltage (terminals 1 - 12)
Temperature sensor connection, etc. - safety voltage (terminals 1 - 12)Temperature sensor connection, etc. - safety voltage (terminals 1 - 12)
Temperature sensor connection, etc. - safety voltage (terminals 1 - 12)
Sensor and remote unit mounting is described in instructions, which are delivered
together with the products.
Type Terminal
Temperature sensor - flow (S1) ESMU 10 - 11
Cylinder temperature sensor (S2)
ESMU 7 - 9
- top sensor in hot water cylinder
Cylinder temperature sensor (S2*)
ESMU 8 - 9
- bottom sensor in hot water cylinder
Temperature sensor - return (S4) ESMA/C/U 4 - 6
Temperature sensor - frost protection (S3) ESMA/C/T 11 - 12
Set point remote setting (S5) 4 - 5
External time switch signal connection ECA 9010 3 - 4
BUS for communication 1 - 2
Wire cross section: min 0.4 mm
2
Total length of all sensor and BUS
wires. Max. 150 meter.
Note!
The measure result might deviate due to
wire resistance. A resistance of 4 Ohm
corresponds to a deviation of about 1 K.
BC-HM VI.72.J3.02 © Danfoss 9/97 11
Master/slave units
EPU 2350 can be coupled via BUS with
other EPU or ECL controls
Address 15 is reserved for master
controller. When ECL controller is
connected to BUS, ECL is always
master and EPU is slave. Addresses 0,
1 or 2 are reserved for slave controls
(see speical settings).
Slave controls with address 0 (max. 8
slave controls) can receive outdoor
Frost protection
EPU 2350 and 2354 have built-in frost
protection to prevent sensor
temperatures from falling below +6 °C.
R1 and R2 are activated (circulation
pump cut-in) even when just one of the
sensor temperatures S1, S2, S2* or S4
falls below +6 °C.
When connecting a separate S3 frost
protection sensor any place in the
system can be frost protected at +2 °C.
temperature (frost protection sensor)
and time switch signals from the master
controller.
Slave controls with addresses 1 and 2
(max. one control per address) can
receive outdoor temperature signals
(frost protection sensor S3) and time
switch signals from master controller
and can send reference temperatures to
the master controller.
R1 and R2 are activated (circulation
pump cut-in) when sensor temperature
S3 falls below +2 °C.
If circulation pumps must operate at out-
door temperatures below +2°C outdoor
sensor ESMT must be mounted on S3.
When several controls are coupled out-
door temperature signal (frost protection
sensor S3) is transferred via BUS.
12 VI.72.J3.02 © Danfoss 9/97 BC-HM
Time control
EPU 2350/2354 can be time controlled
via a built-in time switch mounted in the
controller or via an external time switch
or manual switch. Relay outlets R1 and
R2 status depends on time switch setting.
Time switch type Reduced temp R1 R2
1-zone time switch follows zone 1 follows zone 1 always ON
2-zone time switch follows zone 1 follows zone 1 follows zone 2*)
ECA 9020 follows zone 3 follows zone 3 follws zone 4*)
*) Only at PI-control
when gold-plated contacts are used.
The contacts are connected directly to
terminals 3 and 4. Contacts close to
cut-in constant normal temperature.
b) ECA 9020
EPU can be time controlled/overridden
via control panel ECA 9020. Connect
terminals 1 and 2 (BUS).
One of the four ECA 9020 time swich
zones is addressed to control EPU.
EPU as Master
- address 15 = zone 3
EPU as Slave
- address 0 = no time control
- address 1 = zone 1
- address 2 = zone 2
Note!
ECA 9010 overrides ECA 9020 normal
or reduced temperature operations.
External time control
EPU can be time controlled via an
external signal. The signal can be
transferred from below units.
a) External time switch
or manual switch
EPU can be time controlled via an
external time switch or manual switch.
When the contacts are not gold-plated
use the override module ECA 9010.
ECA 9010 is connected on EPU control
terminals 3 and 4 to adapt the external
switch signal to EPU. Function switch
must be in position "time switch" and
time switch contact (NO) must close
when activated.
Connect switch with ECA 9010 terminals
2 and 3 for normal temperature override.
Connect switch with ECA 9010 terminals
1 and 3 for reduced temperature
override.
ECA 9010 for constant reduced
temperature override is not necessary
BC-HM VI.72.J3.02 © Danfoss 9/97 13
Controller settings
User settings
a) Programmable time switch
b) Temperature setting
c) Funktion switch
d) Indications
e) User guide
a) Time switch
Analog time switch is set in the required
normal and reduced temperature periods
in pushing riders for reduced
temperature settings towards the center
of the time switch.
Set actual time and week day vis-a-vis
the mark in turning the dial in arrow
direction
Digital time switch ECA 9016 or 9017,
see enclosed user guide.
b) Temperature setting
Use the temperature knop for setting
required storage or flow temperature
(reference temperature for S1). Setting
range 30 - 70 °C.
c) Funktion switch
Valve closes and circulation pump
stops, frost protection at 6 °C.
Constant reduced temperature.
Time switch override
Automatic changeover between
normal and reduced temperature
according to time switch settings.
Constant normal temperature. Time
switch is overridden.
Manual control. Controller function
off. Valve motor receives no control
signals, use button b) for manual
valve control.
d) Indications
ON - alight, when controller has been
connected and functions properly
- off if controller is defect or if S1
sensor is interrupted, short-
circuted or missing
- flashes, when frost protection is
active. Frost protection is active
when:
- S1, S2, S2* or S4 are lower
than +6 °C
- S3 is lower than +2 °C.
- flashes together with
when
function switch is set in position
. Number of interruptions show
number of connected sensors.
- alight at reduced temperature
control
- flashes together with ON when
function switch is in position
Number of number of connected
sensors.
alight as long as gear motor
receives signal to open the valve
(to increase temperature).
Shortest signal is 0.5 sec.
alight as long as gear motor
receives signal to close the valve
(to reduce temperature). Shortest
signal is 0.5 sec.
14 VI.72.J3.02 © Danfoss 9/97 BC-HM
neutral zone. The function is similar to a
3-position thermostat.
h)h)
h)h)
h)
Proportional band - XProportional band - X
Proportional band - XProportional band - X
Proportional band - X
pp
pp
p
Setting range 1 - 40 °K.
Proportional band states temperature
range, where motor control impuls
period is proportional to temperature
deviation. Beyond this range, the control
impulse is constantly ON. A small
proportional band is at risk of unstable
control.
i) Temperature difference - i) Temperature difference -
i) Temperature difference - i) Temperature difference -
i) Temperature difference -
TT
TT
T
Setting range is 1 - 30 °K
This function is in operation only in
storage charge systems with 1 or 2 S2-
storage sensors.
1 storage sensor:
S2 sensor temperature difference
between cut-in and cut-out temperature
2 storage sensors:
Temperature difference between cut-in
temperature (top sensor S2) and cut-out
temperature (bottom sensor S2*)
j) Return temperature limit - j) Return temperature limit -
j) Return temperature limit - j) Return temperature limit -
j) Return temperature limit -
Setting range 30 - 70 °C.
Return temperature is limited according
to temperature setting, potentiometer j).
Choose minimum or maximum
temperature limit (switch 1) and
amplification 4 or 8 (switch 2). S1
reference is reduced when return
Installer settingsInstaller settings
Installer settingsInstaller settings
Installer settings
f) Reduced temperature -
g) Integration time - T
n
h) Proportional band - X
p
i) Temperature difference at ON/OFF-
cylinder charge control - T
j) Return temperature limiter
k) Miniswitches
f) Reduced temperature -f) Reduced temperature -
f) Reduced temperature -f) Reduced temperature -
f) Reduced temperature -
Setting range 1 - 40 K and OFF.
Controls with time switch can reduce
normal temperature according to
potentiometer f) settings of period and
degrees
If potentiometer is set in pos. OFF
temperature will be reduced to frost
protection limit (+6°C) during the
required period.
g)g)
g)g)
g)
Integration time - TIntegration time - T
Integration time - TIntegration time - T
Integration time - T
nn
nn
n
Setting range 0 - 10 minutes and OFF.
Integration time states the time that runs
until I-function has changed the output
signal like P-function. A short time
results in a quick control but large
overshooting (risk of unstability)
If the potentiometer is set in pos. OFF,
the integration function is off and the
proportional band X
p
will equal the
BC-HM VI.72.J3.02 © Danfoss 9/97 15
k) Miniswitches
EPU 2350 and 2354 have eight
miniswitches (DIL-switches). The
miniswitches are used for special
settings and functions.
Switch 1 - Return limit function
Choose maximum or minimum return
temperature limit of potentiometer
temperature j). At maximum or minimum
limit return temperature is kept below or
above temperature setting, respectively.
S1 reference is reduced.
Switch 4 - operation difference
between S1 and S2
(This function is used only in charge
circuit systems)
Choose operation difference between
charge temperature (temperature
setting) and S2 sensor cut-out
temperature.
Switch 4 operation signal
ON 10 K
OFF 5 K
Switch 5 function
ON valve operates
OFF valve is closed
Switch 1 Funktion
ON max. limit
OFF min. limit
Switch 2 - Return limit amplificationSwitch 2 - Return limit amplification
Switch 2 - Return limit amplificationSwitch 2 - Return limit amplification
Switch 2 - Return limit amplification
Choose return limit amplification (i.e. S1
reference temperature reduction at each
return temperature deviation degree.
Switch 2 amplification
ON 8 times
OFF 4 times
Switch 3 - neutral zoneSwitch 3 - neutral zone
Switch 3 - neutral zoneSwitch 3 - neutral zone
Switch 3 - neutral zone
Choose neutral zone for PI-control
circuit. Valve motor receives no signal
when temperature is within the neutral
zone.
Switch 3 neutral zone
ON 3 K
OFF 1 K
Switch 5 - Charge temperature at
standby
(This function is used only in charge
circuit systems)
Choose charge temperature at standby,
i.e. charge temperature is maintained
(valve is operating) or frost protection
+6°C (valve is closed)
Switch 6 - Ventil/motor constant
Choose approx. valve motor operation
period from closed to open valve
Switch 6 function
ON 20 sec (quick)
Example:
AMV 323 - 1 s/mm
+ VMO, VR - 15 mm
OFF 120 sec (slow)
Example:
AMV 123 - 8 s/mm
+ VMO, VR - 15 mm
16 VI.72.J3.02 © Danfoss 9/97 BC-HM
Switches 7 and 8 - Addressing
When controller is coupled with other
EPU or ECL controls via BUS, the
controller must be given an address.
See paragraph "Master/slave units".
Following addresses are available:
Switch
Address
78
OFF O N 0
ON ON 1
O N OFF 2
OFF OFF 15
Controller self-test and sensor test
EPU 2350 and 2354 can operate both
self-test and sensor test. Set function
switch in position
. After approx. 5
sec. both ON and
will flash and show
test result. The result will be repeated
every 3rd second.
Test result can show:
1, 2, 3, 4, or 5 interruptions
Number of interruptions corresponds to
number of connected sensors. If the
number of interruptions does no
correspond, one or several sensors
might be defect or are not connected.
No light
Controller is defect or S1 sensor is not
connected.
Constant light
The controller is defect.
Manual valve control
When testing or adjusting gear motor
limit switches valve can be manually
controlled in setting function switch in
position
and turning temperature
button.
Open valve
Turn temperature button all the way to
the right (clockwise)
Close valve
Turn temperatue button all the way to
the left (anti-clockwise).
If the motor does not rotate in correct
direction wires must be interchanged, i.e.
terminals 16 and 17.
BC-HM VI.72.J3.02 © Danfoss 9/97 17
Monting
On wall
Use standard base plate or special base
plate with wall case for mounting EPU
controller.
The plate is fixed on a flat surface with
two 4 mm screws (standard base
plate) or three 4 mm screws (special
base plate). Be aware of the "UP"-arrow.
Then wire EPU controller as described in
paragraph "Wiring".
EPU is mounted in base plate (when
using speical base plate, note that the
controller is first of all to be fit into the
wall case) and screw up the center
screw behind the cover plate.
In panel
EPU can be built into a panel. The
opening is to measure 92 × 138 mm and
the plate is to be max. 3 mm thich.
Fix four retainer springs on the
controller, push it gently into the opening
and the springs will secure the controller
in the opening. The retainer springs are
delivered as accessories togeter with 2
terminals strips.
Wire EPU to the two terminal strips and
then mount them in the controller. The
terminals strips are encoded to prevent
exhange by mistake.
On DIN-rail
EPU can be mounted on a 35 mm DIN-
rail. Fix a spring - delivered as
accessory - on the base plate bottom
and then mount the base plate on the
DIN-rail.
18 VI.72.J3.02 © Danfoss 9/97 BC-HM
Several controllers in parallel
In panel
On wall or DIN-rail
DismountingDismounting
DismountingDismounting
Dismounting
Controllers in panels are dismounted in
pressing retainer springs together and
pushing controller out.
When retainer springs are not
accessible use a screw driver to tip out
the controller.
BC-HM VI.72.J3.02 © Danfoss 9/97 19
Time switch mounting
Remove glass cover, inside cover and
time switch cover and then mount time
switch.
Open the glass cover all the way to the
left - the pintles will then slide out. Tip
out inside cover and unscrew time switch
cover.
Time switch is placed in the center of the
opening with plugs downwards.
Time switch dismounting
Remove screws and gently tip out time
switch.
20 VI.72.J3.02 © Danfoss 9/97 BC-HM
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20

Danfoss EPU 2350/2354 Operating instructions

Type
Operating instructions

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI