Danfoss EVU 1 to 8 Normally Closed (NC) Installation guide

Type
Installation guide
Warning
Never switch on power to the coil when the
coil is dismounted from the valve. Otherwise
the coil may be damaged and there is risk of
injuries and burns.
Installation Guide
Solenoid Valve – US version
Types EVU 1 – 8, EVUB and EVUF NC (Normally Closed)
© Danfoss A/S (AC-MCI / jmn), 2012-12 DKRCC.PI.BD0.A2.22 / 520H6991 1
032 R95 26
032 R95 26
Refrigerants:
R744, R22/R407C, R404A/R507,
R410A, R134a, R407A, R23.
For other refrigerants,
please contact Danfoss.
Max. opening dierential pressure MOPD: Coil dependent
Max. working pressure PS/MWP:
– EVU 1 – 8: 70 barg/1015 psig
– EVUB and EVUF: 45.2 barg/655 psig
Max. temperature of medium: -40 – 105 °C (-40 – 220 °F)
Ambient temperature: -40 – 60 °C (-40 – 140 °F)
ø3.5 mm
(0.14 in.)
max. 700 °C (1300 °F)
Valve connection:
10 – 15 Sec
.
2 – 5 Sec.
Valve connection:
Cobber tube: