BEKA BA364E User manual

Type
User manual

BEKA BA364E intrinsically safe two-input field-mounting counter offers versatile counting solutions in potentially explosive atmospheres. Its robust IP66 GRP enclosure and separate terminal compartment with armored glass window ensure durability. Easily mount it on a flat surface or pipe using the included accessories. The BA364E provides rate and total display of two inputs, their sum, or difference. It features configurable parameters like input type, counting edge, display updates, and decimal point position.

BEKA BA364E intrinsically safe two-input field-mounting counter offers versatile counting solutions in potentially explosive atmospheres. Its robust IP66 GRP enclosure and separate terminal compartment with armored glass window ensure durability. Easily mount it on a flat surface or pipe using the included accessories. The BA364E provides rate and total display of two inputs, their sum, or difference. It features configurable parameters like input type, counting edge, display updates, and decimal point position.

1. DESCRIPTION
The BA364E is a eld mounting intrinsically safe, two input
Counter with a separate terminal compartment which will
function with a wide variety of sensors. The instrument
can display rate and total of the two inputs and their sum or
dierence.
This abbreviated instruction sheet is intended to assist with
installation, a comprehensive instruction manual describing
safety certication, system design and conguration may be
downloaded from the BEKA website or may be requested
from the BEKA sales oce.
The BA364E Counter has IECEx, ATEX and UKEX intrinsic
safety certication for use in ammable gas atmospheres,
plus ETL and cETL gas and dust certication. The certication
information label, which is located on the top of the instrument
assembly, shows the certication numbers and codes. Other
certications may be shown. Copies of certicates may be
downloaded from the BEKA website.
Typical certication information label
2. INSTALLATION
The BA364E Counter has a robust IP66 GRP enclosure with
a separate terminal compartment incorporating an armoured
glass window & stainless steel ttings. It is suitable for
exterior surface mounting in most industrial environments, or
pipe mounting using an accessory kit.
If the enclosure is not bolted to an earthed post or structure,
the earth terminal should be connected to local earthed
metalwork or to the plant’s potential equalising conductor.
B
D
DB
D
D
Step C and D
Remove the temporary
hole plug and install an
appropriate IP rated cable
gland or conduit fitting and
terminate field wiring.
Finally replace the terminal
cover and tighten the two
'A' screws.
Step B
Secure the instrument
to a flat surface with M6
screws through the
two 'B' holes.
Alternatively use a pipe
mounting kit.
Step A
Remove the terminal
cover by unscrewing
the two 'A' screws
B
D
DB
D
D
DISPLAY
DISPLAY
C
A
C
A
DISPLAY
PE
Fig 1 BA364E installation procedure
91
117
72
Two M6 clearance
holes for surface
mounting
M20 x 1.5 tapped. Supplied
with two IP66 stopping plugs
& one temporary hole plug.
1 2
RS1
RS2
3 4 5 6
C1 C2 C3 C4 A3 A4A1 A2
+
Alarm 1 Alarm 2
Terminals for
dual alarms
+
+
Terminals for
4/20mA output
ResetPower
supply
+
Add link
to energise
pulse input A
Pulse
input A
+
7 8 9 10
Add link
to energise
pulse input b
Pulse
input b
+
P1S2S1EP2
Pulse
output
Terminals S1 & S2
internally linked for
joining cable screens
+
141
212
Separate
terminal
compartment
DISPLAY
PE
Fig 2 Dimensions and terminal connections
EMC
For specied immunity all wiring should be in screened twisted
pairs with screens earthed at one point within the safe area.
DISPLAY
PE
Safe area
Power
supply
Single channel
positive polarity
28V: 93mA
Zener barrier
Single channel
positive polarity
28V: 93mA
Zener barrier
Remote reset
in hazardous
area
Input b
Sensor
b
Input A
Remote reset
in safe area
6 5
+
4 3 10 9 8 7
RS2
RS1
2 1
+
+
Hazardous area
Sensor
A
+
Sensor output Input A Input b
Proximity detector
Switch contact
Open collector
Link
3 & 4
Link
7 & 8
Voltage pulse
Magnetic pick-off
Don’t link
3 & 4
Don’t link
7 & 8
Fig 3 Typical measurement loop
Units of measurement and tag number
The BA364E is tted with a blank escutcheon around the
liquid crystal display. This can be supplied printed with any
units of measurement and tag information specied at the
time of ordering. Alternatively, the information may be added
on-site via an embossed strip, dry transfer or a permanent
marker.
To gain access to the escutcheon remove the terminal cover by
unscrewing the two ‘Ascrews which will reveal two concealed
‘D’ screws. Remove the push buttons by unscrewing the
two ‘C’ screws and un-plug the ve way connector. Finally,
unscrew all four ‘D’ screws and carefully lift o the front of the
instrument. The location of all the screws is shown in Fig 1.
3. OPERATION
The BA364E is controlled and congured via four front panel
push buttons. In the display mode i.e. when the instrument
is counting the push button functions are:
) + & Grand total - shows the least signicant 8 digits of
a 16 digit counter.
) + * Grand total - shows the most signicant 8 digits of
a 16 digit counter. If buttons are pressed for longer
than 10 seconds the grand total will be reset to zero
if the grand total reset function clr gtot is enabled.
To reset the grand total to zero from the operating
mode press the ) and * buttons for ten seconds
until CLr. no is displayed. Using the & or * button
change the display to Clr . YE5 and press ) which will
reset the grand total and restore the original display.
& + * If the local total reset function clr tot is enabled in
the conguration menu, simultaneously pressing
the & and * buttons for more than three seconds
allows total A, total b or both totals to be selected
by operating the & or * button. Operating the
) button will then reset the selected total and
clear any stored output pulses.
( + & Shows in succession, rmware version number,
instrument function
2chcntr
and output
accessories which are always tted.
-A Control outputs
-P Pulse output
-c 4/20mA output
( + * Provides direct access to the alarm setpoints when
the AC5P setpoints function has been enabled.
( + ) Access to conguration menu
Abbreviated Instruction for
BA364E intrinsically safe two input
eld mounting Counter
Issue 3
24th November 2022
BEKA associates Ltd. Old Charlton Rd, Hitchin, Hertfordshire,
SG5 2DA, UK Tel: +44(0)1462 438301 e-mail: [email protected]
web: www.beka.co.uk
E
P
* Followed by identical function for input b
Unless otherwise specified menu functions are shown on the upper display
Fig 4 Configuration menu
Manuals and datasheets
can be downloaded from
http://www.beka.co.uk/ba364e
Unless otherwise specified menu functions are shown on the upper display
4. CONFIGURATION
Counters are supplied configured as requested at time of ordering, if not specified default configuration will be supplied but can easily be changed on-site. Fig 4 shows the location of each
function within the configuration menu with a brief summary of the function. Please refer to the full instruction manual for detailed configuration information. Access to the configuration menu
is obtained by pressing the ( and ) buttons simultaneously. If the Counter's security code is set to default 0000 the first parameter input-a will be displayed. If the instrument is protected
by a security code, code will be displayed. The four digit code must be entered to gain access to the menu.
Display
mode
Security Code
Enter code by
pressing
* or & & (
to move to next
digit. Code 0000
allows direct
access to
the menu
Input-A
& or *
to select
Input type
op
.
col
Open
Collector
volt5 l
Pulse
<1V >3V
volt5 h
Pulse
<3V >10V
coil
Magnetic
pick-off
pr.
det
Proximity
detector
contact
Switch
contact
&
(
)(
(
))
code
0000
*
( )
) ) ) ) )
( )
input-a
op
.
col
Debounce
& or *
to select
level of
debounce.
default
heavy
light
&
)
debounce
( )
default
( )
Upper Display
& or *
to select
display
whether
total
or
rate
is shown
on upper
display
Alarms, pulse output and 4/20mA
output functions appear here.
Lower Display
& or *
to turn
lower display
on or off
&
*
( )
total
&
*
( )
Decimal point
& or *
to select
position of
decimal
point and
( to toggle
between rate
and total
displays
( )
00000000
*
&
Count
& or *
to select
Input type
a
:
b
Input A +
Input b
a
:-b
Input A -
Input b
a con b
A count
direction
controlled
by b
a rel b
Quadrature
counting
mode
( )
count
a
:
b
update
inp
.
type
Update
& or *
to select
interval
between
display
updates,
may be set to
0
.
5, 1, 2, 3, 4
or 5 seconds
&
*
&
*
Define
Security Code
Enter by
pressing
& or *
and (
to move to
next digit.
Default code
0000 allows
direct access
to configuration
menu
&
*
(
)
)
0000
code
&
*
(
)
)
cntedg-a
Counting edge
input-A
& or *
to toggle
between
edge1
volts rising edge
and
edge2
volts falling edge
Local total
reset
& or *
to turn the
local total
reset function
on or off.
When on, total
display may be
reset when
& and *
are pressed
simultaneously
for more than 3
seconds in the
display mode
(
)
)
( )
Loc clr
off
*
Local grand
total reset
& or *
to turn the
local grand
total reset
function
on or off.
When on,
grand total
display may
be reset when
) and *
are pressed
simultaneously
for more than 10
seconds in the
display mode
&
)
( )
&
*
**
&
0
.
5
di5p-1 di5p-2
on
dP
)
Total scale
factor
Dividing factor
which defines
total display.
& or *
to adjust value
and ( to
move to
next digit or
decimal point
( )
001
.
00
*
5cale
.
t
)
Rate scale
factor
Dividing factor
which defines
rate display.
& or *
to adjust value
and ( to
move to
next digit or
decimal point
( )
001
.
00
)
Grand total
reset
press
& or *
to select
clr
.
ye5 to
reset grand
total to zero.
Confirm
instruction by
entering 5ure.
Press
& or *
to adjust each
digit and (
to move to
next digit
( )
& &
)
Filter input
& or *
to adjust value
of each digit
and ( to
transfer
control to
the next digit.
First digit:
filter magnitude
Second digit:
step response
Note:
While making
adjustments
the filtered
rate display is
shown on
lower display
so stability can
be assessed
( )
*
filter &
)
Timebase
& or *
to select
rate display
timebase.
tb-01
for pulses/sec
tb-60
for pulses/min
tb-3600
for pulses/hour
( )
tb-01
*
&
t-ba5e
24
)
Direction of
count
& or *
to toggle
between
up and dn
( )
*
&
clr tot clr gtot
off
*
clr gtot &
*
Reset value
& or *
to adjust value
of each digit
and ( to
transfer
control to
the next digit
(
)
)
clr val
(
0000
)
Reset
configuration
to factory
defaults
Confirm
instruction by
entering 5ure.
Press
& or *
to adjust each
digit and (
to move to
next digit
(
)
)
r5et def
0000
*
edge1
*5cale
.
rup or dn
up 00000000 clr
.
no
DISPLAY
PE
*
&
Old Charlton Rd, Hitchin, Hertfordshire, SG5 2DA, UK
Tel: +44(0)1462 438301 Fax: +44(0)1462 453971
e-mail: [email protected] web: www.beka.co.uk
The BA364E is CE marked to show compliance with the European Explosive Atmospheres Directive 2014/34/EU and the European EMC Directive 2014/30/EU.
It is also UKCA marked to show compliance with UK statutory requirements Equipment and Protective Systems Intended for Use in Potentially Explosive Atmospheres Regulations
UKSI 2016:1107 (as amended) and with the Electromagnetic Compatibility Regulations
UKSI 2016:1091 (as amended).
Fig 4 Conguration menu
  • Page 1 1
  • Page 2 2

BEKA BA364E User manual

Type
User manual

BEKA BA364E intrinsically safe two-input field-mounting counter offers versatile counting solutions in potentially explosive atmospheres. Its robust IP66 GRP enclosure and separate terminal compartment with armored glass window ensure durability. Easily mount it on a flat surface or pipe using the included accessories. The BA364E provides rate and total display of two inputs, their sum, or difference. It features configurable parameters like input type, counting edge, display updates, and decimal point position.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI