BEKA BA374E is an intrinsically safe two-input field mounting Timer or Clock, suitable for exterior surface mounting in industrial environments. It can measure and display elapsed time between external events, or control external events via two control outputs. When configured as a Clock, it displays local time and can turn on and off twice in each 24-hour period. It has a separate terminal compartment for easy access and can be configured via four front panel push buttons.

BEKA BA374E is an intrinsically safe two-input field mounting Timer or Clock, suitable for exterior surface mounting in industrial environments. It can measure and display elapsed time between external events, or control external events via two control outputs. When configured as a Clock, it displays local time and can turn on and off twice in each 24-hour period. It has a separate terminal compartment for easy access and can be configured via four front panel push buttons.

1. DESCRIPTION
The BA374E is a eld mounting intrinsically safe, instrument
with a separate terminal compartment which can be
congured as a Timer or as a Clock. As a Timer the BA374E
can measure and display the elapsed time between external
events, or control external events via two control outputs.
When congured as a Clock the BA374E displays local time
and the control outputs can turn on and o twice in each 24
hour period.
This abbreviated instruction sheet is intended to assist with
installation, a comprehensive instruction manual describing
safety certication, system design and conguration may be
downloaded from the BEKA website or may be requested
from the BEKA sales oce.
The BA374E Timer or Clock has IECEx, ATEX and UKEX
intrinsic safety certication for use in ammable gas
atmospheres, plus ETL and cETL gas and dust certication.
The certication information label, which is located on the top
of the instrument enclosure, shows the certication numbers
and codes. Other certications may be shown. Copies of
certicates may be downloaded from the BEKA website.
Typical certication information label
2. INSTALLATION
The BA374E Timer or Clock has has a robust IP66 GRP
enclosure with a separate terminal compartment incorporating
an armoured glass window & stainless steel ttings. It is
suitable for exterior surface mounting in most industrial
environments, or pipe mounting using an accessory kit.
If the enclosure is not bolted to an earthed post or structure,
the earth terminal should be connected to local earthed
metalwork or to the plant’s potential equalising conductor.
B
D
DB
D
D
Step C and D
Remove the temporary
hole plug and install an
appropriate IP rated cable
gland or conduit fitting and
terminate field wiring.
Finally replace the terminal
cover and tighten the two
'A' screws.
Step B
Secure the instrument
to a flat surface with M6
screws through the
two 'B' holes.
Alternatively use a pipe
mounting kit.
Step A
Remove the terminal
cover by unscrewing
the two 'A' screws
B
D
DB
D
D
DISPLAY
DISPLAY
C
A
C
A
DISPLAY
PE
Fig 1 BA374E installation procedure
91
117
72
Two M6 clearance
holes for surface
mounting
M20 x 1.5 tapped. Supplied
with two IP66 stopping plugs
& one temporary hole plug.
1 2
RS1
RS2
P1S2S1EP2
3 4 5 6
A3 A4A1 A2
+
Control
output 1
Control
output 2
+
Status
output
+
ResetPower
supply
+
Add link
to energise
pulse input A
Pulse
input A
+
7 8 9 10
Add link
to energise
pulse input b
Pulse
input b
+
Terminals S1 & S2
internally linked for
joining cable screens
141
212
Separate
terminal
compartment
DISPLAY
PE
Terminals
not used
Fig 2 Dimensions and terminal connections
EMC
For specied immunity all wiring should be in screened twisted
pairs with screens earthed at one point within the safe area.
DISPLAY
Safe area
Power
supply
Single channel
positive polarity
28V: 93mA
Zener barrier
Single channel
positive polarity
28V: 93mA
Zener barrier
Remote reset
in hazardous
area
Input b
Sensor
b
Input A
Remote reset
in safe area
6 5
+
4 3 10 9 8 7
RS2
RS1
2 1
+
+
Hazardous area
Sensor
A
+
Sensor output Input A Input b
Proximity detector
Switch Contact
Open collector
Link
3 & 4
Link
7 & 8
Voltage pulse
Magnetic pick-off
Don’t link
3 & 4
Don’t link
7 & 8
PE
Fig 3 Typical Timer system
Units of measurement and tag number
The BA374E is tted with a blank escutcheon around the
liquid crystal display. This can be supplied printed with any
units of measurement and tag information specied at the
time of ordering. Alternatively, the information may be added
on-site via an embossed strip, dry transfer or a permanent
marker.
To gain access to the escutcheon remove the terminal cover by
unscrewing the two ‘Ascrews which will reveal two concealed
‘D’ screws. Remove the push buttons by unscrewing the
two ‘C’ screws and un-plug the ve way connector. Finally,
unscrew all four ‘D’ screws and carefully lift o the front of the
instrument. The location of all the screws is shown in Fig 1.
3. OPERATION
The BA374E is controlled and congured via four front panel
push buttons. When congured as a Timer the push button
functions are:
& When local control is enabled starts the Timer
* When local control is enabled stops the Timer
) + * Shows the grand total (run time) in hours and tenths
of an hour irrespective of Timer conguration. If
buttons are held for longer than ten seconds the
grand total may be reset to zero if the grand total
reset sub-function Glr gtot is enabled in the
LoC r5Et conguration function.
To reset the grand total to zero from the display
mode press the ) + * buttons for ten seconds
until CLr. no is displayed. Using the & or *
button change the display to CLr. YE5 and press ).
& + * Resets the Timer to zero or to the set time 5Et t
depending on whether the Timer is congured to
time-up or time-down when the two buttons are
operated simultaneously for more than three
seconds. This is a congurable function.
( + & When enabled in the conguration menu, operating
these two buttons simultaneously provides direct
access from the display mode to the set time 5Et t
and, if the repeat timing cycle is enabled, to the
restart delay r5t dela.
( + & Shows in succession, rmware version number,
instrument function
elap5e
or
cloc
and output
accessories which are always tted.
-A Control outputs
-P Pulse output
See full instruction manual for description of use when
congured as a Clock.
Abbreviated Instruction for
BA374E intrinsically safe
two input eld mounting Timer or Clock
Issue 2
24th November 2022
BEKA associates Ltd. Old Charlton Rd, Hitchin, Hertfordshire,
SG5 2DA, UK Tel: +44(0)1462 438301 e-mail: [email protected]
web: www.beka.co.uk
E
P
Fig 4 Configuration menu
Manuals and datasheets
can be downloaded from
http://www.beka.co.uk/ba374e
Unless otherwise specified menu functions are shown on the upper display
4. CONFIGURATION
BA374E Timer or Clocks are supplied configured as requested at time of ordering. If not specified default Timer configuration will be supplied but can easily be changed on-site. Fig 4
shows the location of each function within the Timer configuration menu with a brief summary of the function. Please refer to the full instruction manual for detailed configuration information.
Access to the configuration menu is obtained by pressing the ( and ) buttons simultaneously. If the Timer or Clock's security code is set to default 0000 the first parameter function will
be displayed. If the instrument is protected by a security code, code will be displayed. The four digit code must be entered to gain access to the menu.
Display
mode
Security Code
Enter code by
pressing
* or & & (
to move to next
digit. Code 0000
allows direct
access to
the menu
Function
* or &
to select
Function of
instrument
elap5e
Timer interval
measurement
cloc
Clock time
display
Confirm selection
by entering 5ure
by pressing
* or &
and (
to move to
next digit
&&
*
(
(
)
)
(
(
))
elap5e
( )
function
code
0000
0000
*
(
)
)
) ) ) ) ) )
( )
input-a
op
.
col
Debounce
input-A
* or &
to select
level of
debounce.
default
heavy
light
&
)
debounce
( )
default
( )
( )
op
.
col
&
*
(
)
( )
off
enbl
Start & stop
timer
* or &
to select how
timer is
controlled
local
Start
& button
Stop
* button
control 1
Start
a high (open)
Stop
b high (open)
control 2
Start
a low (closed)
Stop
b low (closed)
control 3
Start
a high (open)
Stop
b low (closed)
control 4
Start
a low (closed)
Stop
b high (open)
&
*
( )
local
5tar5top
Units of
display
* or &
to select
12
:
00
:
00
12:00
30
:
00
30
hours
minutes
seconds
&
*
( )
12
:
00
:
00
unit5
Set time
* or &
to adjust
value and
(
to move
control to
next digit.
Enable
cycle function
* or &
to toggle
between
on and off
( )
00
:
00
:
00
5et t
Clear grand total
* or &
to select ye5
to reset grand
total to zero.
Confirm
instruction by
entering 5ure.
Press
& or *
to adjust each
digit and (
to move to
next digit
&
*
(
)
)
clr.
no
(
clr gtot
0000
&
*
(
)
)
Power fail
* or &
to select how
timer functions
when power is
restored after
failure
idle
Stopped,
requires reset
& start input.
pau5e
Paused,
requires start
input.
continue
Resumes
timing.
&
*
(
)
)
idle
Direction of
count
* or &
to select
up or dn
&
*
(
)
)
( )
up or dn
0000
Enable
access to
Set Time from
display mode
* or &
to select
on or off
(
)
)
ac5et t
enbl
*
Debounce
input-b
* or &
to select
level of
debounce.
default
heavy
light
&
)
debounce
( )
default
Lower Display
cycle5 not
enabled
* or &
to select display
5td
Set time 5et t
off
lower display
disabled.
___________
cycle5
enabled
* or &
to select display
5td
Count No. &
total counts
with status
shown at start
of each
operation.
label
Count No. &
total counts
with status
shown
periodically.
off
lower display
disabled.
( )
di5p-2
5td
*
Security code
for direct
access to
Set Time
Enter code by
pressing
* or &
and (
to move to
next digit
Code 0000
allows direct
access.
)
( )
input-b
inp
.
type inp
.
type
Input-A
* or &
to select
Input type
op
.
col
Open
Collector.
volt5 l
Pulse
<1V >3V
volt5 h
Pulse
<3V >10V
coil
Magnetic
pick-off.
pr
.
det
Proximity
detector.
contact
Switch
contact.
Input-b
* or &
to select
Input type
op
.
col
Open
Collector.
volt5 l
Pulse
<1V >3V
volt5 h
Pulse
<3V >10V
coil
Magnetic
pick-off.
pr
.
det
Proximity
detector.
contact
Switch
contact.
)
( )
( )
*
Local grand
total clear
* or &
to turn the
local grand total
reset function
on or off
When on is
selected
pressing
) and *
simultaneously
for more than 10
seconds in the
display mode
resets the
grand total.
&
)
clr gtot
( )
loc r5et
r5et.enbl
Local total
reset
* or &
to turn the
local total
reset function
on or off
When on is
selected
pressing
* and &
simultaneously
for more than 3
seconds in the
display mode
resets the
total display.
&
*cycle5
&&
*cycl cnt
( )
01
Cycle count
* or &
to adjust
flashing digit
and (
to move
to next digit.
Sets number
of cycles to be
performed.
Timer repeat cycle function
&
*r5t dela
( )
00
:
00
:
00
Restart delay
* or &
to adjust
flashing digit
and (
to move
to next digit.
Sets delay
between cycles
in the same units
as 5cale t
*
) )
)
&
*
(
)
( )
off
enbl
Enable
output 1
* or &
to toggle
between
on and off
&&
*
( )
&
*op1 dela
( )
Output on delay
* or &
to adjust
flashing digit
and (
to move
to next digit
Set delay in
seconds before
output 1
is energised.
*
)
op1 on
( )
Output on at
* or &
to select
required function
run
pau5e
delay
done
n re5et
n run
n pau5e
n delay
n done
re5et
Select action
that energises
output 1.
&
*
))
accd
0000
dn
Define
Security Code
Enter by
pressing
& or * &
( to move
to next digit.
&
*
(
)
)
Reset
configuration to
Timer factory
defaults
Confirm
instruction by
entering 5ure.
Press
& or *
to adjust each
digit and (
to move to
next digit
*
(
)
)
r5et def
on off
op1
op1 off
Output off at
* or &
to select
required function
n run
n pau5e
n delay
n done
re5et
run
pau5e
delay
done
n re5et
Select action
that de-energises
output 1.
Control Output 1 configuration
00000
)
&
*
(
)
( )
off
enbl
Enable
Stat oP
* or &
to toggle
between
on and off
&&
*
( )
&
*5tat
.
dela
( )
Status output
on delay
* or &
to adjust
flashing digit
and (
to move
to next digit.
*
)
5tat on
( )
Status output
on at
* or &
to select
required state
run
pau5e
delay
done
n re5et
n run
n pau5e
n delay
n done
re5et
Select action
that energises
output.
&
*
))
5tat
off
Status output
off at
* or &
to select
required state
n run
n pau5e
n delay
n done
re5et
run
pau5e
delay
done
n re5et
Select action
that energises
output.
00000
op2
As op1
)
0000
code
0000
&
*
&
*
&
*
&
*
&
*
&
External
reset
* or &
to toggle
between
5td
1s
fa5t
?ms
external
contact reset
time.
&
*
(
)
)
e r5et
5td
p-fail 5tat op
run n run
run n run
DISPLAY
PE
The BA374E is CE marked to show compliance with the European Explosive Atmospheres Directive 2014/34/EU
and the European EMC Directive 2014/30/EU.
It is also UKCA marked to show compliance with UK statutory requirements Equipment and Protective Systems
Intended for Use in Potentially Explosive Atmospheres Regulations
UKSI 2016:1107 (as amended) and with the Electromagnetic Compatibility Regulations
UKSI 2016:1091 (as amended).
Fig 4 Conguration menu
  • Page 1 1
  • Page 2 2

BEKA BA374E User manual

Type
User manual

BEKA BA374E is an intrinsically safe two-input field mounting Timer or Clock, suitable for exterior surface mounting in industrial environments. It can measure and display elapsed time between external events, or control external events via two control outputs. When configured as a Clock, it displays local time and can turn on and off twice in each 24-hour period. It has a separate terminal compartment for easy access and can be configured via four front panel push buttons.