BC-HM VI.74.Y5.02 © Danfoss 9/96 9
Function test
The LED indicates whether ECL 9350 is
in operation and indicates the valve
control level. In the auto-test function for
sensors and controller, it also reports
faults.
Control status
During normal operation, the function
selector is on
, , or and the
LED lights up.
Reversible motor
LED lights up constantly:
The flow temperature is correct and the
motor receives no pulses. The valve is
not active.
LED lights up constantly and is then
interrupted twice:
The flow temperature is below the
calculated temperature. The motor
opens the valve.
LED lights up constantly and is then
interrupted three times:
The flow temperature is above the
calculated temperature. The motor
closes the valve.
Auto-test of controller and sensors
Set function selector on position
.
After about 5 seconds the LED begins to
flash. This indication is repeated approx.
every 3 seconds.
LED off:
Controller defective or flow temperature
sensor not connected.
LED lights up with 1, 2, 3 or 4
interruptions:
The number of flashes corresponds to
the number of installed sensors. If it
does not, one or more of the sensors is
short-circuited or not connected.
LED constantly on:
The controller is defective.
Manual valve control
Set function selector on
.
To open the valve, turn the temperature
setting knob b) fully clockwise. To close
the valve the knob must be turned
counterclockwise.
If the direction of motor rotation is
incorrect, swap over the connections on
controller terminals 16 and 17.
Remote override function (from and
including generation 20)
The sensor inputs can be used as
override ("
" or " " ) if external override
module ECA 9010 is connected (to avoid
contact resistance). ECA 9010 can be
connected to the following terminals (see
instruction for further information):
Terminal 3 - room sensor
Terminal 6 - return sensor
Terminal 7 - boiler sensor