Danfoss AKV 15 / AKVA 15 Installation guide

  • Hello! I am an AI chatbot trained to assist you with the Danfoss AKV 15 / AKVA 15 Installation guide. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
Warning
Never switch on
power to the coil
when the coil is
dismounted from
the valve. Otherwise
the coil may be
damaged and there
is risk of injuries and
burns
.
Installation Guide
Electrically Operated Expansion Valve
Types AKV 15, AKVA 15
© Danfoss A/S (AC-MCI / jmn), 2012-12 DKRCC.PI.VA1.C2.53 / 520H6980 1
068R9548
068R9548
Ambient temperature range:
-40 °C < t
amb
< 50 °C
-58 °F < t
amb
< 120 °F
Media temperature range:
-50 °C < t
media
< 60 °C
-58 °F < t
media
< 140 °F
AKV 15
max. 150 °C (300 °F)
DCR
100 μm
max. 700 °C (1300 °F)
AKVA 15
Clip-on
coil
Refrigerants
AKV 15 R744, R22/R407C, R404A/R507, R410A, R134a, R407A, R23.
AKVA 15
R744, R717, R22/R407C, R404A/R507, R410A, R134a, R407A,
R23. For other refrigerants, please contact Danfoss.
Max. working
pressure
AKV 15-1
PS = 42 barg/MWP 610 psigAKV 2
AKV 3
AKV 15-4 PS = 28 barg/MWP 406 psig
AKVA 15 PS = 42 barg/MWP 610 psig
Max. test pressure P
e
= 47 barg/680 psig
Max. dierential pressure
MOPD = P
1
- P
2
= 20 bar/290 psi
max. 150 °C (300 °F)
(en-gb) Do not insulate
(da) Må ikke isoleres
(de) Nicht isolieren
(fr) Ne pas isoler
(es) No encerrar para
evitar condensación
2 DKRCC.PI.VA1.C2.53 / 520H6980 © Danfoss A/S (AC-MCI / jmn), 2012-12
75 Nm
10 Nm
12 Nm
en-gb da de fr es
The gasket must be
exchanged, if the valve
is dismantled.
Pakningen skal skiftes,
hvis ventilen adskilles.
Bei Zerlegung des
Ventils muß dieDichtung
ausgewechselt werden.
Changer le joint
chaque fois que la
vanne est démontée.
Es preciso cambiar la
junta si se desmonta la
válvula
/