Danfoss EPU 2370 Operating instructions

Type
Operating instructions
BC-HM VI.72.M4.02 Danfoss 11/97 1
Instructions (user manual)
EPU 2370
Contents
Installation........................................2-4
Electrical connections
and wiring diagram..........................5-6
Selection of system type ................... 7
Setting of system type .......................8
Operation........................................9-10
- program time switch
- + and - keys
- position selector
- function selector
Time control .................................11-12
- external time switch
- override with ESME
- provisional override to normal
temperature
External setpoint ..............................12
General frost protection ..................12
Digital settings.............................13-21
- operation
- position overview (matrix)
- position function description
(pages 15-21)
System types................................22-48
- see overview on page 7
087R9367
087R9367
2 VI.72.M4.02 Danfoss 11/97 BC-HM
Installation
Wall mounting
For wall mounting use either a standard
base plate or a special base plate with
associated case.
Fasten the base on a flat surface using
two 4 mm screws (standard base
plate) or three 4 mm screws (special
base plate). Remember that the arrow in
the bottom of the base plate must point
upwards.
The control can now be wired (see
section “Electrical connections”).
The control must be mounted in the
base (with special base plate mount
case first) and fastened with the staybolt
under the cover plate.
Panel mounting
(in cutout)
The control can be mounted in a panel
with a cutout of 92 x 138 mm (max.
sheet thickness 3 mm). Fit four retainer
springs on the control before mounting.
The retainer springs are available as
accessories, the set consisting of four
springs and two terminal strips.
Electrical connections must be made to
the loose terminal strips which can then
be mounted. The terminal strips are
coded to prevent mains voltage section
from being connected to low-voltage
section.
Mounting on DIN rail
The control can be mounted on a 35 mm
DIN rail. The base must be fastened by
a spring (available as an accessory)
which must be fitted at the rear of the
base before mounting on the DIN rail.
BC-HM VI.72.M4.02 Danfoss 11/97 3
Several EPU 2370 controls, side by side
Panel mounting
Wall mounting or on DIN rail
Removal from panel
When the control is mounted in a panel
cutout the easiest way to remove it is to
depress the retainer springs on the rear
and press it out of the cutout.
If there is no access to the rear of the
control, it can be tilted out of the cutout
by inserting a screwdriver in the two
recesses provided in both ends of the
unit.
4 VI.72.M4.02 Danfoss 11/97 BC-HM
Time switch mounting
An analog or digital time switch can be
fitted by first removing the plastic lid,
cover plate and time switch cover.
Remove the lid by pressing it towards
the left. The spigots will slide out of the
hinges. The time switch cover can be
removed by taking out the two screws.
Insert the time switch with pins
downwards and centre it in the case.
Then secure time switch and frame with
the screws provided.
Replacement of time switch
The time switch can be removed after
the screws have been taken out by
carefully tilting it from the top with a
small screwdriver.
BC-HM VI.72.M4.02 Danfoss 11/97 5
Electrical connections and
wiring diagram
Connection to 230 VAC -
(terminals 13-24)
The control must be connected using the
terminal strips with screw terminals.
Up to 3 x 1.5 mm² or corresponding
wires can be connected in each
terminal. The terminal strips are coded
to prevent terminal strips with mains
voltage being connected to sensor
terminals.
Terminal Load
Neutral (N) - 230 V~ 13
Phase (L) - 230 V~ 14
16 (close) 8(2)A 250V~
Reversible gear motor 230 V~, AMB, AMV etc.
17 (open) 8(2)A 250V~
Relay output R1 - 230 V~ (NC) 21 - 22 8(2)A 250V~
Relay output R2 - 230 V~ (NC) 23 - 24 8(2)A 250V~
Connections for sensors, etc. -
safety voltage (terminals 1 - 12)
Sensor mounting is described in the
instructions enclosed with the product.
Wire cross-section: min. 0.4 mm²
Total length of all sensor and BUS
wires: max. 150 metres.
Type Terminal
S1 flow/duct (PI circuit) ESMA/B/C/U 10 - 11
storage tank upper sensor ESMB/U
S2 7 - 9
room sensor (P circuit) ESMR
S3 frost protection sensor ESMB/U/T 11 - 12
S4 return temperature sensor ESMA/B/C/U 4 - 6
S5 external setpoint ESME 4 - 5
storage tank lower sensor ESMB/U
S6 8 - 9
compensation sensor ESMR/T
External time switch/override ECA 9010 3 - 4
Communication BUS 1 - 2
Note!
Wire resistance can give measurement
error. A resistance of 4 ohm
corresponds to a temperature increase
of about 1 degree.
6 VI.72.M4.02 Danfoss 11/97 BC-HM
Wiring diagram (general)
The above wiring diagram shows all
connection possibilities for sensors, etc.
In the individual system types, the
necessary electrical connections are
shown with full lines. The remaining
possibilities are chain-dotted (see
system types on pages 22-48).
BC-HM VI.72.M4.02 Danfoss 11/97 7
Selection of system type
EPU 2370 is a multipurpose control for
use with several different types of
systems. Therefore the type of system
must be selected before the control is
operated. The selection procedure is as
follows: 1) Connect sensors, 2) Connect
voltage, 3) Select system type.
The individual system type numbers
denote different control principles. When
the necessary sensors have been
connected and the system type
selected, control operation on that
principle is automatically activated.
The following system types can be
selected in P0.2 (see also page 8):
System
System-
Description type Page
type
number
Installation 0
No control, but sensor temperatures can be
read off and valve motor and relay outputs can be
controlled manually.
Hot-water-service system 1 22-29
Control of flow heat exchanger with 1-A and 1-B
two and three-way valve - (PI).
Control of hot-water-service system with 1-C
secondary mixing - (PI)
Control of heat exchanger - storage tank charging with 1-D and 1-E
one or two tank sensors - (ON/OFF + PI).
Radiator system 2 30-33
Constant flow temperature control - (PI) 2-A
Constant room temperature control - (P+PI) 2-B
Water to air system (unit heater) 3 34-37
Constant room temperature control - (P+PI) 3-A
Floor heating system 4 38-41
Constant flow temperature control - (PI) 4-A
Constant room temperature control - (P+PI) 4-B
Ventilation system 5 42-45
Constant duct temperature control - (PI) 5-A
Constant room temperature control - (P+PI) 5-B
Refrigeration system 6 46-48
Constant brine temperature control - (PI) 6-A
Constant room temperature control - (P+PI) 6-B
8 VI.72.M4.02 Danfoss 11/97 BC-HM
Setting of system type
number
- Remove the black cover plate.
- Set the position selector (f) on 0.
- Press the + key (d) twice.
The display will now change between
P0.2 and a number between 0 and 6.
- With a pointed object, press the SET
key (i). The number will begin to flash.
- Press either the + or - key (d or e)
until the display shows the required
system type number.
- Press the SET key (i) to store the
required system type number.
- Refit the black cover plate.
Control operates according to factory-
set values.
Note
If the factory-set values in the control
are to be changed, see the pages 13-48
or contact Danfoss.
Display of actual temperature
Actual temperature (hot water, flow or
room temperature) can be read off with
the function selector (f) on
(pos. 7).
Setting required normal temperature
Set the position selector (f) on
(pos.
8). The temperature can be increased or
reduced by pressing the + or - key.
Setting required reduced temperature
Set the position selector (f) on (pos.
9). The temperature can be increased or
reduced by pressing the + or - key.
BC-HM VI.72.M4.02 Danfoss 11/97 9
Operation
a) Program time switch
b) Light emitting diode
c) Display
d) + key
e) - key
f) Position selector
g) Function selector
h) User instructions
a) Program time switch
If an analog program time switch is
mounted it can be set for normal and
reduced temperature periods by pushing
the slides in towards the middle to set
the periods in which an reduced
temperature is required.
The correct time and day can be set
opposite the markings by turning the dial
in the direction of the arrow.
If a digital time switch type ECA 9016 or
9017 is used, see the instructions
enclosed with the time switch.
b) Light emitting diode
The diode indicates as follows:
- lights up constantly when the control
is on.
- flashes when an alarm signal is
registered. At the same time, an
alarm code can be read off in P7.1.
See description of alarm codes in
section on settings, page 21.
c) Display
The display shows diverse temperatures
and settings.
d) and e) + and - keys
These keys are for use when setting and
programming the control.
f) Position selector
The function selector is for use in
selecting temperature indication and
programming. The selector can be set in
ten different positions, but on the cover
plate only three positions and associated
symbols are shown.
The display indicates the actual
temperature at sensor S1 (PI
control) or sensor S2 (P + PI
control).
T
The display indicates the required
normal temperature. The
temperature can be changed using
the + and - keys.
T
The display indicates the required
reduced temperature. The
temperature can be changed using
the + and - keys.
The remaining seven positions are used
for indicating other system temperatures
and in programming (see digital settings,
page 13).
10 VI.72.M4.02 Danfoss 11/97 BC-HM
g) Function selector
Control stopped, but system frost-
protected at 6 °C.
Time control not possible.
Constant reduced temperature.
The status of relay outputs depends
on the type of system selected.
Changeover between normal and
reduced temperature, as set on the
time switch.
The status of relay outputs depends
on the type of system selected.
Constant normal temperature.
The status of relay outputs depends
on the type of system selected.
Manual operation
All control functions inactive. The
control valve motor can be
operated manually with + and -
keys.
Relay outputs R1 and R2 can be
operated manually by pressing the
SET key (i) (see page 13).
The following combinations are
possible:
R1 (I) R2 (II)
00
01
10
11
0 = open contact
1 = closed contact
In P0.0 the relay status and motor
function are displayed by horizontal
bars. A horizontal bar means
closed contact, see page 15, P0.0
BC-HM VI.72.M4.02 Danfoss 11/97 11
Funktion Resistance
Normal temperature Short circuited
Reduced temperature 820
Time control
The temperatures of hot-water-service,
room, flow or duct can be reduced
(increased) by a time program, provided
a time switch is built into the control (see
section on time switch mounting, page
4). Alternatively, an external time switch
can be connected. Time control is also
possible through ECA 9020 or a master
control connected to the BUS.
By setting in P0.3 it is possible to select
precisely the zone that is to control
normal and reduced temperatures, relay
output R1 and relay output R2.
(Changeover between normal and
reduced temperature always follows the
zone that controls R1).
For position P0.3, see page 15.
External time switch
External time control is possible via
override module ECA 9010 on time
switch input terminals 2, 3 and 4. Time
control applies only to relay R1 and can
only be received by the EPU when the
function selector is in position
.
ECA 9010 is necessary when the
contact set in the external time switch is
not gold plated.
The contact set must be connected to
one of the ECA 9010 inputs. The
following time control functions are
possible:
If the contact set is gold plated,
connection can be made direct to control
terminals 3 and 4. Closed contact gives
normal temperature.
ECA 9010
Function
terminal
Normal temperature 2 and 3
Reduced temperature 1 and 3
12 VI.72.M4.02 Danfoss 11/97 BC-HM
Override with ESME
External override is possible with remote
control unit ESME connected to
terminals 4 and 5. The override signal
applies only to relay output R1 and can
only be received by the control when the
function selector is in position
.
Provisional override to normal
temperature
Provisional override to normal
temperature for 2 hours is possible when
an external override unit is used (ESME
connected to terminals 4 and 5 or
external time switch connected to
terminals 3 and 4).
Override can be started by setting the
ESME or time switch function selector
on
for 5-30 seconds and then back to
.
Override can be annulled by setting the
function selector on
for at least 5
seconds and then back to
.
External setpoint
Normal temperature can be set
externally with the potentiometer in the
remote control unit (ESME). ESME must
be connected to terminals 4 and 5. It
overrides the normal temperature setting
on the control in P8.0. The setting range
becomes ±20 K about the middle
temperature setting in P5.3 (approx. 2 /
degree).
Note! Override or external setpoint
connected to terminals 4 and 5 is not
possible when an external time switch is
connected to terminals 3 and 4.
General frost protection
EPU 2370 has a frost protection function
which ensures that the measured
temperature at the sensors does not fall
below 6°C. If the temperature at one of
the sensors, S1, S2 or S4, is lower than
6°C, relay contacts R1 and R2 become
activated. When all sensor temperatures
are higher than 6°C the relay contacts
return to their initial position, after a
delay of 3 minutes.
In applications 3 and 5 the delay
depends on the setting in P.4.3.
Note:
Actual frost protection depends on
the application selected.
It is also possible to protect the system
against frost at any point by connecting
a separate S3 sensor. Frost protection
limits must be set in P3.1 (see digital
settings).
BC-HM VI.72.M4.02 Danfoss 11/97 13
Digital settings
Operation
The system temperatures and settings
can be controlled or changed by using
the display (c) and keys (d), (e), (f), and
(i).
Each control and setting range has a
“given” position, e.g. P3.4 where 3 refers
to row 3 and 4 to column 4. (See
position overview (j) on next page).
Position selection
The switch (f) selects a row between 0
and 9, keys + and - select a column
between 0 and 4.
When a position is selected, the display
alternates between the position number
(e.g. P2.3) and a value (e.g. 70°C).
Note! In column 0 only values are
displayed.
Changing values
1) Select the required position.
2) Press SET once - the display flashes.
3) Change the value with the (+) and (-)
keys.
4) Press SET to store the value.
Note:
It is not possible to make settings before
the system type number has been
chosen. When this has been done, only
the necessary settings are displayed.
There is a set of factory settings for
each type of system. These values can
be changed as desired. (See selection
of system type, page 7).
Resetting factory settings
To begin again with factory settings,
RESET can be accessed by selecting
P0.2 and then pressing the SET key
twice.
14 VI.72.M4.02 Danfoss 11/97 BC-HM
Row (–) Column 0-4 (+)
0-9
01234
0 P0.0 P0.1 P0.2 P0.3 P0.4
Status Software System Time switch Bus
generation number channel select address
0-15 0,1,2,3,4 0-15
1 P1.0 P1.1 P1.2 P1.3 P1.4
S1 actual S1 reference Total stop Balance Motor
temperature PI circuit 0 or 1 temperature constant
PI circuit -20 til 110 °C 1-899 s
2 P2.0 P2.1 P2.2 P2.3 P2.4
S2 actual S2 reference Temp.diff. Anti-bacteria X
p
- propor-
storage tank/ storage tank/ TS1-TS2 function tional band
room temp. room temp. 1-30 °C 0-99 °C / - - 1-199 K
3 P3.0 P3.1 P3.4
S3 actual S3 frost T
n
- integra-
temperature protection limit tion time
2-10 °C / - - 1-899 s
4 P4.0 P4.1 P4.2 P4.3 P4.4
S4 actual S4 return Return limit Warm-start N
z
-
return max./min. amplification delay time neutral zone
temperature +(20-99) or ±(0-20) 1-899 s 0-9 K
-(20-99)
5 P5.0 P5.3 P5.4
S5 actual S5 Mid-point Tmax.
ext. setpoint ext. pot. PI circuit
0-99 °C -20 to 110 °C
6 P6.0 P6.1 P6.2 P6.3 P6.4
S6 (S2*) actual S6 reference Compensation Compensation Tmin.
temperature storage tank/ base point I/ factor I PI circuit
compensation diff S2-S6 ±(0-20) -20 to 110 °C
temperature ±(0-90)
7 P7.0 P7.1 P7.2 P7.3 P7.4
S1/S2 actual Alarm code Compensation Compensation K
p
- propor-
temperature base point II factor II tional factor
±(0-90) ±(0-20) 0-30
8 P8.0
Normal
temperature
-20 to 110 °C
9 P9.0
Reduced
temperature
-20 to 110 °C
*
See description of position functions, pages 15-21.
Factory settings are shown under the system type concerned, see pages 22-48.
Position overview (matrix)
*
BC-HM VI.72.M4.02 Danfoss 11/97 15
P0.0 Status
Relay outputs R1 and R2
and valve motor status
displayed as horizontal bars.
A horizontal bar means contact
closed in relay.
P0.1 Software generation
Control software generation displayed.
P0.2 System type number 0-15
Setting of required system:
0 Installation. Control not possible, but sensor temperatures can be read off,
valve motor and relay outputs can be manually controlled.
1 Hot-water-service system (PI and ON/OFF + PI)
2 Radiator system (PI and P + PI)
3 Water to air system (unit heater) (PI and P + PI)
4 Floor heating system (PI and P + PI)
5 Ventilation system (PI and P + PI)
6 Refrigeration system (PI and P + PI)
(see system selection, page 7)
P0.3 Time switch channel selection 0,1,2,3,4
Setting of time switch channels to control relay outputs R1 and R2. Reduced
temperature always follows the channel controlling R1.
Relay output R2
Reduced temperature and relay output R1
x can be set at the following values:
0 No time control
1 Time control - channel 1 on analog time switch or digital time switch or
channel 1 on ECA 9020.
2 Time control - channel 2 on digital time switch or channel 2 on ECA 9020.
3 Time control - channel 3 on ECA 9020 or channel 1 on master control.
4 Time control - channel 4 on ECA 9020 or channel 2 on master control.
Override of relay output R1 possible with external override unit or with function
selector, irrespective of setting in P0.3.
Description of position functions
Relay output R1
Relay output R2
Reduced temperature
Valve closed
Valve open
xx
16 VI.72.M4.02 Danfoss 11/97 BC-HM
P0.4 Bus address 0 - 15
Setting of control address. Master control must always have address 15 and slaves
always 0-14.
Master control
Transmits:
Time switch signal and S3 temperature
Receives:
Reference temperature
Slave regulator
Address 0
Receives:
Time switch signal or S3 temperature*
Address 1-14
Transmits:
Reference temperature
Receives:
Time switch signal and S3 temperature*
*Master control S3 temperature can only be received under the following conditions:
- no sensor S3 on slave control
- slave control P3.1 must be set within range 2-10°C
P1.0 Actual temperature at sensor S1
Display shows actual temperature at sensor S1 in PI circuit.
P1.1 Required temperature at sensor S1
Display shows temperature required (reference temperature) at sensor S1 in PI
circuit. Reference temperature is the sum of balance temperature and diverse
compensations.
P1.2 Valve function/Total stop: 0 or 1
Valve function (systems 1-D and 1-E)
0 When storage tank charging is finished the valve closes (system without
circulation or system with circulation through tank - 1-D).
1 When storage tank charging is finished the valve continues to control and
maintains charging temperature in circulation line (system with circulation
through heat exchanger - 1-E).
Total stop (system 2-6)
0 On reduced operation, control according to reduced temperature as set in
P9.0.
1 On reduced operation, control according to frost protection temperature
6°C. If room temperature falls below set value in P9.0, control again
according to normal temperature (P8.0) until temperature rises 1°C.
P1.3 Balance temperature for S1 reference: -20 to 110°C
When sensor S2 is connected (P + PI control) the PI circuit reference varies around
the balance temperature. The basic setting of the balance temperature depends on
the system selected. The balance temperature is adaptive and can vary ±5 K
around the set value. The displacement is not displayed in this position.
P1.4 Motor constant: 1 - 899 s
Setting of valve motor running time from fully closed to fully open valve for the valve/
motor combination selected. When the correct time for the motor/valve combination
is set, the Tn integration time can be set in seconds (P3.4).
BC-HM VI.72.M4.02 Danfoss 11/97 17
P2.0 Actual temperature at sensor S2
Display of actual temperature at sensor S2.
P2.1 Required temperature at sensor S2
Display of temperature required (reference temperature) at sensor S2.
P2.2 Temperature difference between S1 and S2: 1 - 30°C
(System 1 D and 1 E only)
Setting of temperature difference between S1 charging temperature and sensor S2
(sensor S6) cutout temperature.
P2.3 Anti-bacteria function: 10 - 99°C or (- -)
Setting of temperature the storage tank is to reach when the anti-bacteria function is
cut in. Duration and frequency must be set on the time switch controlling relay
output R2.
The anti-bacteria function is OFF when (- -) is displayed.
P2.4 Proportional band - Xp: 1 - 199 K
Setting of proportional band - Xp. The proportional band gives the temperature
range in which the length of motor control pulse is proportional to the temperature
deviation. Outside this range the control pulse is constantly ON. With a small
proportional band there is a risk of instability.
P3.0 Actual temperature at sensor S3 (frost sensor)
Display of actual temperature at sensor S3.
If a KP thermostat is connected, the display becomes “- - -” when the input is short-
circuited.
P3.1 Required frost protection temperature at sensor S3: 2 - 10°C or “- -”
Setting of the temperature at which the system is to be frost-protected when frost
protector S3 is used. All Pt 1000 type sensors can be used. If “- - ” is set in the
display no S3 temperature can be received from the master control.
P3.4 Integration time - Tn: 1 - 899 s
Setting of integration time - Tn. The integration time expresses the time that elapses
until the I-function has changed the output signal like the P-function. A short
integration time gives fast control but with large overshoot (risk of instability).
18 VI.72.M4.02 Danfoss 11/97 BC-HM
P4.0 Actual return temperature at sensor S4
Display of actual return temperature measured by sensor S4.
P4.1 Required return temperature at sensor S4: ±(20-99)°C
Setting of temperature at which return temperature limitation is to begin. The
limiter can function as max. or min. limiter.
Positive value (+): max. limit
Negative value (-): min. limit
P4.2 Return temperature limiter influence on reference temperature:±(0-20)
When return temperature is higher (max. limit) or lower (min. limit) than the set
limit in (P4.1) the reference is increased or reduced.
The value determines the magnitude of the change (amplification) and the sign
determines the direction.
Positive value (+): reference increased
Negative value (-): reference reduced
P4.3 Warm-start delay time: 1 - 899s
Setting of relay R1 delay. R1 is delayed at warm-start after night set-back and at
start after frost protection. (Applications 2, 3, 4 and 5 only.)
P4.4 Neutral zone - Nz: 0 - 9 K
Setting of neutral zone for PI circuit. When the temperature lies within the neutral
zone, the motor receives no pulses.
P5.0 External setpoint - S5: -20 to 119°C
Display of set point set with external potentiometer.
The setpoint applies only to S1 with (PI) control and S2 with (P + PI) control.
P5.3 Middle temperature for external setpoint: 0 - 99°C
Setting of middle temperature - setting range for external potentiometer.
Note: The input to external setpoint has a time constant of 1 minute.
P5.4 Maximum limiter in PI circuit: -20 to 110°C
Setting of highest permissible temperature in PI circuit.
BC-HM VI.72.M4.02 Danfoss 11/97 19
P6.0 Actual temperature at sensor S6
Display of actual temperature at sensor S6.
Sensor S6 can be used as follows:
- Lower sensor in hot-water-service storage tank in a tank-charging system (cutout
temperature).
- Compensation sensor, heating, refrigeration and ventilation systems.
P6.1 Required temperature at sensor S6
Display of temperature required at sensor S6 (reference temperature for decoupling
hot-water-service charging system when two sensors are used).
P6.2 System 1: Storage tank temperature differential: ±(0-90) K
Setting of differential between cutin and cutout temperatures in tank-charging
system.
System 2-6: Compensation I: ±(0-90)°C
Setting of temperature giving base point for compensation I.
Compensation influences sensor S1 reference.
The value indicates the temperature at which compensation begins. The sign
indicates maximum or minimum compensation.
(+): max. compensation
(-): min. compensation
20 VI.72.M4.02 Danfoss 11/97 BC-HM
P6.3 Compensation factor: ±(0-1-20)
Setting of value which states compensation influence on reference temperature (see
P6.2).
The sign of the value indicates increase or reduction of reference temperature on
compensation.
(+): reference increased
(-): reference reduced
P6.4 Minimum limitation in PI circuit: -20 to 110°C
Setting of lowest permissible temperature in PI circuit.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48

Danfoss EPU 2370 Operating instructions

Type
Operating instructions

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI