BC-HM VI.76.H6.02 Danfoss 9/97 15
Total stop
The system can be cut out so that a flow
temperature of only 10 °C is maintained
in connection with reduced temperature,
see P8.4. During total stop, no account is
taken of room temperature.
k) Required flow temperature in
charging circuit
For service water heating, the flow
temperature in the charging circuit can
be set within the range 30 - 110 °C.
Factory setting: 70 °C.
Note:
Hot-water-priority or parallel operation
must be set digitally in P3.2 (see digital
settings). The hot-water-service
conditions must be set in P4.3 og P4.4.
Reduced temperature without room
temperature sensor
Reduction of flow temperature in
connection with reduced temperature
can be seen in the above diagram.
(example of heat curve slope 1.0). The
table shows different settings (2, 4, 6
and AUTO).
switch to room heating is not accepted, a
run-on time in minutes for pump P2 can
be set in P9.3.
If a certain run-on time is set, the control
valve closes after service water heating
has been completed. After the set run-on
time, pump P2 cuts out and pump P1
(radiator circuit) cuts in. Finally, the
control valve opens.
Min. flow limitation
If the valve is almost closed, a signal
switch in the motor can override
controller ECL 9370 and completely
close the valve. After a set time (P9.3)
the valve is opened again.
(Connection, see page 9).
Special functions
Heat time
The heating-up time is monitored when
the service water in the hot-water-
storage tank is being heated.
When water heating takes more than 40
minutes there are two possibilities:
A: If the cut-in temperature is exceeded
- system switch to radiator heating.
B: If the required cut-in temperature is
not exceeded, service water heating
remains cut-in for a further
40minutes.
Run-on time, charge pump (P2)
When service water heating has been
completed, room heating is cut in
immediately on demand. If immediate