BEKA BA334E is a field-mounting intrinsically safe one-input Rate Totalizer designed for use in potentially explosive atmospheres. With a robust GRP enclosure and separate terminal compartment, it's ideal for exterior surface or pipe mounting in various industrial environments. BA334E excels in rate and total flow measurement, displaying both values in the same or different engineering units. It features four front-panel push buttons for easy control and configuration, allowing users to modify settings like total scale factor, rate scale factor, and various reset options.

BEKA BA334E is a field-mounting intrinsically safe one-input Rate Totalizer designed for use in potentially explosive atmospheres. With a robust GRP enclosure and separate terminal compartment, it's ideal for exterior surface or pipe mounting in various industrial environments. BA334E excels in rate and total flow measurement, displaying both values in the same or different engineering units. It features four front-panel push buttons for easy control and configuration, allowing users to modify settings like total scale factor, rate scale factor, and various reset options.

1. DESCRIPTION
The BA334E is a eld mounting intrinsically safe, one input
Rate Totaliser with a separate terminal compartment which
will function with a wide variety of sensors. The instrument
can display rate of ow and total ow in the same or dierent
engineering units.
This abbreviated instruction sheet is intended to assist with
installation, a comprehensive instruction manual describing
safety certication, system design and conguration may be
downloaded from the BEKA website or may be requested
from the BEKA sales oce.
The BA334E Rate Totaliser has IECEx, ATEX and UKEX
intrinsic safety certication for use in ammable gas
atmospheres, plus ETL and cETL gas and dust certication.
The certication information label, which is located on the top
of the instrument assembly, shows the certication numbers
and codes. Other certications may be shown. Copies of
certicates may be downloaded from the BEKA website.
Typical certication information label
2. INSTALLATION
The BA334E Rate Totaliser has a robust IP66 GRP enclosure
with a separate terminal compartment incorporating an
armoured glass window & stainless steel ttings. It is suitable
for exterior surface mounting in most industrial environments,
or pipe mounting using an accessory kit.
If the enclosure is not bolted to an earthed post or structure,
the earth terminal should be connected to local earthed
metalwork or to the plant’s potential equalising conductor.
B
D
DB
D
D
Step C and D
Remove the temporary
hole plug and install an
appropriate IP rated cable
gland or conduit fitting and
terminate field wiring.
Finally replace the terminal
cover and tighten the two
'A' screws.
Step B
Secure the instrument
to a flat surface with M6
screws through the
two 'B' holes.
Alternatively use a pipe
mounting kit.
Step A
Remove the terminal
cover by unscrewing
the two 'A' screws
B
D
DB
D
D
DISPLAY
DISPLAY
C
A
C
A
DISPLAY
PE
Fig 1 BA334E installation procedure
91
117
72
Two M6 clearance
holes for surface
mounting
M20 x 1.5 tapped. Supplied
with two IP66 stopping plugs
& one temporary hole plug.
1 2
RS1
RS2
3 4 5 6
ResetPower
supply
+
Add link
to energise
pulse input
Input
+
C1 C2 C3 C4 A3 A4A1 A2
+
Alarm 1 Alarm 2
Terminals for
dual alarms
+
+
Terminals for
4/20mA output
P1S2S1EP2
Pulse
output
+
Terminals S1 & S2
internally linked for
joining cable screens
141
212
Separate
terminal
compartment
DISPLAY
PE
Fig 2 Dimensions and terminal connections
EMC
For specied immunity all wiring should be in screened twisted
pairs with screens earthed at one point within the safe area.
DISPLAY
Single channel positive polarity
28V: 93mA Zener Barrier
Remote reset
in safe area
++
+
Voltage pulse
Magnetic pick-off
Proximity detector
Switch contact/
open collector
OR
N
S
Power
supply
External
reset
Single channel positive polarity
28V: 93mA Zener Barrier
6 5
No
link
4 3
+
++
2 16 5 4 3
RS2
RS1
Safe areaHazardous area
PE
Fig 3 Typical measurement loop
Units of measurement and tag number
The BA334E is tted with a blank escutcheon around the
liquid crystal display. This can be supplied printed with any
units of measurement and tag information specied at the
time of ordering. Alternatively, the information may be added
on-site via an embossed strip, dry transfer or a permanent
marker.
To gain access to the escutcheon remove the terminal cover by
unscrewing the two ‘Ascrews which will reveal two concealed
‘D’ screws. Remove the push buttons by unscrewing the
two ‘C’ screws and un-plug the ve way connector. Finally,
unscrew all four ‘D’ screws and carefully lift o the front of the
instrument. The location of all the screws is shown in Fig 1.
3. OPERATION
The BA334E is controlled and congured via four front panel
push buttons. In the display mode i.e. when the instrument
is displaying ow the push button functions are:
) + & Grand total - shows Lo followed by least signicant
8 digits of the 16 digit grand total.
) + * Grand total - shows Hi followed by the most
signicant 8 digits of the 16 digit grand total.
If Local Grand Total Reset CLr Gtot in the
instrument conguration menu has been activated,
operating the ) and * buttons for ten seconds
will result in Clr. no being displayed with the
no ashing. Operating the & or * button will
change the display to CLr . YE5, the ) button
will then reset the grand total to zero which will be
conrmed by a brief display of Gt Clrd.
& + * If Local Total Reset CLr tot in the instrument
conguration menu has been activated, operating
the & and * buttons for three seconds will
reset the total display to zero and clear any pulses
stored in the pulse output. The Grand Total is not
reset.
( + & Shows in succession, rmware version number,
instrument function
totali5e
and output
accessories which are always tted.
-A Control outputs
-P Pulse output
-c 4/20mA output
( + * Provides direct access to the alarm setpoints when
the Rate Totaliser is tted with optional alarms and
the AC5P setpoints function has been enabled.
( + ) Access to conguration menu
Abbreviated Instruction for
BA334E intrinsically safe
eld mounting Rate Totaliser
Issue 2
24th November 2022
BEKA associates Ltd. Old Charlton Rd, Hitchin, Hertfordshire,
SG5 2DA, UK Tel: +44(0)1462 438301 e-mail: [email protected]
web: www.beka.co.uk
E
P
Fig 4 Configuration menu
Old Charlton Rd, Hitchin, Hertfordshire, SG5 2DA, UK
Tel: +44(0)1462 438301 Fax: +44(0)1462 453971
e-mail: [email protected] web: www.beka.co.uk
Manuals and datasheets
can be downloaded from
http://www.beka.co.uk/ba334e
Unless otherwise specified menu functions are shown on the upper display
4. CONFIGURATION
Rate Totalisers are supplied configured as requested at time of ordering, if not specified default configuration will be supplied but can easily be changed on-site. Fig 4 shows the location of
each function within the configuration menu with a brief summary of the function. Please refer to the full instruction manual for detailed configuration information. Access to the configuration
menu is obtained by pressing the ( and ) buttons simultaneously. If the Rate Totaliser's security code is set to default 0000 the first parameter function will be displayed. If the instrument
is protected by a security code, code will be displayed. The four digit code must be entered to gain access to the menu.
Security Code
Enter code by
pressing
& or * & (
to move to next
digit. Code 0000
allows direct
access to
the menu
Function
& or *
to select
Function of
rate totaliser
5td
Linear
lin
16 segment
lineariser
&&
*
(
(
)
)
(
(
))
function
code
0000
)
*
(
)
)
)
( )
input
op.
col
Debounce
& or *
to select
level of
debounce.
default
heavy
light
&
)
debounce
( )
default
( )
update
0
.
5
inp.
type
&
*
&
*
Display
mode
Input
& or *
to select
Input type
op.
col
Open
Collector.
volt5 l
Pulse
<1V >3V
volt5 h
Pulse
<3V >10V
coil
Magnetic
pick-off.
pr.
det
Proximity
detector.
contact
Switch
contact.
5td
Update
& or *
to select
interval
between
display
updates,
may be set to
0.5, 1, 2, 3, 4
or 5 seconds
)
( )
di5p-1
total
&
*
Upper Display
& or *
to select
whether
rate or total
is shown
on the upper
display
)
( )
di5p-2
on
&
*
Lower Display
& or *
to turn
lower display
on or off
)
( )
00000000
&
*
Decimal point
& or *
to select
position of
decimal
point and
( to toggle
between rate
and total
displays
)
( )
factor
001
.
00
&
*
K-factor
& or *
to select
value and
( to move
to next digit or
decimal point
Note: When
lin is
selected 16
values for
factor may
be entered
)
( )
5cale-t &
Total scale
factor
Divides
factor
to produce
total display
Press
& or *
to adjust
value and
( to move
to next digit or
decimal point
dp
001
.
00
&
*
Clip off
Rate display
below which
totalisation
is inhibited
Press
& or *
to adjust value
of each digit
and ( to
move to next
digit
)
( )
*
clp off
000
.
0
&
*
Filter
& or *
to adjust
value of each
digit and
( to transfer
control to
other digit
First digit:
filter magnitude
second digit:
step response
Note: While
making
adjustments
the filtered
rate display is
shown on
lower display
so stability can
be assessed
)
( )
filter
&
*
Timebase
& or *
to select
rate display
timebase
tb-01
for flow/sec
tb-60
for flow/min
tb-3600
for flow/hour
)
( )
t-ba5e
tb-01
&
Rate scale
factor
Divides
factor
to produce
rate display
Press
& or *
to adjust
value and
( to move
to next digit or
decimal point
)
( )
5cale-r
001
.
00
*
(
)
)
)
( )
loc clr &
)
clr gtot
( )
( )
clrgtot
clr tot
&
*
&
*
Local total
reset
& or *
to turn the
local total
reset function
on or off.
When on,
total display
is reset to
zero when
& and *
are operated
simultaneously
in display
mode for more
than 3 seconds
Local grand
total reset
& or *
to turn the
local grand total
reset function
on or off.
When on,
grand total
display may be
reset to
zero when
) and *
are operated
simultaneously
in display mode
for more than
10 seconds
Clear grand
total
Press
& or *
to select ye5
to reset grand
total to zero
Confirm
instruction by
entering 5ure.
Press
& or *
to adjust each
digit and (
to move to
next digit
)
( )
&
*
Alarms, pulse output and 4/20mA
output functions appear here.
)
*
Reset
configuration
to factory
defaults
Confirm
instruction by
entering 5ure.
Press
& or *
to adjust each
digit and (
to move to
next digit
24
off off
(
0000
clr.
no
Define
Security Code
Enter by
pressing
& or *
and ( to
move to next
digit
code
0000
)
(
0000
r5et def
*
DISPLAY
PE
The BA334E is CE marked to show compliance with the European Explosive Atmospheres Directive 2014/34/EU and the European EMC Directive 2014/30/EU.
It is also UKCA marked to show compliance with UK statutory requirements Equipment and Protective Systems Intended for Use in Potentially Explosive Atmospheres Regulations
UKSI 2016:1107 (as amended) and with the Electromagnetic Compatibility Regulations
UKSI 2016:1091 (as amended).
Fig 4 Conguration menu
  • Page 1 1
  • Page 2 2

BEKA BA334E User manual

Type
User manual

BEKA BA334E is a field-mounting intrinsically safe one-input Rate Totalizer designed for use in potentially explosive atmospheres. With a robust GRP enclosure and separate terminal compartment, it's ideal for exterior surface or pipe mounting in various industrial environments. BA334E excels in rate and total flow measurement, displaying both values in the same or different engineering units. It features four front-panel push buttons for easy control and configuration, allowing users to modify settings like total scale factor, rate scale factor, and various reset options.