  • Hello! I've reviewed the installation instructions for the FläktGroup LQBB outdoor unit. This document covers essential aspects such as delivery, mounting on foundations, block jointing, and roof installation. I'm here to assist with any questions you might have regarding these procedures or the unit itself.
  • How is the LQBB unit delivered?
    What is the maximum spacing of plinths when mounting the unit?
    How are the blocks connected together?
FläktGroup DC_9131GB 20180416_R0 Specifications are subject to alteration without notice
LQBB – GENERAL INSTRUCTIONS,
OUTDOOR VERSION
INSTALLATION INSTRUCTION
~ 1500
DELIVERY
The LQBB unit is delivered as a single unit, i.e. factory-assembled unit
with roof and mounted on a base frame. The unit can also be delivered as
individual blocks with roof and mounted on a base frame for assembly at
the building site.
MOUNTING ON THE FOUNDATION
For connection of the duct to the underside of the unit, accessability must
be provided from underneath. If the unit is mounted on plinths, the
spacing of the plinths in the longitudinal direction of the unit must not
exceed 1.5 m.
Fig. 1
Size 60 62, 71, 80 64, 73, 82 84
A2050 2650 3250 4000
3154 12;3(A) EUB(A,B) FIG 3
Fig. 2
A
30 30
3154 12;4 EUB(A,B) F
150
120 120
Beams
Plinths
max. 1,5 m
max. 1,5 m
Separate, tightly sealed
roof duct for connecting
ducts max. 1.5 m
ANCHORING OF LQBB OUTDOORS
8 x 100 x 100 M6S-TT 8 x 20 (Taptite)
L 50 x 50 x 5
Fig. 3
Fig. 4
2
Installation instruction
FläktGroup DC_9131GB 20180416_R0 Specifications are subject to alteration without notice
Fig. 5
EUGA 20
15 x 5
Screw
Bushing
Screw
Bushing
Fig. 7
3154 6;1 EUGB FIG 35
Justerad 20.3.95
Fig. 8
15 x 5 mm sealing
strip, supplied
Fig. 9
3154 6;2 EUGB FIG 35
M 10 x 160 M10
Supplied
Compress seal
to 1–2 mm
Fig. 6
CONNECTING MULTI-FUNCTION BLOCKS
Sealing strip is supplied loose and must thus be fitted before the blocks
are connected together. See Fig. 4 and 5.
JOINTING OF BLOCKS
Internal bolted joints at the bolt lugs fitted along the frame are used for
jointing the blocks to one another. Access to the inside of the casing can
be gained either by opening an inspection door or by removing a wall
panel. Some of the unit sections, such as the filter section, may be
dismantled for better access.
1. Fit the sealing strips supplied to the frame of one of the blocks.
2. Push the blocks towards one another, making sure that they are well
lined up with one another.
3. Fit the joint bolts into the corner brackets on the inside of the frame and
make sure that they are firmly in position.
4. Tighten all four bolts alternately, compressing the seal to 1–2 mm, see
the figures below.
TO REMOVE INDIVIDUAL PANELS
3
Installation instruction
FläktGroup DC_9131GB 20180416_R0 Specifications are subject to alteration without notice
TO FIT THE ROOF JOINT
The LQBZ-01 roof is fitted to each individual unit at the factory as shown in
Fig. 10.
Roof joint to be fitted on site when multi-function blocks are delivered.
On size 60–84 units, place the cover trim on the joint where the folded
edges of the roof sections meet and secure it by applying light hammer
blows to ”snap” it on.
PG slip clamp, to be fitted
over the joints between
the units (supplied)
PG slip clamp,
factory-mounted
Roof panel
End plate
Delivery
unit
Delivery
unit
PG slip clamp, sizes 60–84, to
be fitted over the joints
between the
units (supplied)
Center the PG slip clamp so that
its right-hand end extends
equally as much as its left-hand
end from the edge of the roof.
Then bend the clip clamp ends
over the edge of the roof.
Secure the end pieces using self-threading
screws.
Fig. 10
Fig. 11
Secured roof joint
/