Reznor PEH Operating instructions

Type
Operating instructions
P/N 261698, Page 1
Form CP-DMPR MTR 159877
Instructions for Replacement Kit, P/N 261697
Applies to: Models with Damper Motor, P/N 159877,
Belimo Model AFB24-MFT95-US
www.ReznorHVAC.com; (800) 695-1901
©2014 Reznor, LLC. All rights reserved.
Trademark Note: Reznor
®
is registered in the United States and other countries.
0514 Form CP-DMPR MTR 159877 (Version 0.1)
Application
Damper actuator identied as P/N 159877 has been changed by the manufac-
turer. Belimo Model AFB24-MFT95-US has been replaced by Belimo Model
AFX24-MFT95-US. Both models are attached in the same manner and perform
the same function; however, the wire terminal designations and wire colors dif-
fer. Follow the instructions below when replacing a Model AFB24-MFT95-US
damper motor with a Model AFX24-MFT95-US.
Instructions
1. Turn off the gas and the electric.
2. Disconnect the six damper motor wires from their various connections and
remove the damper motor.
3. Install the new damper motor in the same location. Refer to the wiring dia-
gram on the unit to determine where to connect the wires listed in the table.
New Motor Wires*
Connect new motor wire to Terminal or Twist-on Wire Con-
nector shown on the Unit Wiring Diagram for connecting
Terminal* Color
R White -- the white wire from the “old” damper motor Terminal 4
B Gray -- the white wire from the “old” damper motor Terminal 5
W Pink -- the white wire from the “old” damper motor Terminal 3
U Orange -- the white wire from the “old” damper motor Terminal 6
+ Red -- the red wire from the “old” damper motor Terminal 2
- Black -- the black wire from the “old” damper motor Terminal 1
FIGURE 1 - Match the Wire Colors on the New Damper Motor with the Wire Terminal
Designations on the Old Damper Motor to determine where to connect the wires.
4. Verify that all connections are correct and secure and test for proper oper-
ation. For future reference, keep this form with the wiring diagram.
R BK
W
“OLD” removed DAMPER MOTOR
W
W
W
6
3
5
4
BELIMO Model AFB24-MFT95-US
R BK
W
CCW for Option AJ1
(left side controls)
NOTE: Spring rotation is
CW for Option AJ2
(right side controls)
GY
PK
O
U
W
B
R
+ -2 1
“NEW” replacement DAMPER MOTOR
BELIMO Model AFX24-MFT95-US
* NOTE: The wires on the
replacement motor are bundled
and a specic “terminal” is not
physically discernible. Match
the new wire colors to the “old”
motor terminal designations as
listed in the table and illustrated
in FIGURE 1.