BEKA BA367E-SS User manual

Type
User manual

BEKA BA367E-SS, your newly purchased rugged one-input intrinsically safe counter, offers reliable counting in hazardous environments. With IECEx, ATEX, and UKEX certifications, it's suitable for use in flammable gas and dust atmospheres. ETL and cETL approvals allow installation in the USA and Canada. Its stainless steel enclosure ensures durability, while the captive gasket guarantees an IP66 seal.

BEKA BA367E-SS, your newly purchased rugged one-input intrinsically safe counter, offers reliable counting in hazardous environments. With IECEx, ATEX, and UKEX certifications, it's suitable for use in flammable gas and dust atmospheres. ETL and cETL approvals allow installation in the USA and Canada. Its stainless steel enclosure ensures durability, while the captive gasket guarantees an IP66 seal.

1. DESCRIPTION
The BA367E-SS is an intrinsically safe, one input Counter housed
in a rugged 316 stainless steel panel mounting enclosure which
can operate with a wide range of sensors.
This abbreviated instruction sheet is intended to assist with
installation, a comprehensive instruction manual describing safety
certication, system design and conguration may be downloaded
from the BEKA website or may be requested from the BEKA sales
oce.
The BA367E-SS has IECEx, ATEX and UKEX intrinsic safety
certication for use in ammable gas and dust atmospheres. ETL
and cETL approval permits installation in the USA and Canada.
The certication information label, which is located on the top
of the instrument enclosure, shows the certication number and
codes. Other certications may be shown. Copies of certicates
may be downloaded from the BEKA website.
Typical certication information label
Special conditions for safe use
The IECEx, ATEX and UKEX intrinsic safety certicate numbers
have an ‘X’ sux indicating that for some applications special
conditions apply for safe use.
a. When installed in an Ex e, Ex p or Ex t panel enclosure all
connections to the BA367E-SS must be made by appropriately
rated Zener barriers or galvanic isolators.
This means that when installed in an Ex e, Ex p or Ex t panel
enclosure the BA367E-SS remains an intrinsically safe instrument.
b. The front of the stainless steel enclosure complies with the
requirements for Ex e, Ex p & Ex t type of protection.
Therefore when correctly installed the BA367E-SS Counter will not
invalidate the Ex e, Ex p or Ex t panel enclosure certication.
Use in combustible dust atmospheres
See full instruction manual for installation information
requirements and special conditions for safe use in combustible
dust atmospheres.
2. INSTALLATION
Cut-out dimensions
Mandatory to achieve an IP66 seal between instrument and
panel and to maintain certication of panel enclosure in which it
is mounted.
105
8013
60
DISPLAY
Captive gasket
Maximum
panel thickness
8 mm
+
A1 A2 A3 A4 P1 P2
+
Alarm 1 Alarm 2
Terminals for
optional dual alarms
Terminals for
optional pulse
output
Terminals
for optional
4/20mA output
+
C1 C2 C3 C4
OR OR
Reset Add link
to energise
pulse
input
Pulse
input
Power
supply
10 to 28V dc
RS1 RS2
3 4
+
5 6
1 2
+
Connect M4 earth
stud to panel
enclosure in which
instrument is mounted
E
+
Panel cut-out 90 +0.5 / -0.0 x 43.5 +0.5 / -0.0
Typical
terminals shown
Support panel wiring to prevent vibration damage
Fig 1 Cut-out dimensions and terminals
Fig 2 Installation procedure
EMC
For specied immunity all wiring should be in screened twisted
pairs with screens earthed at one point within the safe area.
Single channel positive polarity
28V: 93mA Zener Barrier
Single channel positive polarity
28V: 93mA Zener Barrier
Remote reset
in safe area
2 16 5
++
4 3
+
RS2
RS1
Voltage pulse
Magnetic pick-off
Proximity detector
Switch contact/
open collector
OR
N
S
Power
supply
External
reset
6 5
No
link
4 3
Safe areaHazardous area
+
DISPLAY
Fig 3 Use with Zener barriers
Scale card
The Counters units of measurement are shown on a printed scale
card visible through a window at the right hand side of the display.
The scale card is mounted on a exible strip that is inserted into a
slot at the rear of the instrument as shown below
I
n
s
e
r
t
Unlock
Lock
Fig 4 Inserting exible strip carrying scale
card into slot at the rear of Counter.
Thus the scale card can easily be changed without removing the
Counter from the panel or opening the instrument enclosure.
New Counters are supplied with a printed scale card showing the
requested units of measurement, if this information is not supplied
when the Counter is ordered a blank card will be tted.
A pack of self-adhesive scale cards printed with common units of
measurement is available as an accessory from BEKA associates.
Custom printed scale cards can also be supplied.
To change a scale card, unclip the protruding end of the exible
strip by gently pushing it upwards and pulling it out of the enclosure.
Peel the existing scale card from the exible strip and replace it with
a new printed card, which should be aligned as shown below. Do
not t a new scale card on top of an existing card.
Align the self-adhesive printed scale
card onto the exible strip and insert
the strip into the Counter as shown.
Fig 5 Fitting scale card to exible strip
3. OPERATION
The Counter is controlled by four front panel push buttons. When
in the operating mode they have the following functions:
( + ) Access to conguration menu.
& + * If Local Total Reset CLr
tot in the instrument
conguration menu has been activated, operating the
& and * buttons simultaneously for three seconds
will reset the total display to zero and clear any pulses
stored in the optional pulse output.
) + & Grand total - shows Lo followed by least signicant 8
digits of the 16 digit grand total.
) + * Grand total - shows Hi followed by the most signicant
8 digits of the 16 digit grand total.
If Local Grand Total Reset Clr Gtot in the instrument
conguration menu has been activated, operating the
) and * buttons simultaneously for ten seconds will
result in Clr
.
no being displayed with the no ashing.
Operating the * or & button will change the display
to Clr . YE5, the ) button will then reset the grand
total to zero which will be conrmed by a brief display
of Gt Clrd.
( + & Shows in succession, rmware version number,
instrument function counter and any output
accessories that are tted:
- A Dual Alarm Outputs
- P Pulse output
- C 4/20mA output.
( + * When optional alarms are tted provides direct access
to the alarm setpoints if A5CP (access setpoints) has
been enabled in the conguration menu.
Align on
these
edges
Scale
card
Abbreviated instructions for
BA367E-SS Rugged one input
intrinsically safe Counter
Issue 4
24th November 2022
BEKA associates Ltd. Old Charlton Rd, Hitchin, Hertfordshire,
SG5 2DA, UK Tel: +44(0)1462 438301 e-mail: [email protected]
web: www.beka.co.uk
BA367E-SS
Slide a panel clamp into the
two grooves at each corner
of the instrument
Secure each clamp
with a stainless steel washer and wing nut,
tighten 22cNm (1.95lbf in) min. Finally fit protective caps.
Optional
stainless steel
support plate
Captive gasket
Panel
enclosure
4. CONFIGURATION
Counters are supplied configured as requested at time of ordering, if not specified default configuration will be supplied but can easily be changed on-site.
Fig 6 shows the location of each function within the configuration menu with a brief summary of the function. Please refer to the full instruction manual for detailed configuration information and optional outputs.
Access to the configuration menu is obtained by pressing the ( and ) buttons simultaneously. If the Counter's security code is set to default 0000 the first parameter input will be displayed. If the instrument is protected by a security code, code will be
displayed. The four digit code must be entered to gain access to the menu.
Fig 6 Configuration menu
Manuals, certificates and data-
sheets can be downloaded from
http://www.beka.co.uk/ba367e-ss
Unless otherwise specified menu functions are shown on the upper display
Display
mode
Input
& or *
to select
Input type
op
.
col
Open
Collector.
volt5 l
Pulse
<1V >3V
volt5 h
Pulse
<3V >10V
coil
Magnetic
pick-off.
pr.
det
Proximity
detector.
contact
Switch
contact.
&
(
)(
(
))
code
0000
*
( )
) ) ) )
( )
input
op
.
col
Debounce
& or *
to select
level of
debounce.
default
heavy
light
&
)
debounce
( )
default
( )
Upper Display
& or *
to select
display
whether
total
or
rate
is shown
on upper
display
Optional pulse output, alarms
or 4/20mA output appear here
Lower Display
& or *
to turn
lower display
on or off
&
*
( )
total
&
*
( )
Decimal point
& or *
to select
position of
decimal
point and
( to toggle
between rate
and total
displays.
( )
00000000
*
&
update
inp
.
type
Update
& or *
to select
interval
between
display
updates,
may be set to
0
.
5, 1, 2, 3, 4
or 5 seconds.
&
*
Define
Security Code
Enter by
pressing
& or *
and (
to move to
next digit.
Default code
0000 allows
direct access
to configuration
menu
&
*
(
)
)
0000
code
&
*
(
)
)
cntedg
Counting edge
& or *
to toggle
between
edge1
volts rising edge
and
edge2
volts falling edge
Local total
reset
& or *
to turn the
local total
reset function
on or off.
When on is
selected, Total
may be
reset when
& and *
are pressed
simultaneously
for more than 3
seconds in the
display mode.
(
)
)
( )
Loc clr
off
*
Local grand
total reset
& or *
to turn the
local grand
total reset
function
on or off.
When on,
grand total
display may
be reset when
) and *
are pressed
simultaneously
for more than 10
seconds in the
display mode.
&
)
( )
&
*
**
&
0
.
5
di5p-1 di5p-2
on
dP
)
Total scale
factor
Dividing factor
which defines
total display.
& or *
to adjust value
and ( to
move to
next digit or
decimal point.
( )
001
.
00
*
5cale
.
t
)
Rate scale
factor
Dividing factor
which defines
rate display.
& or *
to adjust value
and ( to
move to
next digit or
decimal point.
( )
001
.
00
)
Grand total
reset
Press
& or *
to select
clr
.
ye5
to reset grand
total to zero
Confirm
instruction by
entering 5ure.
Press
& or *
to adjust each
digit and (
to move to
next digit
( )
& &
)
Filter input
& or *
to adjust value
of each digit
and ( to
transfer
control to
the next digit.
First digit:
filter magnitude
Second digit:
step response
Note:
While making
adjustments
the filtered
rate display is
shown on
lower display
so stability can
be assessed
( )
*
filter &
)
Timebase
& or *
to select
rate display
timebase.
tb-01
for pulses/sec
tb-60
for pulses/min
tb-3600
for pulses/hour
( )
tb-01
*
&
*
&t-ba5e
24
)
Direction of
count
& or *
to toggle
between
up and dn
( )
*
&
clr tot clr gtot
off
*
clr gtot &
*
Reset value
& or *
to adjust value
of each digit
and ( to
transfer
control to
the next digit.
(
)
)
clr val
(
0000
)
Reset
configuration
to factory
defaults
Confirm
instruction by
entering 5ure.
Press
& or *
to adjust each
digit and (
to move to
next digit
(
)
)
r5et def
0000
edge1
5cale
.
rup or dn
up 0000000 clr
.
no
Security Code
Enter code by
pressing
& or * & (
to move to next
digit. Code 0000
allows direct
access to
the menu
DISPLAY
The BA367E-SS is CE marked to show compliance with the European Explosive Atmospheres Directive 2014/34/EU and the European EMC Directive 2014/30/EU.
It is also UKCA marked to show compliance with UK statutory requirements Equipment and Protective Systems Intended for Use in Potentially Explosive Atmospheres Regulations
UKSI 2016:1107 (as amended) and with the Electromagnetic Compatibility Regulations
UKSI 2016:1091 (as amended).
Fig 6 Conguration menu
  • Page 1 1
  • Page 2 2

BEKA BA367E-SS User manual

Type
User manual

BEKA BA367E-SS, your newly purchased rugged one-input intrinsically safe counter, offers reliable counting in hazardous environments. With IECEx, ATEX, and UKEX certifications, it's suitable for use in flammable gas and dust atmospheres. ETL and cETL approvals allow installation in the USA and Canada. Its stainless steel enclosure ensures durability, while the captive gasket guarantees an IP66 seal.