CKD AX Series(TS・TH・XS) DeviceNet User manual

Type
User manual
SMF-2009-A
INSTRUCTION MANUAL
ABSODEX Driver
AX Series
TS Type
TH Type
XS Type
[DeviceNet Specification]
Read this Instruction Manual
carefully and thoroughly before
using this product.
Pay extra attention to the
instructions concerning safety.
After reading this Instruction Manual,
keep it in a safe and convenient
place.
3rd Edition
CKD Corporation
Contents
ABSODEX
DeviceNet specification] ABSODEX Driver
AX series [TS type, TH type, and XS type
Instruction Manual No. SMF-2009-A
Introduction ··························································································· 1
1. Specifications
1.1 Product Configuration ································································ 1-1
1.2 General Specifications of Driver ·················································· 1-2
1.3 Performance Specifications of Driver ············································ 1-5
2. Wiring
2.1 Panel Description ····································································· 2-1
2.2 Communication Connector ························································· 2-3
2.3 Connecting the Communication Cable ·········································· 2-4
2.4 IO Interface ············································································· 2-7
2.4.1 Wiring of emergency stop input (TB3) ······································· 2-7
3. DeviceNet Communication Function
3.1 Communication Specifications ···················································· 3-1
3.2 Remote I/O ············································································· 3-2
3.2.1 Basic format ········································································· 3-2
3.2.2 8-byte occupied (Input 8 bytes/output 8 bytes) ···························· 3-3
3.2.3 3-byte occupied (Input 3 bytes/output 3 bytes) ···························· 3-9
3.3 Data Communication Timing Chart ··············································· 3-10
3.3.1 Monitor code ········································································ 3-10
3.3.2 Command code ···································································· 3-11
3.3.3 Response code ···································································· 3-12
3.4 Defining the DeviceNet Register ·················································· 3-13
3.5 Monitoring the DeviceNet Communication State ····························· 3-15
3.6 LED Indication ········································································· 3-16
3.7 7-segment LED Indication ·························································· 3-17
4. Network Operation Mode
4.1 Point Table Operation ································································ 4-1
4.1.1 Operation method ································································· 4-1
4.1.2 Point table data ···································································· 4-2
4.1.3 Point table setting example ····················································· 4-5
4.2 Data Input Operation ································································· 4-8
4.2.1 Operation method ································································· 4-8
4.2.2 Input data ············································································ 4-9
4.2.3 Input data setting examples ···················································· 4-11
Created on 5 June, 2019
--- MEMO ---
Introduction
[SMF-2009-A]
1
Introduction
Thank you for choosing ABSODEX.
ABSODEX is a direct-drive index unit developed to drive intermittently operated turntables or the likes of
general industrial assembling machines and inspection machines flexibly and with precision.
This Instruction Manual is for DeviceNet specification TS type, TH type, and XS type ABSODEX drivers.
It is not for drivers of other types.
For the operation method, precautions on operation, maintenance and inspection items and so on, refer
to "Instruction Manual for AX Series TS, TH, XS Types" (SMF-2006) contained in the attached CD-ROM.
The descriptions, specifications, and appearances in this Instruction Manual are subject to change
without notice.
DeviceNetTM is a registered trademark of ODVA.
Company and product names in this document are registered trademarks or trademarks of their
respective owners.
Introduction
[SMF-2009-A]
2
--- MEMO ---
1. Specifications
[SMF-2009-A]
― 1-1
1. Specifications
1.1 Product Configuration
Table 1.1 Product structure
Name
Quantity
1
Driver unit
1
2
Accessories
CN5 motor power connector:
PC4/3-ST-7.62 (Phoenix Contact)
1
CN4 power supply connector:
PC4/5-ST-7.62 (Phoenix Contact)
1
CN3 communication connector (DeviceNet):
MSTB2.5/5-STF-5.08AUM (Phoenix Contact)
1
1. Specifications
[SMF-2009-A]
― 1-2
1.2 General Specifications of Drivers
Table 1.2 General specifications of TS type and TH type drivers
Item
1. Power
supply
voltage
Main
TS
TH
Control
TS
TH
2. Power supply frequency
3. Rated input current
TS
TH
4. Input phase
5. Output voltage
6. Output frequency
7. Rated output current
TS
TH
8. Output phase
9. Power system
10. Mass
TS
TH
11. Outside dimensions
TS
TH
12. Configuration
13. Operating ambient
temperature
0 to 50ºC
14. Operating ambient
humidity
20 to 90%RH (no condensation allowed)
15. Storage ambient
temperature
-20 to 65ºC
16. Storage ambient humidity
20 to 90%RH (no condensation allowed)
17. Atmosphere
No corrosive gases and no dust
18. Noise resistance
19. Vibration resistance
20. Altitude
21. Protection
1. Specifications
[SMF-2009-A]
― 1-3
*1) Only models with a maximum torque of 45 Nm or less can be used with 1-phase 100 VAC power.
For models with a maximum torque of 75 Nm or more, the torque limit area is calculated differently
when used with 1-phase 200 VAC. Please contact CKD to determine if it can be used.
*2) Supply the main power and control power from the same power source. Do not supply them from
power sources of different voltages or phases. Otherwise, it may cause a malfunction or damage.
Use 1-phase 100 to 115 VAC power for the control power. If 1-phase 200 to 230 VAC power is
connected by mistake, the internal circuits of the driver will be damaged.
1. Specifications
[SMF-2009-A]
― 1-4
Table 1.3 General specifications of XS type driver
Item
Description
Power
supply
voltage
Main
1-phase or 3-phase: 200 VAC ± 10% to 230 VAC ± 10%
(standard)
1-phase 100 VAC ± 10% to 115 VAC ± 10% (-J1 option)
Control
1-phase 200 VAC ± 10% to 230 VAC ± 10% (standard)
1-phase 100 VAC ± 10% to 115 VAC ± 10% (-J1 option)
Power supply frequency
50/60 Hz
Rated input current
1.8 A
Input phase
1-phase or 3-phase
Output voltage
0 to 230 V
Output frequency
0 to 50 Hz
Rated output current
1.9 A
Output phase
3-phase
Power system
TN, TT, IT
Mass
About 1.6 kg
Outside dimensions
W75 × H220 × D160
Configuration
Open modular type (integrated driver and controller)
Operating ambient
temperature
0 to 50ºC
Operating ambient
humidity
20 to 90%RH (no condensation allowed)
Storage ambient
temperature
-20 to 65ºC
Storage ambient
humidity
20 to 90%RH (no condensation allowed)
Atmosphere
No corrosive gases and no dust
Noise resistance
1,000 V (P-P), 1 μsec pulse width, 1 nsec rise time
Vibration proof
4.9 m/s2
Altitude
1,000 m or less
Protection
IP2X (excludes CN4 and CN5)
1. Specifications
[SMF-2009-A]
― 1-5
1.3 Performance Specifications of Drivers
Table 1.4 Performance specifications of TS type and TH type drivers
Item
Description
Number of controlled axes
1 axis; 540,672 pulses/rotation
Angle setting units
° (degree), pulse, and number of indexes
Minimum angle setting units
0.001°, 1 pulse (= about 2.4 sec [0.00067 deg.])
Speed setting units
sec, rpm
Speed setting range
0.01 to 100 sec/0.11 to 300 rpm
Number of equal segments
1 to 255
Maximum instruction value
7-digit input ±9,999,999
Timer
0.01 to 99.99 sec
Programming language
NC language
Programming method
Data is set via RS-232C port using PC
Operation modes
Automatic, single block, MDI, jog, servo OFF, pulse string
input, network operation mode
Coordinates
Absolute and incremental
Acceleration curve
<5 types>
Modified sine (MS), Modified constant velocity (MC, MC2)
Modified trapezoid (MT), Trapecloid (TR)
Status display
LED power status indicator
Motion display
7-segment LED (2 digits)
Communication interface
RS-232C compliant
DeviceNet communication
function
<Input>
Home positioning instruction, reset, start, stop, continuous
rotation stop, emergency stop, answer, position deviation
counter reset, program number selection, jog, brake
release, servo ON, program number setting, ready return
<Output>
Alarm 1 and 2, positioning completion, in-position, standby
for start input, M code 8 points, output during indexing 1
and 2, home position output, M code strobe, segment
position strobe, servo status, ready output
Program capacity
<NC program>
About 6,000 characters (256 pcs.)
<Point table>
64 points
Electronic thermal
Actuator overheat protection
1. Specifications
[SMF-2009-A]
― 1-6
Table 1.5 Product specifications of XS type driver
Item
Description
Number of controlled axes
1 axis; 4,194,304 pulses/rotation
Angle setting units
° (degree), pulse, and number of indexes
Minimum angle setting units
0.001°, 1 pulse (= about 0.31 sec [0.000086 deg.])
Speed setting units
sec, rpm
Speed setting range
0.01 to 100 sec/0.11 to 240 rpm
Number of equal segments
1 to 255
Maximum instruction value
8-digit input ±99,999,999
Timer
0.01 to 99.99 sec
Programming language
NC language
Programming method
Data is set via RS-232C port using PC
Operation modes
Automatic, single block, MDI, jog, servo OFF, pulse string
input, network operation mode
Coordinates
Absolute and incremental
Acceleration curve
<5 types>
Modified sine (MS), Modified constant velocity (MC, MC2)
Modified trapezoid (MT), Trapecloid (TR)
Status display
LED power status indicator
Motion display
7-segment LED (2 digits)
Communication interface
RS-232C compliant
DeviceNet communication
function
<Input>
Home positioning instruction, reset, start, stop, continuous
rotation stop, emergency stop, answer, position deviation
counter reset, program number selection, jog, brake
release, servo ON, program number setting, ready return
<Output>
Alarm 1 and 2, positioning completion, in-position, standby
for start input, M code 8 points, output during indexing 1
and 2, home position output, M code strobe, segment
position strobe, servo status, ready output
Program capacity
<NC program>
About 6,000 characters (256 pcs.)
<Point table>
64 points
Electronic thermal
Actuator overheat protection
1. Specifications
[SMF-2009-A]
― 1-7
--- MEMO ---
2. Wiring
[SMF-2009-A]
― 2- 1
2. Wiring
2.1 Panel Description
Fig. 2.1 TS type and TH type DeviceNet specifications driver panel
Control power LED
CN4 Main power supply
Transmission monitor LED
CN1 RS -232C connector
DIP switch for gain 1 adjustment
(convergence time)
Motion display
7-segment LED (2 digits)
CN5 Actuator output terminal
Nameplate
Ground terminals (2 × M4)
TB3 Emergency stop terminal
CN3 Communication connector for DeviceNet
Main power LED
CN4 Control power supply
TB2 Brake terminal
TB1 Safety function terminal
CN2 Resolver cable connector
DIP switch for gain 2 adjustment
(load)
2. Wiring
[SMF-2009-A]
― 2- 2
Fig. 2.2 XS type DeviceNet specifications driver panel
Note *1: The safety function (TB1) of this product does not comply with the safety standards.
Control power LED
CN4 Control power supply
CN5 Actuator output terminal
Nameplate
Ground terminals (2 × M4)
Motion display
7-segment LED (2 digits)
CN3 Communication connector for DeviceNet
CN2 Encoder cable connector
DIP switch for gain 1 adjustment
(convergence time)
TB2 Brake terminal
Transmission monitor LED
CN1 RS -232C connector
DIP switch for gain 2 adjustment
(load)
TB1 Safety function terminal*1
TB3 Emergency stop terminal
CN4 Main power supply
Main power LED
2. Wiring
[SMF-2009-A]
― 2- 3
2.2 Communication Connector
The pin layout of DeviceNet communication connector CN3 is shown below.
Fig. 2.3 Pin layout of communication connector
Table 2.1 Pin layout of CN3
Pin
Signal name
Function
Description
1
V-
Communication
power (-)
Power supply (11 to 25 VDC) with less
noise is used.
2
CAN_L
Communication
terminal (L)
This terminal is connected to the
communication line "CAN_L" of the
master station or other slave station.
3
Drain
Shield terminal
The shield line of the cable is connected
to this terminal.
4
CAN_H
Communication
terminal (H)
This terminal is connected to the
communication line "CAN_H" of the
master station or other slave station.
5
V+
Communication
power (+)
Power supply (11 to 25 VDC) with less
noise is used.
It is not connected with the drain (shield terminal) and ground terminal (heat sink section)
of the driver.
We recommend the use of cables and connectors dedicated for DeviceNet.
If this product is the termination of the network, connect a terminating connector between "CAN_L"
and "CAN_H".
5
4
3
2
1
CAN_H (White)
SHIELD (Bare)
CAN_L (Blue)
V- (Black)
Up
V+ (Red)
2. Wiring
[SMF-2009-A]
― 2- 4
2.3 Connecting the Communication Cable
Follow the procedure below to connect the special DeviceNet cable to the module.
[1] Peel the sheath of the cable off without causing a broken wire (length of peeled cable sheath:
7 mm).
Do not solder the bare cable. Otherwise poor continuity may be caused. The solderless
terminals specified below are recommended.
Select a solderless terminal that matches the size of the cable.
Note that the peeling dimension of the cable sheath varies according to the type of the
solderless terminal.
Fig. 2.4 Peeling dimension of communication cable
7mm
Device Net 専用ケーブル
ドレイン線
0mm程度
◇圧着端子を使用しない場合
About 30 mm
If solderless terminals are not used
DeviceNet specific cable
Drain
圧着端子に
合わせた長さ
ケーブル
電線
(ねじらない)
<1本差込み用>
圧着端子
名:ラスチッ
棒端子
型番:AI シリーズ
メーカ:フェニックス・コンタクト
圧着端子専用工具
品名:圧着工具
型番ZA 3
メーカ:フェニックス・コンタクト
<2本差込み用>
圧着端子に
合わせた長さ
ケーブル
電線
(ねじらない)
圧着端子
名:ラスチッ
TWIN 棒端子
型番:AI-TWIN シリーズ
メーカ:フェニックス・コンタクト
圧着端子専用工具
品名:圧着工具
型番:ZA 3
メーカ:フェニックス・コンタクト
◇圧着端子を使用する場合
<To insert two cables>
If solderless terminals are used
<To insert a single cable>
Electric wire
(Do not twist)
Electric wire
(Do not twist)
Cable
Cable
Solderless terminal
Part name: Solderless terminal
Model number: AI series
Manufacturer: Phoenix Contact
Special tool for solderless terminal
Part name: CRIMPFOX
Model number: ZA3
Manufacturer: Phoenix Contact
According to the length of the
solderless terminal
According to the length of the
solderless terminal
Solderless terminal
Part name: TWIN terminal with plastic
insulation collar
Model number: AI-TWIN series
Manufacturer: Phoenix Contact
Special tool for solderless terminal
Part name: CRIMPFOX
Model number: ZA3
Manufacturer: Phoenix Contact
2. Wiring
[SMF-2009-A]
― 2- 5
[2] Insert the CAN_H (white), CAN_L (blue), V+ (red), V- (black), and Drain (bare) lines of the
DeviceNet cable into relevant holes (CAN_H, CAN_L, V+, V-, Drain) while referring to the
orientation of the connection connector (MSTB2.5/5-STF-5.08AUM). (For details, see the
following Figure.)
The recommended connector is MSTB2.5/5-STF-5.08AUM manufactured by Phoenix Contact.
Fig. 2.5 Connection example of communication cable
[3] Secure each line firmly using the cable fixing screws of the connection connector.
(Proper tightening torque: 0.5 N•m)
[4] Make sure that the cable colors are matched with those shown on the connector. Insert the
connection connectors into the slave station and secure them using the connector fixing screws.
(Proper tightening torque: 0.3 N•m)
Fore station
Aft station
(Black)
(Blue)
(Bare)
(White)
(Red)
(Black)
(Blue)
(Bare)
(White)
(Red)
T-branch tap
T-branch method
Multi-drop method
(Black)
(Blue)
(Bare)
(White)
(Red)
2. Wiring
[SMF-2009-A]
― 2- 6
Only one section of the drain (shielding wire) of the DeviceNet cable must be grounded to avoid
ground loop problems. Also, ground the wire as close to the center of the network as possible.
Primary AC power supply for the communication power supply must not be used among
components such as motors and inverters. Those components must be driven by control
power supply instead. Always insert a noise filter to the AC power supply input section as
well.
For details of the laying of the communication cable, refer to the DeviceNet Laying Manual, etc.
CAUTION
Be sure to use special signal cables complying with the DeviceNet specifications.
For those provided with a connector fixing screw, securely tighten the connector fixing
screw when inserting the connector. Otherwise the connector may be dislocated and cause
malfunction.
For those not provided with a connector fixing screw, check that the catch of the connector
snaps in position.
Before disconnecting the connector, loosen the fixing screws (2 places) sufficiently.
For those not provided with a connector fixing screw (2 places), check that the catch of
the connector snaps in position. Loosen the fixing screws before removing the
connector. The connector may be damaged if excess force is applied to the connector
without the screws loosened.
Remove the connector vertically to avoid excess force from being applied to the
connector.
Do not bend the communication cable forcibly. Assure a sufficient bending radius.
Reserve a sufficient distance between the communication cable and power cable
(motor cable).
If the communication cable is routed near the power cable or if they are tied, noise will
enter to make communication unstable, possibly causing frequent communication
errors and/or communication retries.
Use in the RUN mode to output signals from the PLC and drive ABSODEX.
Before switching, check that other devices do not malfunction unexpectedly.
2. Wiring
[SMF-2009-A]
― 2- 7
2.4 IO Interface
Connect "emergency stop input (TB3)" in the following way.
2.4.1 Wiring of emergency stop input (TB3)
Rated voltage 24 V ±10%, rated current within 5 mA
Fig. 2.6 Connection example of emergency stop input (TB3)
The emergency stop input will be effective as default setting. Refer to the "Instruction Manual
for AX Series TS, TH, XS Types" (SMF-2006) for setting instructions.
Emergency stop is a "b" contact input. Thus it will take effect when emergency stop input
(TB3) becomes open.
Emergency stop using DeviceNet communication will be effective when the input data is OFF.
Fig. 2.7 Specification of emergency stop input
Tow inputs, input terminal TB3 and DeviceNet communication CN3, are provided for the
emergency stop inputs, and if one of the inputs becomes open (or OFF), it will be recognized
as emergency stop.
Input to TB3 is necessary to release the emergency stop.
Fig. 2.8 Applicable cable to TB3 and peeling size
The cable sheath peeling length should be 8 to 9 mm.
The applicable cable is AWG20 to 24 (single cable) or AWG20 to 22 (stranded cable).
EMG+
EMG-
+24V
※外部供給電源の極性を
  反転しても接続可能です。
TB3:非常停止入力
I/O
CN3:非常停止入力
(シリアル通信)
非常停止処理
入力処理:
  どちらかの入力が
 オープン(またはOFF)に
 なると非常停止
シリアル通信処理
ABSODEX
Serial communication
processing
CN3: Emergency stop input
(serial communication)
Emergency stop
processing
Input processing:
Emergency stop is
triggered when either
input is open (or OFF).
TB3: Emergency stop input
(I/O)
External power supply
24 VDC
(Prepared by
customer)
8 to 9 mm
* Connection is possible even if the polarity
of the external power supply is reversed.
AWG20 to 24 (single cable)
AWG20 to 22 (stranded cable)
*
3. DeviceNet Communication Function
[SMF-2009-A]
― 3- 1
3. DeviceNet Communication Function
3.1 Communication Specifications
Table 3.1 Communication specifications
Item
Specifications
Power voltage
(communication power)
11 to 25 VDC
Consumption current
(communication power)
50 mA or less
Communication
Protocol
DeviceNet conformed (remote I/O)
Number of occupied
nodes
Input 8 bytes / output 8 bytes
Communication speed 500 k / 250 k / 125 kbps
(select by parameter setting)
Connection cable DeviceNet compatible cable
(shielded 5-wire cable: 2 signal lines, 2
power lines, 1 shield)
Node address 0 to 63 (configured with parameter)
Number of connected
modules
Max. 64 stations (including master)
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48