  • Hello! I am an AI chatbot trained to assist you with the Danfoss EVUL, EVU, EVUB and EVUF - 032R9551 Installation guide. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
Correct position
Warning
Never swich on power
to the coil when it is
dismounted from the valve.
There is a danger the coil
may be damaged and a risk
of injuries and burns.
Installation Guide
Solenoid Valve
Types EVUL 1 – EVUL 8, EVU 1 – EVU 8, EVUB and EVUF
DKRCC.PI.BD0.C5.02 / 520H7456 1
032R9551
032R9551
Refrigerants:
R744, R22/R407C, R404A/R507,
R410A, R134a, R407A, R23.
For other refrigerants, please
contact Danfoss.
Max. opening dierential
pressure MOPD:
Coil dependent
Note!
Danfoss recommends that a suitable
lter or lter drier (max. size of
40–50µm) is installed ahead of each
solenoid valve to keep scale, solder
material and other foreign dirt and
particles out of the valve.
Be sure that
the O-ring is
in place
Max. temperature of medium:
-40 – 105 °C (-40 – 220 °F)
Ambient temperature:
-40 – 60 °C (-40° – 140 °F)
Max. working pressure PS/MWP:
– EVUL 1-8: 90 barg / 1305 psig
– EVU 1-8: 70 barg / 1015 psig
– EVUB and EVUF: 45.2 barg / 655 psig
Click!
To ensure correct sealing between coil
and valve make sure that the coil is fully
clicked on to the valve.
Valve connection:
2 - 5 sec.
Cobber tube:
10 - 15 sec.
Valve connection:
max. 700 °C (1300 °F)
Warning
Never swich on power to
the coil when it is
dismounted from the valve.
There is a danger the coil
may be damaged and a risk
of injuries and burns.
© Danfoss A/S (AC-MCI sw) 2013-02
Installation Guide
DKRCC.PI.BD0.C5.02 / 520H7456 2
032R9551
032R9551
Solenoid Valve – US coil
Types EVUL 1 – EVUL 8, EVU 1 – EVU 8, EVUB and EVUF
Be sure that there
is no O-ring!
ø3.5 mm
(0.14 in.)
/